DIN Rail kWh Meters for Panel Energy Monitoring

DIN rail energy meters that put a kWh reading inside a control panel, from one module wide up to four modules. Direct connected types take the load current themselves up to 65 A or 100 A; larger feeds use a current transformer input. Accuracy is class B, which is one percent on active energy, with class 1 on the single phase ranges. Outputs cover a passive pulse, RS-485 Modbus RTU and M-Bus, and multi-tariff versions are listed separately.
quote now

Product Specifications

Product Overview

A kWh meter inside a panel turns an estimate into a number. Sub-tenant billing, machine level consumption, a PV or battery branch, and a service contract that is priced per kWh all need a meter at the point of use rather than one at the utility cut-out. DIN rail types fit the same row as the breakers and take their supply from the circuit they measure, so no extra wiring run is needed.

The first decision is direct connected or transformer connected. A direct meter carries the full load current through its own terminals, which is practical up to about 65 A on a three phase feeder and 100 A on the wider 4 module bodies. Above that the current goes through a current transformer and the meter reads the secondary, which is why a CT ratio has to be set in the meter before the readings mean anything.

The second decision is the output. A pulse output is enough for a simple totaliser or a PLC counter, and it needs no configuration beyond the pulse weight. Modbus RTU over RS-485 gives every parameter including per phase values, and it is the normal choice where a building management system is already reading the panel. M-Bus appears where the utility or the landlord standardised on it, and the two protocols are separate order codes on the same meter body.

Key Specifications

FamilyPhasesConnectionCurrentAccuracyOutputWidth
ABB B21 111-100single phasedirect5 (65) Aclass B, 1 percentpulse2 modules
ABB B21 112-100single phasedirect5 (65) Aclass B, 1 percentpulse and Modbus RTU2 modules
ABB B23 111-100three phasedirect5 (65) Aclass B, 1 percentpulse4 modules
ABB B23 112-100three phasedirect5 (65) Aclass B, 1 percentpulse and Modbus RTU4 modules
ABB B23 113-100three phasedirect5 (65) Aclass B, 1 percentpulse and M-Bus4 modules
ABB B24 112-100three phasecurrent transformer1 (6) A secondaryclass B, 1 percentpulse and Modbus RTU4 modules
Eastron SDM120-Modbussingle phasedirect5 (45) Aclass 1, class B2 pulse and Modbus RTU1 module, 17.5 mm
Eastron SDM630-Modbusthree phasedirect10 (100) Aclass 1, class B2 pulse and Modbus RTU4 modules

Included Models and Order Codes

Model codes carry the phase count, the output and the current range. On ABB the first two digits are the family, B21 single phase and B23 three phase direct, the third group is the output, 111 pulse only, 112 Modbus, 113 M-Bus, and the 100 suffix is the 65 A steel version. On Eastron the letters after the number name the protocol, so SDM120-Modbus and SDM120-Mbus differ only in the communication board on the same 18 mm body.

Part numberPhasesCurrentVoltageAccuracyCommunicationPulse
B21 111-100single phase5 (65) A220 to 240 Vclass Bnone1 output, 1000 imp/kWh
B21 112-100single phase5 (65) A220 to 240 Vclass BModbus RTU, RS-4851 output, 1000 imp/kWh
B23 111-100three phase5 (65) A3 x 230/400 Vclass Bnone1 output, 1000 imp/kWh
B23 112-100three phase5 (65) A3 x 230/400 Vclass BModbus RTU, RS-4851 output, 1000 imp/kWh
B23 113-100three phase5 (65) A3 x 230/400 Vclass BM-Bus1 output, 1000 imp/kWh
B24 112-100three phase1 (6) A3 x 230/400 Vclass BModbus RTU, RS-4851 output, 5000 imp/kWh
SDM120-Modbussingle phase5 (45) A120 or 230 Vclass 1, class BModbus RTU, RS-4852 outputs, 1000 imp/kWh
SDM120-Mbussingle phase5 (45) A120 or 230 Vclass 1, class BM-Bus2 outputs, 1000 imp/kWh
SDM120-Pulsesingle phase5 (45) A120 or 230 Vclass 1, class Bnone2 outputs, 1000 imp/kWh
SDM630-Modbusthree phase10 (100) A3 x 230/400 Vclass 1, class BModbus RTU, RS-4852 outputs, 400 imp/kWh
SDM630-Mbusthree phase10 (100) A3 x 230/400 Vclass 1, class BM-Bus2 outputs, 400 imp/kWh
SDM630-MTthree phase10 (100) A3 x 230/400 Vclass 1, class BModbus RTU, RS-4852 outputs, multi-tariff

Direct Connection or Current Transformer

The current decides the connection method, and the breaker in front of the meter decides whether the meter can be installed at all. The table works through the usual feeder sizes and names the protection the meter expects upstream.

