Phase Failure and Voltage Monitoring Relays

DIN rail relays that watch a three-phase supply and drop a contact when a phase is lost, the sequence is reversed or the voltage leaves its window. Families cover phase failure only, phase failure with asymmetry, and full over and undervoltage monitoring on one or two thresholds. Most types are powered from the measuring circuit, so no separate auxiliary supply is needed in the panel. Widths run from 17.5 mm for a single function to 35 mm where two independent output contacts are required.
quote now

Product Specifications

Product Overview

A phase failure relay is a voltage watchdog. It sits on the incoming three-phase supply, compares the three phase-to-phase voltages, and holds its output contact closed only while all three phases are present, in the right order, and inside the set window. When one phase opens, the contact drops and the starter coil loses its feed. The motor never sees the single-phase condition that overheats it in a few minutes.

The reason a panel needs one is that a running motor does not fail cleanly when a fuse blows. It keeps turning on two phases, draws a much higher current per remaining winding, and the overload relay may take long enough to trip that the winding is already damaged. Voltage monitoring acts first, because it sees the missing phase at the supply side before the overload sees the current rise.

Three functions are often confused and they are not the same purchase. Phase failure detection looks only at whether all three voltages are present. Phase sequence detection looks at the rotation order, which matters on a pump or a compressor that must not run backwards. Voltage monitoring compares each phase against an absolute threshold and trips on over or undervoltage, with a delay so a motor start does not cause a nuisance trip. Many families combine two of the three, and the table below states exactly what each type covers.

Key Specifications

FamilyFunctions monitoredMeasuring rangeOutputWidthNote
Schneider RM17TG00Phase failure, phase sequence208 to 480 V AC, limits 183 to 528 V1 C/O, 5 A17.5 mmself powered, trip below 100 V
Schneider RM17TG20Phase sequence, phase failure, asymmetry208 to 480 V AC, limits 183 to 484 V2 C/O, 5 A17.5 mm130 ms response on a fault
Schneider RM17UB310Over and undervoltage between phases208 to 480 V AC, limits 183 to 528 V1 C/O, 5 A17.5 mm0.3 to 30 s delay, 2 percent hysteresis
Schneider RM35UB330Over and undervoltage between phases220 to 480 V AC, limits 195 to 528 V2 C/O, 5 A35 mmone contact per threshold
ABB CM-PVS.31SSequence, failure, over and undervoltage3 x 160 to 300 V AC2 c/o, 4 A22.5 mmtrue RMS, 0 to 30 s delay
ABB CM-PVS.41SSequence, failure, over and undervoltage3 x 300 to 500 V AC2 c/o, 4 A22.5 mmscrew terminals, same body as 31S
Siemens 3UG4512-1BR20Phase failure, phase sequence3 x 160 to 690 V AC2 changeover, 3 A22.5 mm450 ms maximum response
Siemens 3UG5512-1BR20Failure, sequence, asymmetry3 x 160 to 690 V AC, 15 to 70 Hz2 changeover22.5 mmcurrent type, replaces 3UG4512
Omron K8AK-PH1Phase sequence, phase loss3 x 200 to 480 V AC1 DPDT, 5 A22.5 mm0.1 s, loss level 80 percent
Omron K8AK-VS2Over or undervoltage, single phase1 to 150 V AC/DC in three ranges1 SPDT, 5 A22.5 mm24 V AC/DC auxiliary supply
Omron K8AK-VS3Over or undervoltage, single phase20 to 600 V AC/DC in three ranges1 SPDT, 5 A22.5 mmwide range, isolated input

Included Models and Order Codes

The rows below are the codes we quote most often. On Schneider the digits after RM17TG set the function: TG00 is phase failure and sequence with one changeover contact, TG20 adds asymmetry and a second contact. On ABB the last letter of CM-PVS.31S and CM-PVS.41S is the terminal type, S for screw and P for push-in. On Omron the K8AK-PH1 is the three-phase voltage type, while K8AK-VS2 and K8AK-VS3 are single-phase units whose third digit sets the voltage range, not the supply.

Part numberFamilyFunctionRangeOutputWidthNote
RM17TG00RM17TGphase failure and sequence208 to 480 V AC1 C/O, 5 A17.5 mmself powered, 22 VA at 400 V
RM17TG20RM17TGsequence, failure, asymmetry208 to 480 V AC2 C/O, 5 A17.5 mm130 ms response
RM17UB310RM17UB3over and undervoltage183 to 528 V AC1 C/O, 5 A17.5 mmdelay 0.3 to 30 s
RM17UAS15RM17UASover or undervoltage, one threshold65 to 260 V AC/DC1 C/O, 5 A17.5 mm110 to 240 V supply
RM17UBE15RM17UBEover and undervoltage, window65 to 260 V AC/DC1 C/O, 5 A17.5 mm110 to 240 V supply
RM35UB330RM35UB3over and undervoltage, three phase195 to 528 V AC2 C/O, 5 A35 mmone contact per threshold
RM35UB3N30RM35UB3Nover and undervoltage, phase to neutral114 to 329 V AC2 C/O, 5 A35 mmalso flags a lost neutral
CM-PVS.31SCM-PVSsequence, failure, over and undervoltage3 x 160 to 300 V AC2 c/o, 4 A22.5 mmscrew terminals
CM-PVS.41SCM-PVSsequence, failure, over and undervoltage3 x 300 to 500 V AC2 c/o, 4 A22.5 mmscrew terminals
CM-PVS.41PCM-PVSsequence, failure, over and undervoltage3 x 300 to 500 V AC2 c/o, 4 A22.5 mmpush-in terminals
3UG4512-1BR203UG4phase failure and sequence3 x 160 to 690 V AC2 changeover, 3 A22.5 mmphase out, successor 3UG5512
3UG5512-1BR203UG5failure, sequence, asymmetry3 x 160 to 690 V, 15 to 70 Hz2 changeover22.5 mmsuccessor type
K8AK-PH1K8AK-PHphase sequence and phase loss3 x 200 to 480 V AC1 DPDT, 5 A22.5 mm0.1 s operating time
K8AK-VS2 24 VAC/DCK8AK-VS2over or undervoltage1 to 150 V AC/DC1 SPDT, 5 A22.5 mmisolated supply
K8AK-VS3 100-240 VACK8AK-VS3over or undervoltage20 to 600 V AC/DC1 SPDT, 5 A22.5 mmthree input ranges

