Contact Us

Residual Current Devices for Panel Feeders

Residual current devices that compare the current going out on the phases with the current coming back on the neutral, and open when the difference passes the set level. Bodies cover two pole outgoing circuits and four pole feeder protection, at 25 to 63 A and 30, 100 or 300 mA. Detection types run from AC for resistive loads to A for pulsating DC and B for smooth DC from drives and chargers. Conditional short circuit ratings are 10 kA with the matching upstream fuse or breaker, so the feeder device and the backup device are chosen together.
quote now

Product Specifications

Product Overview

A residual current device protects people and cables from earth fault current, not from overload. It sums the current in the live conductors and the neutral, and when the vector sum is not zero the difference is going to earth through a person, a wet terminal or a damaged cable. At 30 mA the trip is fast enough to be a person protection measure, and at 100 or 300 mA the same device is a fire and feeder protection measure.

The device does not replace the breaker above it. A residual current device has no overcurrent element, so a short circuit on the outgoing cable is cleared by the upstream fuse or breaker, and the residual current device only has to survive that fault. That survival is the conditional short circuit rating, usually 10 kA with a specified backup device, and it is the number that decides whether the combination can be installed at the point of supply.

The other decision is the detection type, and it is decided by what is downstream. A resistive heater produces a sine wave residual current, which type AC sees. A single-phase drive or a switch mode supply produces a pulsating DC component, which needs type A. A three-phase drive, a charger or a PV inverter can produce a smooth DC component that saturates the toroid of a type A device, so the device stops seeing the fault at all and type B is required. Getting this wrong is not a nuisance trip, it is a device that no longer trips.

Key Specifications

FamilyPolesRated currentSensitivityDetection typeConditional short circuitWidth
Schneider iID AC2P40 A30 mAAC10 kA36 mm
Schneider iID A2P40 A30 mAA10 kA36 mm
Schneider iID A-SI2P40 A30 mAA-SI10 kA36 mm, 3 kA surge
Schneider iID AC4P40 A30 mAAC10 kA72 mm
ABB F200, F2022P25 A30 mAA10 kA35 mm, 2 modules
ABB F200, F2044P63 A300 mAA10 kA70 mm, 4 modules
Siemens 5SV3, 30 mA2P63 A30 mAA10 kA36 mm
Siemens 5SV3, 100 mA2P63 A100 mAA10 kA36 mm
Doepke DFS 4 type B4P40 A30 mAB SK10 kA72 mm, 0 to 150 kHz

Included Models and Order Codes

The codes below are the ones we quote for panel feeders. On Schneider the iID digit group carries the type first: A9R4 is the AC type, A9R2 is type A and A9R6 is the A-SI version with the higher surge withstand. On ABB the F202 is the two pole body and the F204 the four pole body. On Siemens the 5SV3 group with the 30 mA suffix is the socket and final circuit device, while the 100 mA code is the feeder device that sits upstream of it.

Part numberFamilyPolesRated currentSensitivityTypeNote
A9R41240iID2P40 A30 mAAC220 to 240 V, 36 mm
A9R21240iID2P40 A30 mAApulsating DC detection
A9R61240iID2P40 A30 mAA-SI3 kA surge withstand
A9R41440iID4P40 A30 mAAC380 to 415 V, 72 mm
F202 A-25/0.03F2002P25 A30 mAA230/400 V, 35 mm
F204 A-63/0.03F2004P63 A30 mAA230/400 V, 70 mm
F204 A-63/0.3F2004P63 A300 mAAfeeder level, 70 mm
5SV3316-65SV32P63 A30 mAA230 V, 36 mm, IP20
5SV3416-65SV32P63 A100 mAAfeeder level, 36 mm
DFS 4 040-4/0,03-B SKDFS 44P40 A30 mAB SK0 to 150 kHz, 72 mm

What Each Detection Type Sees

The type letter is the part of the order that is most often copied from the previous project without checking. The table states what each type detects and where it is normally used. A type B device costs several times a type A device, and the reason to pay for it is a load that can inject smooth DC into the fault path.

