Interface and Coupling Relays for DIN Rail
Product Specifications
Product Overview
An interface relay sits between a control output and a field load and does three jobs at once. It separates the control circuit from the field circuit, so a fault on a 230 V valve coil cannot reach the PLC card. It amplifies, because a transistor output rated 0.5 A cannot close a 2 A load. And it converts, because the same family offers 24 V DC, 110 V AC and 230 V AC coils on the same 6.2 mm footprint. In a panel the part is chosen for the load, and the coil is chosen for whatever signal is available at that terminal.
Three physical forms cover the work. The complete module is a base with a relay already plugged in, ordered as one catalog number. The separate form is a socket plus a plug-in relay, which lets the relay be replaced without tools and lets a different contact material be fitted later. The third form is the slim module with screw, spring or push-in terminals, where the terminal style decides the wiring time rather than the electrical behaviour. All three take the same 35 mm rail, and all three are usually mixed in one panel.
The details that decide the part are rarely on the front of the catalog page. Coil current matters when eight channels share one output: 9 mA at 24 V DC means eight relays draw 72 mA, while a 230 V AC coil at 3.2 mA allows far more channels on the same card. Protection matters in the other direction: a DC coil needs a freewheel diode, an AC/DC coil needs a bridge rectifier, and both are built into the base on the Phoenix and Finder modules. Contact material matters for small signals, where a gold layer keeps a 1 mA dry contact readable and a plain silver alloy does not.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Width | 6.2 mm on Phoenix, Finder and Omron, 6 mm on Schneider RSL | about 32 channels in 200 mm of rail |
| Contact configuration | 1 changeover, single contact | 1 NO plus 1 NC used as an alternative on some frames |
| Rated contact current | 6 A general purpose | 10 A inrush for 4 s on the Phoenix base |
| Maximum switching voltage | 250 V AC/DC on Phoenix, 400 V AC on Finder 38.61, 440 V AC on Omron | the separating plate is needed above 250 V between adjacent modules |
| Rated load | 6 A at 250 V AC, 6 A at 30 V DC | 2.5 A at 250 V AC on an inductive load at cos phi 0.4 |
| Coil voltages | 12, 24, 48, 110, 220 to 230 V AC and DC | AC/DC wide range coils on the universal sockets |
| Coil current at 24 V DC | 9 mA typical at 24 V DC, 3.2 mA at 230 V AC | this is what limits the number of channels per output |
| Response and release time | 5 ms and 8 ms on Phoenix 24 V DC, 7 ms and 15 ms on 230 V AC | the AC coil is slower because of the bridge rectifier |
| Mechanical life | 10 million cycles on Finder, 20 million on Phoenix | electrical life 60,000 cycles at rated load on Finder |
| Contact material | AgSnO as standard, hard gold plated on the AU and AP versions | gold holds 1 mA at 100 mV, silver needs 10 mA at 12 V |
| Insulation | rated insulation voltage 250 V, impulse withstand 6 kV | test voltage 4 kV AC between coil and contact |
| Ambient temperature | -40 to +60 C in operation, -40 to +70 C on Finder | derating applies when modules are stacked and all coils are held in |
| Mounting | 35 mm DIN rail to EN 60715, zero spacing in rows | separating plate above 250 V between modules |
| Approvals | UL and CSA on the listed combinations, ATEX and IECEx on the EX version | check the combination, not only the relay |
Included Models and Order Codes
Order codes differ in what they carry. Phoenix puts the function in the name and the order number beside it, so PLC-RSC-24DC/21 is a screw terminal base with a 24 V DC coil and one changeover contact, catalog number 2966171, and the AU suffix marks the gold contact version. Finder writes five fields: 38.51.0.024.0060 is the 38 series, 6.2 mm wide, 24 V AC/DC coil, one changeover contact at 6 A, screw terminals, while 38.61 uses spring terminals and 39.31 is the 6 A relay set with a different base. Omron splits push-in and screw into G2RV-SR500 and G2RV-SR700. Schneider uses RSL1PV for the screw connector, RSL1PR for spring and RSL1AB4 for the replacement relay alone. The coil code is the field that decides whether the module fits the signal you have, so it is called out per row.
| Part number | Maker | Coil | Contact | Terminals | Note |
|---|---|---|---|---|---|
| PLC-RSC-24DC/21 (2966171) | Phoenix Contact | 24 V DC | 1 CO, 6 A | screw | 9 mA coil, 5 ms response, 6.2 mm |
| PLC-RSC-230UC/21 (2966207) | Phoenix Contact | 230 V AC, 220 V DC | 1 CO, 6 A | screw | 3.2 mA at 230 V AC, bridge rectifier |
| PLC-RSC-24DC/21AU (2966265) | Phoenix Contact | 24 V DC | 1 CO, gold | screw | 1 mA at 24 V, 50 mA limit on the gold layer |
| 38.51.0.024.0060 | Finder | 24 V AC/DC | 1 CO, 6 A | screw | 6.2 mm, LED and protection built in |
| 38.51.0.230.0060 | Finder | 230 V AC | 1 CO, 6 A | screw | same base, 230 V coil |
| 38.61.0.024.0060 | Finder | 24 V AC/DC | 1 CO, 6 A | spring | screwless version of 38.51 |
| 38.61.8.240.0060 | Finder | 230 to 240 V AC | 1 CO, 6 A | spring | AC only coil on the screwless base |
| 39.31.0.024.0060 | Finder | 24 V AC/DC | 1 CO, 6 A | screw | 6.2 mm relay set, 94.3 mm depth |
| G2RV-SR500 DC24 | Omron | 24 V DC | 1 CO, 6 A | push-in | 1500 VA, 440 V AC maximum, 6.2 mm |
| G2RV-SR500 AC/DC24 | Omron | 24 V AC/DC | 1 CO, 6 A | push-in | universal coil on the same base |
| G2RV-SR700 DC24 | Omron | 24 V DC | 1 CO, 6 A | screw | screw terminal version of the SR500 |
| G2RV-SR500-AP DC24 | Omron | 24 V DC | 1 CO, 50 mA | push-in | gold contacts for micro loads |
| RSL1PVBU | Schneider RSL | 24 V AC/DC | 1 CO, 6 A | screw | 6 mm wide, LED and protection module |
| RSL1PRBU | Schneider RSL | 24 V AC/DC | 1 CO, 6 A | spring | spring version of RSL1PVBU |
| RSL1AB4BD | Schneider RSL | 24 V AC/DC | 1 CO, 6 A | relay only | replacement relay for the RSL base |
Standard and Gold Contacts Side by Side
The contact material decides whether a small signal can be read at all. A silver alloy needs a wetting current to break through the surface film, and a gold layer does not, which is why the same 6 A module comes in two versions and why the gold one must not be used above its own current limit.