Feeder currentConnectionMeter rangeUpstream protectionNote
up to 45 Adirect, 1 moduleSDM120, 5 (45) A45 A MCB or gG fusesingle phase branch
up to 65 Adirect, 2 or 4 modulesB21 or B23, 5 (65) A65 A MCB C curve or 65 A gL-gGthe usual panel feeder
up to 100 Adirect, 4 modulesSDM630, 10 (100) A100 A MCB or gG fusethree phase, no CT
100 to 400 Acurrent transformerB24, 1 (6) ACT primary protection as specifiedset the CT ratio in the meter
above 400 Acurrent transformerB24 with a 5 A CTCT primary protection as specifiedratio up to 9999/1

Key Features

Direct connection to 65 A or 100 A – the load current passes through the meter terminals, so a panel feeder up to 100 A needs no current transformer and no extra enclosure space.

Class B active energy – one percent accuracy is the level required for billing inside a building, and it is stated on the label rather than implied by a display resolution.

Pulse output for a totaliser – a passive pulse at 1000 imp/kWh feeds a PLC counter without any protocol work, which is the cheapest way to put consumption on an existing controller.

Modbus RTU and M-Bus in the same body – the two protocols are separate order codes but the same dimensions, so a change of building system does not change the panel cut-out.

Multi-tariff on the wider types – four tariffs with ten time segments on the SDM630-MT, for sites where the tariff structure has to be applied inside the meter rather than in software.

One module for a single phase branch – the 17.5 mm SDM120 covers a lighting or a charger circuit without taking a full row, which matters in a retrofitted panel.

Applications

The meter is chosen from what the reading is for, and the three usual reasons need different outputs.

Sub-tenant and cost centre billing – a class B meter per tenant feeder with a pulse or Modbus output into the billing system, sized to the feeder so no CT is needed.

Machine level consumption – a meter on each machine feed so the energy per production hour can be compared, usually with Modbus into the plant network rather than a local display.

PV, battery and EV branches – a bi-directional single phase meter that separates import from export, which is the figure a self-consumption calculation needs.

The meter is quoted with the controller that reads it, so the SUPERB PCBA and the SUPERB PCB are checked against the same panel list and the RS-485 termination is planned once for the whole bus.

Sourcing and Cross-Reference

Check the current range against the feeder, not the breaker frame. A 100 A feeder on a 65 A direct meter will read, and then fail, because the meter terminals are the load path. The reverse mistake costs money too: a CT connected meter on a 40 A branch needs a transformer that the panel has no room for.

Decide the protocol before the brand. A panel that will be read by a building system over Modbus needs the 112 or the Modbus version, and buying the pulse only type to save a little means a second meter later. If the site standard is M-Bus, the 113 and the Mbus version are different parts and not a firmware change.

Plan the space and the upstream protection. A 4 module meter with a 25 mm2 terminal needs the cable bend radius behind the door, and the recommended protection is written per meter because a 100 A direct meter is not protected by a 63 A breaker. Related pages cover current transformers for the CT version, panel meters and counters for local display, and lead time and availability for the current position.

The SUPERB Assembly team keeps the meter voltage taps on their own fuses and the RS-485 pair on a shielded run, because a shared neutral on the voltage side is the usual reason a three phase meter reads one phase low.

Q: Can you supply the meter with the current transformers, the fuses and the breakers it is installed with, on one list?

A: Yes. Send the feeder current, the number of phases, the protocol the site uses and whether billing needs class B, and the SUPERB Tech team returns the meter, the connection method and the upstream protection.

Why Panel Builders Buy kWh Meters From SUPERB

  1. Connection method stated: direct or CT connected is written per row, so the CT ratio and the meter type are decided together rather than after the panel is drilled.
  2. Accuracy class in the open: class B or class 1 is listed against each family, which is what a billing or a verification argument turns on.
  3. Protocol named exactly: Modbus RTU and M-Bus are separate rows, because the two boards are not interchangeable on the same meter.
  4. Width given in modules: the row width is stated, so the meter is planned into the DIN rail with the breakers it shares the row with.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Current Transformers and AC Current Sensing for Energy Metering, Digital Panel Meters and Counters for Control Panels, Residual Current Devices for Panel Feeders, Fuse Switch Disconnectors for Panel Isolation, DIN Rail Power Supplies for Control Cabinets.