Multifunction Power Meters and Power Quality Analyzers
Product Specifications
Product Overview
A panel needs voltage, current, power, power factor and energy, and the traditional answer is four instruments and a selector switch. A multifunction meter measures all of them from one set of inputs, calculates the derived quantities, and holds a log that a single function meter cannot. On a modern panel it also becomes the metering point for a building or plant monitoring system, which is where the communication port and the accuracy class start to matter more than the display.
The accuracy class is the first decision because it is tied to what the reading is used for. Class 0.5S is the normal choice for sub metering and internal cost allocation, and class 0.2S is what a utility or a landlord accepts for billing. The difference is the error at low current: an S class meter keeps its accuracy down to a small fraction of the rated current, which is why a class 1 meter that reads well at full load can be several percent out on a lightly loaded feeder at night.
The second decision is the current input. Most meters take a 5 A or 1 A secondary from a current transformer, and the transformer class sets the accuracy of the whole measurement: a class 0.5 meter behind a class 3 transformer reads like a class 3 instrument. Harmonic analysis is the third decision, and the order range is what separates a metering type from an analyzer: 31st order covers the harmonics that carry most of the distortion, while 63rd order is needed where a drive or a rectifier injects higher orders.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Measured quantities | voltage, current, active, reactive and apparent power, power factor, frequency, energy | per phase and three phase totals |
| Energy accuracy | class 0.2S or class 0.5S to IEC 62053-22 | class 1 on the entry level types |
| Measurement accuracy | voltage and current class 0.2 to IEC 61557-12 on the network analyzer types | power class 0.5, frequency class 0.1 |
| Harmonic analysis | to the 31st order on the metering types, to the 63rd on the billing type | THD of voltage and current, individual orders |
| Voltage input | 3 phase 3 or 4 wire, up to 690 V line to line | direct connection on low voltage panels |
| Current input | 5 A or 1 A from a current transformer | Rogowski coil input on some types |
| Tariffs | 8 energy registers | time of use and remote tariff switching |
| Alarms and log | 52 alarms on the billing type, event and min max log | alarm list on the display and on the bus |
| Digital inputs and outputs | 4 digital inputs and 2 digital outputs | 4 programmable I/O on the analyzer types |
| Communication | RS485 Modbus RTU and ASCII, Modbus TCP, BACnet IP, DNP3 | two Ethernet ports for daisy chain on the billing type |
| Pulse output | 200,000 impulses per kWh on the analyzer types | for a separate energy counter |
| Display | graphic LCD, 3.5 inch on the 96 x 96 types | backlit, multi language |
| Mounting | 96 x 96 mm panel cut out | DIN rail and 144 x 144 mm types also in the range |
| Supply | 48 to 240 V AC or DC on the analyzer types | wide range supply, no separate transformer |
| Standards | IEC 62053-22, IEC 61557-12, IEC 61010-1 | MID approval on the M type |
| Ambient temperature | 0 to 50 C in operation | per type data sheet |
Included Models and Order Codes
The two families below cover the same job from different directions. The Schneider PowerLogic range starts at the entry metering type and goes up to a billing meter with two Ethernet ports and 63rd order harmonics. The ABB M4M range is a network analyzer family where the accuracy class is in the type name: M4M 30 is class 0.5S and M4M 32 is class 0.2S, and the communication port is a suffix in the order code, so the same analyzer is bought with Modbus, Ethernet, Profibus or BACnet. The M type carries MID approval for billing in the EU.
| Type | Energy class | Harmonics | Communication and notes |
|---|---|---|---|
| Schneider METSEPM5560 | class 0.2S | to the 63rd order | 2 Ethernet, Modbus RTU, BACnet IP, DNP3, 4 DI and 2 DO |
| Schneider METSEPM5350 | class 0.5S | to the 31st order | Modbus RTU, 2 relay outputs |
| Schneider METSEPM2230 | class 0.5S | to the 31st order | RS485 Modbus, LCD display |
| ABB M4M 30 Modbus | class 0.5S | THD and individual orders | 2CSG274761R4051, Modbus RTU and Bluetooth, 4 programmable I/O |
| ABB M4M 30 Ethernet | class 0.5S | THD and individual orders | 2CSG274681R4051, Modbus TCP, two RJ45 ports |
| ABB M4M 30-M Modbus | class 0.5S with MID | THD and individual orders | MID approval for billing, Modbus RTU |
| ABB M4M 32 Modbus | class 0.2S | THD and individual orders | class 0.2 voltage and current per IEC 61557-12 |
| ABB M4M 30 Profibus | class 0.5S | THD and individual orders | 2CSG236791R4051, Profibus DP-V0 |
| ABB M4M 30 Bacnet | class 0.5S | THD and individual orders | 2CSG202451R4051, BACnet IP |
What the Accuracy Class Means at Part Load
The class is a percentage of the reading, and the S in 0.2S and 0.5S is what keeps that percentage valid at low current. The table shows the error allowed at three load points for the three classes that appear on panels. A feeder that runs at 10 percent of its rating for most of the night is where the difference between a class 1 and a class 0.5S meter shows up in a monthly energy figure.
