Rogowski Coil Current Sensors for Retrofit Metering
Product Specifications
Product Overview
A Rogowski coil is a toroidal winding with no magnetic core. The conductor passes through the loop, the changing flux induces a voltage proportional to the rate of change of current, and the meter integrates that signal back into a current reading. With no core there is nothing to saturate, which is why one coil covers 100 A to 15,000 A at 0.5 % linearity instead of the narrow band a iron core transformer handles well. The same property explains the very low phase shift, under 0.5 degrees, that a power or power factor reading needs.
The practical value on site is that the coil opens at the connector junction. It closes around a cable or a busbar that is already installed, with no shutdown, no disconnection and no cutting of the bar. The loop is thin and flexible, so it passes through a cable duct or behind a breaker where a split core transformer will not fit. On a retrofit the coil is often the only way to add a measurement point without a planned outage, and the IP68 rating on the standard coil means the loop can sit in a damp enclosure or an outdoor cabinet.
The output is a voltage, not a current, so the second decision is where the integration happens. A meter built for Rogowski inputs integrates internally and is set to 70 mV per 1,000 A, which is the native scale of these coils. A meter with a 0.333 V input needs an integrator between coil and meter, and the integrator needs a supply, 12 to 30 V AC or DC on the 4800 series, 9 to 36 V DC on the 180L series. Getting that pair right is the whole job: the coil is linear, and a wrong scale factor shows up as a reading that is out by a fixed ratio rather than as an unstable number.
A Rogowski coil measures AC only. It has no response to a steady DC current, so it is not a substitute for a shunt in a battery or DC bus measurement. It is also sensitive to the position of the conductor inside the loop: the winding is uniform, but a conductor pressed against the inner wall, or a return conductor running outside the loop, adds error. Centre the conductor, close the gap cleanly and keep the adjacent phase outside the loop, and the 0.5 % figure holds. Those three habits matter more than the choice between one coil size and the next.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Rated primary current | 100 A to 15,000 A | RCT standard series, 5,000 A on the 180L series |
| Rated output | 0.070 V per 1,000 A at 60 Hz | 58.33 mV per 1,000 A at 50 Hz |
| Output with integrator | 0.333 V AC | single phase integrator, 12 to 30 V AC or DC supply |
| Linearity | 0.5 % class per IEC 61869-2 | stated from 100 A to 15,000 A |
| Phase displacement | below 0.5 degrees | matters for power and power factor |
| Frequency range | 30 Hz to 1,000 Hz | covers harmonics through the audio band |
| Coil protection | IP68 per IEC 60529 | IP64 on the 180L series |
| Maximum voltage | 600 V on a bare conductor, BIL 10 kV | insulation test 10 kV AC for one minute |
| Lead length | 8 ft, 24 AWG | rated 600 V |
| Operating temperature | -15 to +65 C | storage -45 to +80 C, UL ambient 55 C |
| Humidity | 85 % relative, UL rating | sealed coil |
| Weight | 0.15 kg standard coil | 0.18 kg on the 180L series |
| Approvals | UL 61010-1, CSA C22.2 No. 61010, IEEE C57.13 | UL 2808 on the 180L series |
| Integrator supply | 12 to 30 V AC or DC | 9 to 36 V DC on the 180L series |
Included Models and Order Codes
The coil diameter sets the largest conductor bundle that fits. A 4.0 inch loop takes a single cable, 6.0 and 8.0 inch loops take a three phase bundle, and 12.0 or 16.0 inch loops take a busbar or a bundle with a sheath. All sizes share the same 0.070 V per 1,000 A output, so a meter setting does not change when the coil is swapped for a larger one. RCT-4800-000 is supplied as a coil only, without the integrator, for meters that integrate internally. The 180L series is the UL listed version, rated to 5,000 A with a 9 to 36 V DC integrator supply and an IP64 coil, and it covers the same 4.0 to 12.0 inch diameters under the RCT-120L to RCT-360L codes.
| Type | Coil size | Rated current | Output | Note |
|---|---|---|---|---|
| Magnelab RCT-1200-Coil | 4.0 inch diameter | up to 15,000 A | 0.070 V per 1,000 A | single cable, tight enclosures |
| Magnelab RCT-1800-Coil | 6.0 inch diameter | up to 15,000 A | 0.070 V per 1,000 A | three phase cable bundle |
| Magnelab RCT-2400-Coil | 8.0 inch diameter | up to 15,000 A | 0.070 V per 1,000 A | bundle with sheath |
| Magnelab RCT-3600-Coil | 12.0 inch diameter | up to 15,000 A | 0.070 V per 1,000 A | busbar and large bundles |
| Magnelab RCT-4800-000 | 16.0 inch diameter, 48 inch length | 250 to 15,000 A | 0.070 V per 1,000 A | coil only, integrator separate |
| Magnelab RCT-120L-Coil | 4.0 inch diameter | up to 5,000 A | 0.070 V per 1,000 A | UL 2808, 9 to 36 V DC integrator |
| Magnelab RCT-180L-Coil | 6.0 inch diameter | up to 5,000 A | 0.070 V per 1,000 A | UL 2808, 9 to 36 V DC integrator |
| Magnelab RCT-240L-Coil | 8.0 inch diameter | up to 5,000 A | 0.070 V per 1,000 A | UL 2808, 9 to 36 V DC integrator |
| Magnelab RCT-360L-Coil | 12.0 inch diameter | up to 5,000 A | 0.070 V per 1,000 A | UL 2808, 9 to 36 V DC integrator |
Coil Output Against Primary Current
The table converts the 0.070 V per 1,000 A scale into the millivolts a meter sees at common currents, at 60 Hz and at 50 Hz. The 50 Hz column is 0.833 of the 60 Hz value because the output follows frequency, which is the reason a meter set for 60 Hz reads low on a 50 Hz system unless the setting is changed. An integrator brings the same currents to a 0.333 V full scale output, so the meter is configured for its input range rather than for the coil.