TypeResidual currents detectedTypical downstream loadNote
ACsinusoidal alternating current onlyheaters, contactor coils, simple lightingcheapest, and blind to any DC component
Aalternating plus pulsating direct currentsingle phase drives, switch mode supplies, household socketsthe usual choice for a mixed panel
A-SIas type A, with a higher surge withstandcircuits with frequent switching surges3 kA surge instead of 250 A on the 40 A body
Falternating, pulsating and mixed frequency currentthree phase drives and invertersdefined for mixed frequencies, not for smooth DC
Balternating, pulsating and smooth direct currentchargers, PV inverters, three phase drivesthe only type that sees a smooth DC fault
B SK or B NKtype B with a shaped frequency responsesites with high leakage at the clock frequencySK is less sensitive above 1 kHz, NK keeps sensitivity to 150 kHz

Key Features

Trips without a supply – the electromechanical types trip on a type A residual current even when the mains voltage has collapsed, because the sensing is not derived from an electronic supply.

Two pole and four pole bodies – a 36 mm two pole device for a single phase outgoing circuit and a 72 mm four pole device where a three phase feeder with neutral has to be protected as one circuit.

One sensitivity step per row – 30 mA for person protection, 100 mA for a feeder, 300 mA for fire protection, stated as the rated residual current rather than a class name.

Surge withstand stated – the 250 A figure on the standard 40 A body against 3 kA on the A-SI version is the difference between a device that holds on a switching surge and one that trips the row.

10 kA conditional rating – the combination with the specified backup fuse or breaker is stated, so the feeder device is not installed at a point where the prospective fault exceeds it.

Test button on the front – the mechanical test checks the trip mechanism and the contact opening, which is the part of the periodic inspection that does not need a tester.

Applications

Three shapes of the same decision. Each one fixes the pole count, the sensitivity and the detection type.

Machine feed with a drive – four pole type B on the feeder, because the drive injects a smooth DC component during a fault and a type A device would be blinded by it.

Socket row in a control cabinet – two pole type A at 30 mA per circuit, so a fault in one service socket does not take the whole panel down and the person protection level is kept.

Feeder to a sub distribution board – four pole 300 mA upstream and 30 mA downstream, with the upstream device time delayed so a fault in one final circuit trips the local device first.

The feeder is quoted with the board it supplies, so the SUPERB PCBA and the SUPERB PCB are checked against the same load list and the device rating agrees with the cable.

Sourcing and Cross-Reference

Start from the load, not from the shelf. If the circuit feeds a drive, a charger or a PV inverter, the detection type is B and there is no cheaper substitute. If it feeds a resistive heater or a contactor coil, type AC is enough and the money saved belongs in the surge protection.

Then check the current and the pole count against the cable. A 40 A device on a 63 A cable is a device that will be overloaded before the breaker trips, and a two pole device cannot protect a three phase circuit with a neutral. The rated current of the device is a continuous current, not a trip level.

Finally check the backup device. The 10 kA conditional rating only holds with the fuse or breaker the maker lists, and the cable length to the sub board changes the prospective fault current. A device installed without that check is a device with an unverified rating, whatever the label says. See lead time and availability for the panel schedule and obsolete part cross reference when the installed type has been replaced by a new range.

The SUPERB Assembly team keeps the neutral of each residual current circuit separate downstream of the device, because a shared neutral is the fault that makes a healthy row trip.

Q: Can you supply the residual current device together with the breakers and the surge protector for the same feeder, matched on one list?

A: Yes. Send the load type, the rated current, the pole count and whether a drive or a charger sits downstream, and the SUPERB Tech team returns the detection type, the sensitivity and the backup device that fit.

Why Panel Builders Buy Residual Current Devices From SUPERB

  1. Detection type named per code: the AC, A, A-SI and B rows are separated, so the order does not depend on reading a suffix from a catalogue page.
  2. Sensitivity and current together: 30, 100 and 300 mA are quoted against the rated current, which is where the mismatch between a feeder device and its cable usually appears.
  3. Backup device in the same quotation: the fuse or breaker that the conditional rating depends on is offered with the device, so the pair is checked before the panel is wired.
  4. Replacements for installed ranges: the current range and the older code are compared side by side, which keeps a service replacement that fits the existing row width.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads, Surge Protective Devices for AC Distribution Boards, Power Distribution Blocks for Panel Feeds, DIN Rail Power Supplies for Control Cabinets.