Protection Current Transformers for Overcurrent Relays
Product Specifications
Product Overview
A protection current transformer is specified by four numbers written in one line: ratio, burden, class and accuracy limit factor. 200/5, 10 VA, 5P10 means a transformer that turns 200 A into 5 A, carries a 10 VA burden, and holds a composite error under 5 % while the primary carries up to ten times its rated current. The class letter P stands for protection, the 5 is the composite error in percent at the limit, and the 10 is the multiple of rated current where that limit applies. A relay that has to trip on a fault at eight times rated current needs the transformer to still be telling the truth at eight times, which is exactly what the second number guarantees.
The accuracy limit factor is quoted at the rated burden. Fit a relay and leads that draw less than the rated burden and the transformer saturates later, so the real factor is higher than the printed one. Fit more burden and the real factor falls, and the secondary current distorts before the relay expects it. The relationship is Fa = Fn x (Sin + Sn) / (Sin + Sa), where Fn is the rated factor, Sn the rated burden, Sa the actual burden and Sin the internal burden of the secondary winding. A transformer rated 5P10 at 10 VA with an internal burden of 1.75 VA works out at an actual factor of 17.4 on a 5 VA burden and 7.0 on a 15 VA burden. That single line of arithmetic explains most of the misoperation cases seen in the field.
This is where a protection core differs from a metering core. A metering transformer is built for accuracy at rated current and is deliberately saturated by a safety factor, often five, so that a fault current does not destroy the meter. A protection transformer is built for linearity far above rated current, and its low end accuracy is secondary. The two cannot be swapped: a 0.5 class metering core in a protection circuit will saturate at the fault current and the relay will see a fraction of the real current, and a 5P core in a metering circuit gives a billing error at light load.
The window and the ratio are the two mechanical decisions. A 40 mm window passes a cable primary, a 60 or 80 mm window passes a cable bundle, and a 100 to 180 mm window passes a busbar or a large bundle. The ratio is set by the load current and by the relay setting range, not by the cable size. On a feeder rated 250 A, a 300/5 transformer keeps the relay inside its setting range and leaves the transformer at 83 % of rated current at full load, which is a comfortable place for a class 5P core.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Ratio range | 100/5 to 5000/5 | intermediate ratios on request |
| Secondary current | 5 A | 1 A versions on request |
| Accuracy class | 5P10 and 5P20 | 10P10 on request |
| Rated burden | 2.5 to 35 VA | the class applies at this burden |
| Composite error at the limit | 5 % for class 5P | 10 % for class 10P |
| Ratio error at rated current | plus or minus 1 % for 5P | plus or minus 3 % for 10P |
| Phase displacement at rated current | plus or minus 60 minutes for 5P | not specified for 10P |
| Accuracy limit factor | 10 or 20 standard | 5, 15 and 30 on request |
| Inner diameter | 40, 60, 80, 100, 140 and 180 mm | cable or busbar primary |
| Frequency | 50 or 60 Hz | one core per frequency band |
| Insulation | resin cast body | dry type, no oil |
| Housing size, 40 mm window | 160 x 205 x 66 mm | TRP40 frame |
| Weight | 2.6 to 9.3 kg | by frame size |
| Standard | IEC 61869-2 | protection current transformers |
Included Models and Order Codes
The table lists the 5P10 versions with the burden that belongs to each ratio, because the burden and the ratio are chosen together. TRP40 covers 100/5 to 500/5 in a 40 mm window, TRP60 covers 150/5 to 1000/5 in a 60 mm window, and the TRP80 to TRP180 frames continue to 5000/5 with windows up to 180 mm. Every ratio is also available in class 5P20 under a P502xx code, which is the right choice where the fault level is high and the relay setting is low. Where a relay is already installed, the burden it presents plus the lead resistance decides whether the 5P10 version is enough or the 5P20 is needed.
| Type | Ratio | Class | Burden | Window | Weight |
|---|---|---|---|---|---|
| Circutor TRP40 P50311 | 100/5 | 5P10 | 5 VA | 40 mm | 5.0 kg |
| Circutor TRP40 P50312 | 150/5 | 5P10 | 5 VA | 40 mm | 5.0 kg |
| Circutor TRP40 P50313 | 200/5 | 5P10 | 10 VA | 40 mm | 5.0 kg |
| Circutor TRP40 P50314 | 250/5 | 5P10 | 10 VA | 40 mm | 5.0 kg |
| Circutor TRP40 P50315 | 300/5 | 5P10 | 15 VA | 40 mm | 5.1 kg |
| Circutor TRP40 P50316 | 400/5 | 5P10 | 20 VA | 40 mm | 5.1 kg |
| Circutor TRP40 P50317 | 500/5 | 5P10 | 25 VA | 40 mm | 5.2 kg |
| Circutor TRP60 P50321 | 150/5 | 5P10 | 2.5 VA | 60 mm | 2.6 kg |
| Circutor TRP60 P50322 | 200/5 | 5P10 | 2.5 VA | 60 mm | 2.7 kg |
| Circutor TRP60 P50323 | 250/5 | 5P10 | 5 VA | 60 mm | 2.7 kg |
| Circutor TRP60 P50324 | 300/5 | 5P10 | 5 VA | 60 mm | 2.7 kg |
| Circutor TRP60 P50325 | 400/5 | 5P10 | 7.5 VA | 60 mm | 2.8 kg |
| Circutor TRP60 P50326 | 500/5 | 5P10 | 10 VA | 60 mm | 2.8 kg |
| Circutor TRP60 P50327 | 600/5 | 5P10 | 10 VA | 60 mm | 2.9 kg |
| Circutor TRP60 P50328 | 750/5 | 5P10 | 15 VA | 60 mm | 3.0 kg |
| Circutor TRP60 P50329 | 1000/5 | 5P10 | 20 VA | 60 mm | 3.2 kg |
| Circutor TRP80 P50339 | 1500/5 | 5P10 | 30 VA | 80 mm | 4.0 kg |
Actual Accuracy Limit Factor Against Burden
The worked example takes a transformer rated 5P10 at 10 VA with an internal burden of 1.75 VA and shows the factor that a relay actually sees as the connected burden changes. At the rated 10 VA the factor is the printed 10. At 5 VA it is 17.4, and at 15 VA it falls to 7.0, below the printed value. A relay with a 3 VA burden and a 10 m run of 2.5 square millimetre copper adds about 3.5 VA for the leads, so the actual burden is close to 6.5 VA and the printed 10 VA rating is the safe choice. The table is arithmetic from the formula, not a test result, and it is the check that a protection study needs.