| Primary current | Output at 60 Hz | Output at 50 Hz | With integrator |
|---|---|---|---|
| 100 A | 7.0 mV | 5.8 mV | scaled to the 0.333 V input |
| 250 A | 17.5 mV | 14.6 mV | scaled to the 0.333 V input |
| 500 A | 35.0 mV | 29.2 mV | scaled to the 0.333 V input |
| 1,000 A | 70.0 mV | 58.3 mV | 0.333 V at rated range |
| 2,500 A | 175.0 mV | 145.8 mV | scaled to the 0.333 V input |
| 5,000 A | 350.0 mV | 291.7 mV | scaled to the 0.333 V input |
| 10,000 A | 700.0 mV | 583.3 mV | scaled to the 0.333 V input |
| 15,000 A | 1,050.0 mV | 875.0 mV | scaled to the 0.333 V input |
Key Features
No core to saturate – the winding has no magnetic core, so a fault current does not push the coil into saturation and the reading stays linear across the whole range.
0.5 % linearity from 100 A – the accuracy figure is quoted across the working range, not at one current, so a reading at a light load is as trustworthy as a reading at full load.
Opens around a live conductor – the loop separates at the connector and closes around a cable or bar that is already in service, which removes the outage a conventional transformer needs.
IP68 sealed coil – the loop is sealed for damp enclosures and outdoor cabinets, and it is thin enough to pass through a cable duct.
Two output scales – 0.070 V per 1,000 A at the coil and 0.333 V after an integrator, so both a Rogowski input meter and a standard voltage input meter can be served.
Phase shift under 0.5 degrees – the low phase displacement keeps power and power factor readings honest at low power factor, where a small angle error becomes a large number.
30 Hz to 1,000 Hz – the coil reads the harmonic content that a 50 or 60 Hz transformer filters out, which is what a power quality study needs.
0.15 kg coil – the whole sensor weighs less than a hand tool, so it hangs on its own lead without a support bracket.
Applications
Three places where a coil that opens around an installed conductor does work a transformer cannot.
Retrofit submetering – a tenant metering point added to an existing riser, where the busbar cannot be shut down and a split core transformer will not fit around the bar.
EV charging and generator output – a feeder that carries a high fault current, where a core based transformer would need a much larger frame to stay linear at the top of the range.
Power quality surveys – a temporary or permanent measurement on a drive or a rectifier, where the harmonic content above the fundamental is part of the question.
Switchgear condition monitoring – a coil left in place around a busbar to log load current, with no secondary open circuit risk if the lead is disconnected.
On a control board that carries the meter, the SUPERB PCBA and the SUPERB PCB are checked against the same coil scale and the same meter constant, so the logged current matches the panel drawing.
Sourcing and Cross-Reference
A Rogowski replacement is decided by four numbers: the largest conductor the loop must pass, the highest current to be read, the meter input scale, and whether the meter integrates internally. The first sets the coil diameter, the second sets the series, 15,000 A for the standard RCT and 5,000 A for the UL listed 180L, the third sets 70 mV per 1,000 A or 0.333 V, and the fourth decides whether an integrator is needed at all. A coil bought without checking the meter scale reads by a fixed factor, which is easy to correct in software but easy to miss on a bill.
Where the conductor cannot be centred, or where a return conductor runs close to the loop, the reading carries an error that no calibration removes. In that case the answer is a larger loop that clears the adjacent conductors, or a fixed split core transformer with a known burden. A Rogowski coil is the right part for an AC retrofit with a wide current range and a crowded enclosure, and the wrong part for a DC bus or a measurement that needs class 0.2 revenue accuracy.
For a panel waiting on one coil, the lead time question is usually about the integrator rather than the loop. See lead time and availability for a specific diameter, or BOM shortage recovery when a meter is already on site and only the sensor is missing.
The SUPERB Assembly team labels each coil lead with its diameter and its scale factor, because two coils of different sizes look the same once the loop is closed.
Q: Can a Rogowski coil replace a 400/5 transformer in an existing panel without cutting the busbar?
A: Yes. The loop opens at the connector and closes around the bar without an outage. Send the bar size, the maximum current and the meter input scale, and the SUPERB Tech team returns the coil diameter and whether an integrator is needed.
Why Panel Builders Source Rogowski Coils Through SUPERB
- Coil size chosen from the conductor: the diameter table is written against the conductor bundle, 4.0 inch for a single cable up to 16.0 inch for a busbar, so the loop is not ordered one size too small.
- Output scale stated twice: the native 0.070 V per 1,000 A and the 0.333 V integrated output are both on the page, which is the pair a meter setting has to match.
- Phase and frequency given: under 0.5 degrees and 30 Hz to 1,000 Hz are listed, because those two numbers decide whether a power reading or a harmonic survey is valid.
- Sealed coil and lead rating: IP68 and a 600 V lead are on the row, so a damp cabinet or a 480 V bar is checked before the order rather than after installation.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Current Transformers and AC Current Sensing for Energy Metering, Protection Current Transformers for Overcurrent Relays, Metering Current Transformers for Panel and Switchgear, Multifunction Power Meters and Power Quality Analyzers, DIN Rail kWh Meters for Panel Energy Monitoring, Insulation Monitoring Devices for Unearthed Systems, Component Lead Time Solutions.