Metering Current Transformers for Panel and Switchgear
Product Specifications
Product Overview
Every meter on a feeder reads through a current transformer, and the transformer is the part that sets the accuracy of the measurement. The core is chosen on the primary current, the secondary is 5 A or 1 A, and the class is quoted at a burden: class 0.5 at 2 VA means the transformer holds its error while the meter and the wiring together draw 2 VA. Fit a meter with a larger burden and the class falls to 1 or 3 before the current reaches the top of the range.
The burden is not the meter alone. The leads from the transformer to the meter carry the secondary current, and their resistance adds to the burden in proportion to their length. On a 5 A secondary, 2 VA allows 0.08 ohm in the whole loop, which at 2.5 square millimetres copper is about 5.4 m of one way run. A transformer in a remote compartment with 12 m of lead is outside that window, and the answer is a larger VA rating or a shorter run rather than a better meter.
The second number that matters on switchgear is the thermal rating. A 6 kA conventional thermal current with a dynamic rating of 2.5 times that is what keeps the transformer together during a fault, and the safety factor of 5 means the secondary current is limited to five times rated when the primary carries its thermal current. That factor is the reason a metering transformer is not used with an overcurrent relay that needs a faithful reproduction of a fault current.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Primary current | 100, 150 and 200 A | other ratios on request |
| Secondary current | 5 A | 1 A versions on request |
| Accuracy class | class 0.5 at 2 VA, class 1 at 2.5 VA, class 3 at 3.5 VA | the class follows the burden connected |
| Rated operational voltage | below 720 V AC, 50 or 60 Hz | low voltage panels and switchgear |
| Thermal current | 6 kA conventional, free air | one second thermal rating of the primary |
| Dynamic withstand | 2.5 times the thermal current | 15 kA peak |
| Safety factor | 5 | secondary current limited to five times rated |
| Insulation | 3 kV rated insulation, 3 kV impulse withstand | test at 3 kV for one minute |
| Window | 21 mm cable diameter | cable type, tropicalised |
| Dimensions | 44 mm wide, 65 mm high, 30 mm deep frame, 37 mm overall | fits a 44 mm pitch row |
| Mounting | screw fixing or clip on | mounting plate or 35 mm DIN rail |
| Degree of protection | IP20 | installed inside the enclosure |
| Ambient temperature | -25 to +60 C | class B insulation |
| Standards | VDE 0414, IEC 61869-2 | CE and EAC marked |
| Weight | 0.19 kg | one unit per feeder |
Included Models and Order Codes
The three types below are the same core in three ratios, and the code carries the primary current in its last three digits. METSECT5CC010 is 100/5, CC015 is 150/5 and CC020 is 200/5, all with the same 21 mm window and the same 6 kA thermal rating. The ratio is the only difference that shows on the panel schedule, but the meter has to be set to it: a meter left at 100/5 behind a 200/5 transformer reads half the current and the energy register follows.
| Type | Ratio | Thermal current | Window and class |
|---|---|---|---|
| Schneider METSECT5CC010 | 100/5 | 6 kA, dynamic 15 kA | 21 mm window, class 0.5 at 2 VA |
| Schneider METSECT5CC015 | 150/5 | 6 kA, dynamic 15 kA | 21 mm window, class 0.5 at 2 VA |
| Schneider METSECT5CC020 | 200/5 | 6 kA, dynamic 15 kA | 21 mm window, class 0.5 at 2 VA |
Burden and Lead Length at a 5 A Secondary
The burden a transformer can carry is shared between the meter and the leads. The table converts the class burden into the maximum loop resistance and into a one way lead length at 2.5 square millimetres copper, calculated with a loop of twice the run length. A meter rated 1 VA with 6 m of lead already uses more than half of the 2 VA window, which is why the lead length belongs on the metering drawing.
| Class and burden | Maximum loop resistance | One way length at 2.5 mm squared | Room left for the meter |
|---|---|---|---|
| Class 0.5 at 2 VA | 0.080 Ohm | 5.4 m | 2 VA less the lead loss |
| Class 1 at 2.5 VA | 0.100 Ohm | 6.7 m | 2.5 VA less the lead loss |
| Class 3 at 3.5 VA | 0.140 Ohm | 9.4 m | 3.5 VA less the lead loss |
| 1 A secondary, 2 VA | 2.0 Ohm | 135 m | a 1 A core carries a much longer run |
Key Features
Class stated at a burden – the class is quoted at 2 VA, 2.5 VA and 3.5 VA, so the accuracy on the drawing is the accuracy the panel reaches.