| Actual burden | Actual factor Fa | What it means for the relay |
|---|---|---|
| 2.5 VA | 27.6 | the core stays linear far above the printed factor |
| 5 VA | 17.4 | a light burden raises the real factor |
| 7.5 VA | 12.7 | still above the printed 10 |
| 10 VA | 10.0 | the printed factor, at rated burden |
| 15 VA | 7.0 | below the printed factor, distortion starts earlier |
| 20 VA | 5.4 | heavy leads or a second relay pull the factor down |
Key Features
Class and ALF on one line – 5P10 and 5P20 are shown with the burden they apply to, so the relay study uses the same numbers as the order.
Composite error defined – 5 % to the accuracy limit is the figure that matters in a fault, and it is stated rather than left to the class name.
Low end accuracy given – 1 % ratio error and 60 minutes at rated current for 5P, which is what a definite time overcurrent setting needs.
Windows from 40 to 180 mm – cable primaries and busbar primaries are both covered, so the feeder type decides the frame and not the other way round.
Resin cast body – the winding is encapsulated, which suits a damp switchroom and a panel that is washed down.
Weights published – 2.6 to 9.3 kg per frame tells the panel builder what the DIN rail or the plate has to carry.
5P20 option on every ratio – where the fault level is high and the relay setting is low, the higher factor is available without changing the frame.
Sealable secondary terminals – the secondary terminals accept a seal, so a setting cannot be changed without leaving a trace.
Applications
Three feeders where the protection core, not the relay, limits what the panel can do.
Incoming feeder overcurrent – a 1000/5 transformer at the incomer, where the fault level is highest and the 5P20 version is usually the right choice.
Motor feeder protection – a 150/5 or 200/5 transformer sized to the motor full load current, with the relay set above the starting current.
Capacitor bank feeder – a transformer that has to stay linear through the inrush, where the burden and the factor matter more than the ratio accuracy.
Generator output – a transformer on the generator breaker, where a 5P core feeds the overcurrent relay and a separate metering core feeds the meter.
Where the protection circuit sits on a control board, the SUPERB PCBA and the SUPERB PCB are checked against the same ratio and the same factor, so the relay setting and the transformer nameplate agree.
Sourcing and Cross-Reference
A protection transformer replacement is decided by reading the old nameplate: ratio, burden, class and factor. If the nameplate is missing, the ratio can be measured with a primary injection set, but the class and the factor cannot be recovered from the part, and the safe route is the next size up in both. The burden is the number most often misread, because the relay burden is on the relay data sheet and the lead burden is on the panel drawing, and only the sum belongs in the calculation.
The second check is the window. A 40 mm window takes a cable up to 40 mm overall, and a 60 or 80 mm window takes a bundle or a small bar. A busbar wider than the window needs the 100, 140 or 180 mm frame, or a bar primary type. The third check is the short time current, which has to exceed the panel fault level for the clearing time of the upstream device. A transformer with the right ratio and the wrong short time rating is a fuse, not a sensor.
For a panel waiting on one transformer, a 5P20 in the same frame usually covers a 5P10 that is short of factor, and the lead run can be shortened before the frame is changed. See lead time and availability for a specific ratio, or obsolete part cross reference when only an older code is on the drawing.
The SUPERB Assembly team shorts the secondary before the circuit is opened and marks the ratio on the lead, because an open secondary on a live protection core is a hazard, not a reading.
Q: Can you confirm the burden and the accuracy limit factor our relay actually needs before we order a 5P10 transformer?
A: Yes. Send the ratio, the relay burden, the lead length and the fault level, and the SUPERB Tech team returns the class and the factor that hold at that feeder.
Why Panel Builders Source Protection Transformers Through SUPERB
- Burden paired with ratio: every row carries the VA that belongs to that ratio, so a 5P10 is not ordered at a burden the core cannot hold.
- Factor arithmetic shown: the actual factor against burden table turns the formula into a number, which is the check a protection study needs.
- Windows stated in millimetres: 40 to 180 mm on the row, so a cable primary and a busbar primary are separated before the order.
- 5P20 available in the same frame: the higher factor is a code change rather than a frame change, which matters on a panel that is already drilled.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Rogowski Coil Current Sensors for Retrofit Metering, Metering Current Transformers for Panel and Switchgear, Current Transformers and AC Current Sensing for Energy Metering, Residual Current Devices for Panel Feeders, Phase Failure and Voltage Monitoring Relays, Multifunction Power Meters and Power Quality Analyzers, Component Lead Time Solutions.