Matching the Family to the Mains You Have

The most common ordering mistake is a relay whose measuring range stops below the site voltage. The table maps the usual distribution voltages to a family that covers them, with the phase-to-phase figure in the second column. A relay rated 208 to 480 V AC is not a 690 V device, even though the same housing is used.

Distribution voltagePhase to phaseFamily that covers itNote
120/208 V, North America208 VRM17TG00, CM-PVS.31S, K8AK-PH1all three sit inside their lower range
230/400 V, IEC Europe and Asia400 VRM17TG00, CM-PVS.41S, 3UG4512, K8AK-PH1the usual panel voltage
277/480 V, North America480 VRM17TG00, CM-PVS.41S, K8AK-PH1upper end of each range
400/690 V, heavy industry690 V3UG4512-1BR20 or 3UG5512-1BR20only the 3UG range reaches 690 V
24 V DC control24 V DCK8AK-VS2, RM17UAS16single phase or DC rail
110 V or 220 V DC control110 to 220 V DCRM17UAS15, RM17UBE15, K8AK-VS2window type for both limits

Key Features

Powered from the measuring circuit – no separate auxiliary supply is needed on the RM17TG, CM-PVS and 3UG types, so the relay adds one DIN rail item and no extra wiring run.

Phase sequence in the same body – a reversed L1 and L2 is caught before the first start, which is the failure that destroys a pump seal or a screw compressor.

Asymmetry on the wider types – an unbalanced supply shows up as a voltage difference before it shows up as a hot winding, and the relay trips on the difference rather than waiting for current.

Adjustable tripping delay – 0.1 to 30 s on the ABB and Schneider window types lets a direct-on-line start finish without a nuisance trip while still opening on a real fault.

Two independent contacts – one contact can drop the starter coil while the second signals the PLC, so the operator sees a phase fault rather than a generic trip.

17.5 mm width on single function types – the same footprint as a one-pole breaker, which matters when the relay is added to an existing row without a new enclosure.

Applications

The same relay is bought for three different reasons. Each one decides the function count and the delay setting.

Pump and compressor starters – phase sequence and failure on the incoming feed, so a reversed supply is refused at commissioning and a lost phase stops the drive before the overload heats up.

Generator and mains changeover panels – voltage window monitoring on each source, with a delay long enough to ride through the transfer and short enough to protect the load from a sustained undervoltage.

Machine feed with a long cable run – undervoltage monitoring at the panel, because a long run drops several percent at start and the contactor chatter that follows is often blamed on the coil rather than the supply.

The starter is quoted with the board that sequences it, so the SUPERB PCBA and the SUPERB PCB are checked against the same panel list and the relay supply agrees with the control rail.

Sourcing and Cross-Reference

Decide the function before the brand. If the panel only needs to refuse a reversed supply, a phase sequence unit is enough and a full window relay is money spent on settings nobody will adjust. If the site has a weak supply or a heavy start, the delay and the two thresholds are the reason to buy the wider type.

Check what powers the relay. On the self-powered families the measuring circuit is also the supply, which is why they stop working below about 70 percent of the lowest rated voltage. A site that can sag that far needs a unit with a separate auxiliary supply, or the relay will drop out during the very event it was bought to report.

Read the contact rating against the coil it drives. A 5 A changeover contact will switch a 50 VA contactor coil directly, but a large contactor with an economiser or a brake coil should go through an interposing relay. The output is a signal, not a motor circuit.

Response time belongs in the coordination study. A 100 to 450 ms trip is fast enough for a phase loss but a sustained undervoltage during a start can still be shorter than the delay setting. Set the delay from the start time, not from the fault time. See lead time and availability when the panel schedule is tight, and shortage recovery when the original type is on allocation.

The SUPERB Assembly team lands the three sensing wires on separate terminals and keeps the sensing fuses on the supply side, because a shared return hides the missing phase the relay is meant to report.

Q: Can you supply the monitoring relay together with the contactors and the breakers it works with, on one matched list?

A: Yes. Send the site voltage, the number of phases and whether the panel needs sequence, asymmetry or a voltage window, and the SUPERB Tech team returns the family, the range and the contact arrangement that fit.

Why Panel Builders Buy Monitoring Relays From SUPERB

  1. Function stated per code: each row says whether the type sees failure only, sequence, asymmetry or a voltage window, so the order does not depend on decoding a suffix.
  2. Range checked against the site: the mains voltage is confirmed against the measuring range before the part is quoted, which is where most wrong orders start.
  3. Contact rating in the open: the output current and the contact arrangement are listed, so the coil it drives can be checked in the same pass.
  4. Spares matched to installed rows: the same function on a 17.5 mm and a 35 mm body is quoted together, which keeps a service spare that fits the existing cut-out.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, Motor Protection Circuit Breakers for Panel Feeders, Soft Starters for Motor Starting, DIN Rail Power Supplies for Control Cabinets, Surge Protective Devices for AC Distribution Boards.