| Class | Error at full load | Error at 10 percent load | Typical use |
|---|---|---|---|
| Class 0.2S | 0.2 percent | 0.2 percent down to 1 percent of rated current | billing, utility reporting, landlord metering |
| Class 0.5S | 0.5 percent | 0.5 percent down to 1 percent of rated current | sub metering, cost allocation, ISO 50001 baselines |
| Class 1 | 1 percent | 1 percent at full load, wider spread at low load | panel indication, internal reporting |
| Class 2 | 2 percent | indication only | entry level panels |
Key Features
One unit for five readings – voltage, current, power, power factor and energy come from the same inputs, so the panel door loses four instruments and a selector switch.
Class 0.2S and 0.5S – both classes are listed with their order codes, because the class is what decides whether the reading is accepted for billing.
Harmonics to the 63rd order – the billing type reaches the orders a drive or a rectifier injects, which a 31st order meter cannot show.
Two Ethernet ports – a daisy chain through the meter removes a switch from the panel and keeps the metering link on its own segment.
Tariff registers – eight energy registers cover time of use billing without a separate tariff controller.
Alarm list on the bus – 52 alarms can be read remotely, so an overvoltage event is visible without opening the panel.
CT ratio and class stated – the current input and the transformer class sit next to the meter class, because a good meter behind a poor transformer reads like the transformer.
Applications
Three metering duties, each with a different accuracy and communication requirement.
Sub metering in a plant – a class 0.5S meter on each feeder gives a cost allocation that survives an audit, and Modbus puts the readings on the plant network without a gateway.
Tenant and landlord billing – a class 0.2S meter with MID approval is what a tenant accepts, and the tariff registers remove the manual reading.
Power quality screening – harmonic orders to the 31st or 63rd show whether a feeder needs a filter before a study is commissioned.
Where the meter is part of a control board, the SUPERB PCBA and the SUPERB PCB are reviewed against the same current transformer and the same tariff table, so the readings and the billing agree.
Sourcing and Cross-Reference
The meter is the easiest part of a metering point to replace and the easiest to get wrong. The cut out size, the supply voltage and the communication port decide the type, and the current transformer class decides whether the accuracy on the data sheet is reached in the panel. A class 0.2S meter behind a class 3 transformer is a class 3 measurement with a good display.
The second question is the protocol. A meter with Modbus RTU cannot join an Ethernet segment without a converter, and a meter with two Ethernet ports can be daisy chained without a switch. The third is the tariff structure: a site with time of use billing needs the eight register type, and a site with a single rate does not.
For a panel waiting on one meter, the options are the same class in another family, a higher class with the accuracy left as headroom, or the Ethernet version where the port is the constraint. See lead time and availability for a specific type, and BOM shortage recovery where a switchboard is held up by one instrument.
The SUPERB Assembly team records the current transformer ratio and the meter constants on the panel schedule, because a meter set to the wrong ratio is a wrong invoice every month.
Q: Can you confirm the accuracy class and the protocol our billing meter needs before we replace one in a switchboard?
A: Yes. Send the accuracy class, the current transformer ratio and class, the protocol and the cut out size, and the SUPERB Tech team returns the type that fits the point.
Why Switchboard Builders Source Meters Through SUPERB
- Class and code together: every row carries the class and the order code, so a class 0.2S requirement is not met with a class 0.5S unit and a note.
- Protocol named per type: Modbus, Ethernet, Profibus and BACnet versions are separate rows, because the port is a hardware option and cannot be added later.
- Transformer class linked: the page states that the current transformer sets the accuracy of the point, which is the failure that a meter data sheet never shows.
- Cut out and supply stated: 96 x 96 mm and the wide range supply are on the page, so a retrofit into an existing door does not need a new plate.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail kWh Meters for Panel Energy Monitoring, Current Transformers and AC Current Sensing for Energy Metering, Metering Current Transformers for Panel and Switchgear, Digital Panel Meters and Counters for Control Panels, Active Harmonic Filters for Low Voltage Networks, Reactive Power Controllers for Automatic Capacitor Banks.