Insulation Monitoring Devices for Unearthed Systems
Product Specifications
Product Overview
An insulation monitoring device is the answer to a specific arrangement: a system that is deliberately not earthed. In an IT system the neutral is isolated, so a single fault to earth does not flow a fault current and the process keeps running. That is why operating theatres, shipboard circuits, battery systems, and some process lines run unearthed. The price of that continuity is that the first fault is invisible until it is found, and a second fault on another phase becomes a short circuit through earth.
The monitor closes that gap. It injects a small measuring signal between the system and earth and reads the resulting current, which gives the insulation resistance of the whole system. When the resistance falls below a set value, an alarm relay changes state. Two thresholds let the panel pre-warn at a high resistance and alarm at a low one, so maintenance can plan the search instead of reacting to a trip.
Three numbers decide the type. The system voltage sets the measuring range: 250 V AC and 300 V DC on the small 22.5 mm body, 400 V AC and 600 V DC on the wider 45 mm body, and above that a coupling unit is added. The response range sets the sensitivity: 1 to 100 kOhm for control circuits, 2 to 200 kOhm where a motor winding has to be watched. The system leakage capacitance sets the device itself, because a large capacitance slows the measurement and a body rated for 20 microfarad will misread on a drive system with far more.
Key Specifications
| Family | System voltage | Response range | Supply | Capacitance | Output | Width |
|---|---|---|---|---|---|---|
| Bender IR420-D4-1 | AC 0 to 300 V, 42 to 460 Hz | 1 to 200 kOhm, two values | DC 9.6 to 94 V, AC 16 to 72 V | under 20 microfarad | 2 SPDT relays | 36 mm, two modules |
| Bender IR420-D4-2 | AC 0 to 300 V, 42 to 460 Hz | 1 to 200 kOhm, two values | AC or DC 70 to 300 V | under 20 microfarad | 2 SPDT relays | 36 mm, two modules |
| ABB CM-IWS.1S | AC 0 to 250 V, DC 0 to 300 V | 1 to 100 kOhm | 24 to 240 V AC or DC | 20 microfarad | 1 changeover, 4 A | 22.5 mm |
| ABB CM-IWN.1S | AC 0 to 400 V, DC 0 to 600 V | 1 to 100 kOhm and 2 to 200 kOhm | 24 to 240 V AC or DC | 20 microfarad | 2 changeover, 4 A | 45 mm |
| ABB CM-IWN.1P | AC 0 to 400 V, DC 0 to 600 V | 1 to 100 kOhm and 2 to 200 kOhm | 24 to 240 V AC or DC | 20 microfarad | 2 changeover, push-in | 45 mm |
Included Models and Order Codes
The suffix on each family is the supply and the terminal style, not the measuring range. On Bender IR420-D4-1 and IR420-D4-2 the difference is the control supply: the -1 runs from a 24 V rail, the -2 needs 70 to 300 V, and both measure the same 0 to 300 V AC system. On ABB the S and P suffixes are screw and push-in terminals, and the W in CM-IWN marks the wide measuring input that reaches 400 V AC without a coupling unit.
| Part number | System voltage | Response values | Supply | Alarm relays | Response time | Terminals |
|---|---|---|---|---|---|---|
| IR420-D4-1 | AC 0 to 300 V | 1 to 200 kOhm, two values | DC 9.6 to 94 V, AC 16 to 72 V | 2 SPDT | 1 s at half the set value | screw |
| IR420-D4-2 | AC 0 to 300 V | 1 to 200 kOhm, two values | AC or DC 70 to 300 V | 2 SPDT | 1 s at half the set value | screw |
| CM-IWS.1S | AC 0 to 250 V, DC 0 to 300 V | 1 to 100 kOhm, 1 kOhm steps | 24 to 240 V AC or DC | 1 changeover | max 10 s | screw |
| CM-IWN.1S | AC 0 to 400 V, DC 0 to 600 V | 1 to 100 kOhm and 2 to 200 kOhm | 24 to 240 V AC or DC | 2 changeover | max 10 s | screw |
| CM-IWN.1P | AC 0 to 400 V, DC 0 to 600 V | 1 to 100 kOhm and 2 to 200 kOhm | 24 to 240 V AC or DC | 2 changeover | max 10 s | push-in |
Setting the Two Response Values
Two thresholds are only useful if they are set apart. The table shows the preset values the devices apply at different system voltages, and what each threshold is expected to trigger in the panel.