| Version | Minimum switching | Maximum on the gold layer | Typical use |
|---|---|---|---|
| AgSnO standard | 10 mA at 12 V | not applicable | valve coils, lamps, small contactor coils, 230 V loads |
| Gold plated AU or AP | 1 mA at 100 mV, 100 mV at 10 mA | 50 mA at 30 V, 1.2 W at 24 V DC | dry contacts, multiplexer inputs, analogue card signals |
| Gold version after a load event | 10 mA at 12 V once the layer is broken | 250 V AC/DC, 6 A continuous | mixed panels where one channel occasionally drives a lamp |
Key Features
6.2 mm for the whole family – Phoenix, Finder and Omron share the width, so a channel added later fits the gap left in the row without re-drilling the rail.
Coil current published – 9 mA at 24 V DC and 3.2 mA at 230 V AC are on the row, which is what decides how many channels one output can drive.
Protection inside the base – freewheel diode on DC coils and a bridge rectifier on AC/DC coils are part of the module, not an accessory on the drawing.
Gold contact option – the AU and AP versions hold a 1 mA signal and are listed separately, because a standard silver contact will not read a dry contact reliably.
Plug-in relay with a retaining clip – the relay lifts out of the base with the clip, so a replacement takes seconds and the field wiring stays where it is.
Terminal style in the code – screw, spring and push-in are separate part numbers, so the wiring method is chosen at order time rather than at the panel.
Yellow LED on the coil circuit – the LED follows the coil, not the contact, so a missing signal and a welded contact look different during fault finding.
Applications
The three cases below cover most of the interface relay orders we quote, and each one is decided by a different number on the page.
Machine control panels – a PLC card with 16 outputs drives 16 valve coils, and the interface relay carries the 2 A inductive load and the freewheel energy that the card output cannot.
Retrofit of an older relay logic panel – existing 110 V AC control circuits meet a new 24 V DC controller, and the wide range AC/DC coil on the universal socket bridges the two voltages without a second transformer.
Process skids with long field runs – a 230 V signal travels 80 m to a solenoid and a fault on that cable must not reach the control card, so the relay sits at the panel end and the separation is the point of the part.
The controller board behind these channels is often quoted with the panel, so the SUPERB PCBA and the SUPERB PCB are reviewed against the same channel list and the coil current per output is checked once for both.
Sourcing and Cross-Reference
These modules are ordered in tens and hundreds, and the two things that go wrong are the coil voltage and the terminal style. A panel wired with spring terminals cannot take a screw module without re-terminating the row, and a 24 V DC module on a 110 V AC signal is a dead channel that looks like a wiring fault. Both are in the order code, so the first check on a shortage is the full code rather than the family name.
The second question is the small signal case. Where a channel reads a dry contact, a thermostat or a multiplexer input, a standard silver contact will read open until the current rises above 10 mA, and the fault appears only on the bench. The gold version is the answer, and it has its own current limit, so the row that carries it also states that limit.
For a panel waiting on one coil voltage, the options are usually the same module in the AC/DC universal coil, the equivalent module from another maker in the same 6.2 mm width, or the separate socket and relay form where only the relay is short. See lead time and availability for a specific code, and obsolete part cross reference where a module has been discontinued.
The SUPERB Assembly team labels each module with the channel number before it goes on the rail, because a row of identical 6.2 mm modules is impossible to trace once the duct cover is on.
Q: Can you supply the 24 V DC gold contact version and confirm the coil current and minimum load per channel?
A: Yes. Send the signal voltage, the field load current, the terminal style and whether the load is a dry contact, and the SUPERB Tech team returns the coil code, the contact material and the module width that fit.
Why Panel Builders Source Interface Relays Through SUPERB
- Coil and terminal in one line: the order code is written with the coil voltage and the terminal style, so the module that arrives fits the signal and the row that is already wired.
- Gold versions listed separately: the low level contact option sits as its own row with its 50 mA limit, which stops a standard silver module being sent for a dry contact.
- Protection and LED stated: the freewheel diode, bridge rectifier and coil LED are named per family, so the panel drawing does not carry an external suppression part.
- Replacements across makers: Phoenix, Finder, Omron and Schneider rows share the 6.2 mm width, so a shortage on one brand has an equivalent in the same space.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail Terminal Blocks for Control Panel Wiring, Safety Relay Modules for Guard Monitoring, Phase Failure and Voltage Monitoring Relays, Timer Relays for Panel Control Sequences, PTC Thermistor Motor Protection Relays, DIN Rail Power Supplies for Control Cabinets.