6 kA thermal rating – the primary carries a fault current long enough for the upstream device to clear, and the dynamic rating is 2.5 times that.
21 mm window – cable primaries up to 21 mm pass through, which covers the LV feeder sizes in most panels.
44 mm width – the housing fits a 44 mm pitch, so three transformers sit in a row above a three phase meter.
DIN rail or plate mounting – the clip on foot and the screw holes are both on the housing, which matters in a retrofit where the plate is already drilled.
Safety factor 5 – the secondary is limited to five times rated, which protects the meter but rules the transformer out for a protection core.
Tropicalised core – the winding is finished for humid enclosures, which is the usual condition inside a switchgear room.
Applications
Three metering points where the transformer, not the meter, is the limiting part.
Feeder sub metering – a 100/5 transformer on a 63 A feeder keeps the meter inside its range at full load and still reads at night, where a direct connected meter would lose resolution.
Switchgear incomer metering – a 200/5 transformer with a class 0.5 meter gives a billing grade reading, provided the lead run stays inside the burden window.
Panel retrofit with a 5 A meter – an existing meter with a 5 A input can be kept where the transformer is replaced with the same ratio and a matching burden.
Where the metering point sits on a control board, the SUPERB PCBA and the SUPERB PCB are reviewed against the same transformer ratio and the same meter constants, so the readings agree with the drawing.
Sourcing and Cross-Reference
A transformer replacement is decided by three numbers on the drawing: the primary current, the secondary current and the burden. The ratio has to match the meter setting, and the burden has to cover the meter plus the leads. Where the original transformer is unmarked, the ratio can be found by passing a known current through the primary, and the class can only be assumed from the meter it served.
The second question is the window. A 21 mm window passes a cable primary but not a busbar, and a busbar metering point needs a split core or a bar primary type. The third is the thermal rating: a feeder with a high fault level needs a transformer rated for it, and a 6 kA unit on a 25 kA bus is the wrong part whatever the ratio.
For a panel waiting on one transformer, the options are the next ratio up with the meter reset, a 1 A secondary core where the lead run is long, or a split core where the cable cannot be disconnected. See lead time and availability for a specific ratio.
The SUPERB Assembly team marks the ratio on the secondary lead and records it on the panel schedule, because a crossed secondary on a live transformer is an open circuit with a dangerous voltage across it.
Q: Can you confirm the ratio, the burden and the lead length our metering point allows before we replace a transformer?
A: Yes. Send the primary current, the secondary current, the meter burden and the lead length, and the SUPERB Tech team returns the ratio and the class that hold at that point.
Why Panel Builders Source Metering Transformers Through SUPERB
- Class tied to burden: the three class and burden pairs are on the page, so a class 0.5 requirement is not quoted as a class 3 core at a larger burden.
- Thermal rating stated: the 6 kA thermal and 15 kA dynamic figures are listed, which is the check a switchgear feeder needs and a metering data sheet often omits.
- Lead length converted: the burden table turns VA into metres of 2.5 square millimetre copper, which is the number that decides whether the class holds in the panel.
- Window and width given: 21 mm and 44 mm are on the row, so a cable primary and a 44 mm pitch row are confirmed before the order.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Current Transformers and AC Current Sensing for Energy Metering, Multifunction Power Meters and Power Quality Analyzers, DIN Rail kWh Meters for Panel Energy Monitoring, Residual Current Devices for Panel Feeders, Digital Panel Meters and Counters for Control Panels, Component Lead Time Solutions.