| System voltage | Preset alarm 1 | Preset alarm 2 | Alarm 1 usually drives | Alarm 2 usually drives |
|---|---|---|---|---|
| up to 72 V | 20 kOhm | 10 kOhm | a maintenance lamp | the process interlock |
| above 72 V, 230 V control | 46 kOhm | 23 kOhm | a warning on the HMI | the contactor release |
| 400 V three phase, unearthed | 46 kOhm or higher | 23 kOhm | trend logging | shutdown of the drive |
| battery string, 600 V DC | 50 kOhm and up | 25 kOhm | charge inhibit | main contactor open |
Key Features
Two thresholds, pre-warning and alarm – a high resistance warning lets maintenance plan the fault search, while the low threshold still protects the process from a second fault.
Measuring circuit takes the system voltage – 400 V AC and 600 V DC are connected directly on the wide bodies, so no transformer or coupling unit is needed on a normal panel.
Separate supply input – 24 to 240 V AC or DC means the monitor keeps working when the system it watches is de-energised, which is when an insulation fault is usually found.
Relay outputs rated for a contactor – 4 A changeover contacts switch a coil or a PLC input directly, and the 24 V DC 2 A figure covers the usual interposing relay.
Adjustable response delay – 0 to 99 s on the Bender family and up to 10 s on the ABB bodies stops a transient from tripping the process during a drive start.
Connection monitoring – the measuring leads are supervised for interruption, so a broken wire reads as a fault rather than as a healthy high resistance.
Applications
The monitor is fitted where an earth fault must not stop the process at the first fault, and the three usual cases differ in capacitance.
Medical and laboratory IT systems – an unearthed 230 V circuit with a monitor and a remote alarm panel, so a first fault is reported at the desk and the procedure continues.
Battery and DC auxiliary systems – a 110 or 220 V DC battery installation where an earth fault on one pole must be found before it becomes a short through the charger.
Marine and process lines with drives – an unearthed 400 V distribution with several drives, where the capacitance limit is checked first and a device rated for the total capacitance is chosen.
The monitor is quoted with the board that reads its alarm, so the SUPERB PCBA and the SUPERB PCB are checked against the same panel list and the alarm contact is wired to a supervised input.
Sourcing and Cross-Reference
Confirm that the system is unearthed before you buy one. On a TN system the neutral is bonded to earth and the correct device is a residual current device, not an insulation monitor, and fitting a monitor there produces a constant low reading that has nothing to do with the insulation. The two pages are often confused because both report an earth fault.
Add up the leakage capacitance. Every drive, filter and long cable run adds to the system capacitance, and the measuring principle slows as it rises. A body rated 20 microfarad is right for a control circuit; a distribution with three drives may need a device rated for 500 microfarad or more, and that is a different product rather than a setting.
Set the thresholds for the system voltage and keep them apart. The presets at 46 and 23 kOhm exist because a 400 V winding that reads 30 kOhm is already suspect while a control circuit at the same value is normal. Related pages cover residual current devices for the earthed case, voltage monitoring relays for the supply side, and lead time and availability for the current position.
The SUPERB Assembly team keeps the measuring lead away from the drive output cables and bonds the earth reference at one point only, because a second bond turns the IT system into a TN system and the monitor then reads zero.
Q: Can you supply the monitor with the coupling unit and the alarm panel for a 400 V unearthed system?
A: Yes. Send the system voltage, the number of drives and the total cable length, and the SUPERB Tech team returns the family, the response range and the coupling unit if one is needed.
Why Panel Builders Buy Insulation Monitors From SUPERB
- System voltage and range together: the measuring input and the response range are in one row, so a 400 V system does not get a 250 V device.
- Capacitance limit stated: the 20 microfarad figure is written per family, which is the number that rules a device out on a drive fed distribution.
- Supply separated from measuring: the control supply range is listed apart from the system voltage, because the monitor has to run when the system is dead.
- Relay rating given: the contact current and arrangement are stated, so the alarm can be wired to a coil or a PLC input without a second relay.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Residual Current Devices for Panel Feeders, Phase Failure and Voltage Monitoring Relays, DC Isolator Switches for PV and Battery Strings, Surge Protective Devices for AC Distribution Boards, DIN Rail Power Supplies for Control Cabinets.