Interface and Coupling Relays for DIN Rail

A 6.2 mm housing with one changeover contact at 6 A, so a PLC output drives a valve, a lamp or a small contactor without carrying the load itself. Coils run from 12 V DC to 230 V AC, with LED indication and a freewheel diode or bridge rectifier built into the base. The relay plugs into the base, so a failed part is changed without touching the field wiring. Gold contact versions hold 1 mA signals, which is what a dry contact or a multiplexer input needs.
quote now

Product Specifications

Product Overview

An interface relay sits between a control output and a field load and does three jobs at once. It separates the control circuit from the field circuit, so a fault on a 230 V valve coil cannot reach the PLC card. It amplifies, because a transistor output rated 0.5 A cannot close a 2 A load. And it converts, because the same family offers 24 V DC, 110 V AC and 230 V AC coils on the same 6.2 mm footprint. In a panel the part is chosen for the load, and the coil is chosen for whatever signal is available at that terminal.

Three physical forms cover the work. The complete module is a base with a relay already plugged in, ordered as one catalog number. The separate form is a socket plus a plug-in relay, which lets the relay be replaced without tools and lets a different contact material be fitted later. The third form is the slim module with screw, spring or push-in terminals, where the terminal style decides the wiring time rather than the electrical behaviour. All three take the same 35 mm rail, and all three are usually mixed in one panel.

The details that decide the part are rarely on the front of the catalog page. Coil current matters when eight channels share one output: 9 mA at 24 V DC means eight relays draw 72 mA, while a 230 V AC coil at 3.2 mA allows far more channels on the same card. Protection matters in the other direction: a DC coil needs a freewheel diode, an AC/DC coil needs a bridge rectifier, and both are built into the base on the Phoenix and Finder modules. Contact material matters for small signals, where a gold layer keeps a 1 mA dry contact readable and a plain silver alloy does not.

Key Specifications

ParameterValueNote
Width6.2 mm on Phoenix, Finder and Omron, 6 mm on Schneider RSLabout 32 channels in 200 mm of rail
Contact configuration1 changeover, single contact1 NO plus 1 NC used as an alternative on some frames
Rated contact current6 A general purpose10 A inrush for 4 s on the Phoenix base
Maximum switching voltage250 V AC/DC on Phoenix, 400 V AC on Finder 38.61, 440 V AC on Omronthe separating plate is needed above 250 V between adjacent modules
Rated load6 A at 250 V AC, 6 A at 30 V DC2.5 A at 250 V AC on an inductive load at cos phi 0.4
Coil voltages12, 24, 48, 110, 220 to 230 V AC and DCAC/DC wide range coils on the universal sockets
Coil current at 24 V DC9 mA typical at 24 V DC, 3.2 mA at 230 V ACthis is what limits the number of channels per output
Response and release time5 ms and 8 ms on Phoenix 24 V DC, 7 ms and 15 ms on 230 V ACthe AC coil is slower because of the bridge rectifier
Mechanical life10 million cycles on Finder, 20 million on Phoenixelectrical life 60,000 cycles at rated load on Finder
Contact materialAgSnO as standard, hard gold plated on the AU and AP versionsgold holds 1 mA at 100 mV, silver needs 10 mA at 12 V
Insulationrated insulation voltage 250 V, impulse withstand 6 kVtest voltage 4 kV AC between coil and contact
Ambient temperature-40 to +60 C in operation, -40 to +70 C on Finderderating applies when modules are stacked and all coils are held in
Mounting35 mm DIN rail to EN 60715, zero spacing in rowsseparating plate above 250 V between modules
ApprovalsUL and CSA on the listed combinations, ATEX and IECEx on the EX versioncheck the combination, not only the relay

Included Models and Order Codes

Order codes differ in what they carry. Phoenix puts the function in the name and the order number beside it, so PLC-RSC-24DC/21 is a screw terminal base with a 24 V DC coil and one changeover contact, catalog number 2966171, and the AU suffix marks the gold contact version. Finder writes five fields: 38.51.0.024.0060 is the 38 series, 6.2 mm wide, 24 V AC/DC coil, one changeover contact at 6 A, screw terminals, while 38.61 uses spring terminals and 39.31 is the 6 A relay set with a different base. Omron splits push-in and screw into G2RV-SR500 and G2RV-SR700. Schneider uses RSL1PV for the screw connector, RSL1PR for spring and RSL1AB4 for the replacement relay alone. The coil code is the field that decides whether the module fits the signal you have, so it is called out per row.

Part numberMakerCoilContactTerminalsNote
PLC-RSC-24DC/21 (2966171)Phoenix Contact24 V DC1 CO, 6 Ascrew9 mA coil, 5 ms response, 6.2 mm
PLC-RSC-230UC/21 (2966207)Phoenix Contact230 V AC, 220 V DC1 CO, 6 Ascrew3.2 mA at 230 V AC, bridge rectifier
PLC-RSC-24DC/21AU (2966265)Phoenix Contact24 V DC1 CO, goldscrew1 mA at 24 V, 50 mA limit on the gold layer
38.51.0.024.0060Finder24 V AC/DC1 CO, 6 Ascrew6.2 mm, LED and protection built in
38.51.0.230.0060Finder230 V AC1 CO, 6 Ascrewsame base, 230 V coil
38.61.0.024.0060Finder24 V AC/DC1 CO, 6 Aspringscrewless version of 38.51
38.61.8.240.0060Finder230 to 240 V AC1 CO, 6 AspringAC only coil on the screwless base
39.31.0.024.0060Finder24 V AC/DC1 CO, 6 Ascrew6.2 mm relay set, 94.3 mm depth
G2RV-SR500 DC24Omron24 V DC1 CO, 6 Apush-in1500 VA, 440 V AC maximum, 6.2 mm
G2RV-SR500 AC/DC24Omron24 V AC/DC1 CO, 6 Apush-inuniversal coil on the same base
G2RV-SR700 DC24Omron24 V DC1 CO, 6 Ascrewscrew terminal version of the SR500
G2RV-SR500-AP DC24Omron24 V DC1 CO, 50 mApush-ingold contacts for micro loads
RSL1PVBUSchneider RSL24 V AC/DC1 CO, 6 Ascrew6 mm wide, LED and protection module
RSL1PRBUSchneider RSL24 V AC/DC1 CO, 6 Aspringspring version of RSL1PVBU
RSL1AB4BDSchneider RSL24 V AC/DC1 CO, 6 Arelay onlyreplacement relay for the RSL base

Standard and Gold Contacts Side by Side

The contact material decides whether a small signal can be read at all. A silver alloy needs a wetting current to break through the surface film, and a gold layer does not, which is why the same 6 A module comes in two versions and why the gold one must not be used above its own current limit.

VersionMinimum switchingMaximum on the gold layerTypical use
AgSnO standard10 mA at 12 Vnot applicablevalve coils, lamps, small contactor coils, 230 V loads
Gold plated AU or AP1 mA at 100 mV, 100 mV at 10 mA50 mA at 30 V, 1.2 W at 24 V DCdry contacts, multiplexer inputs, analogue card signals
Gold version after a load event10 mA at 12 V once the layer is broken250 V AC/DC, 6 A continuousmixed panels where one channel occasionally drives a lamp

Key Features

6.2 mm for the whole family – Phoenix, Finder and Omron share the width, so a channel added later fits the gap left in the row without re-drilling the rail.

Coil current published – 9 mA at 24 V DC and 3.2 mA at 230 V AC are on the row, which is what decides how many channels one output can drive.

Protection inside the base – freewheel diode on DC coils and a bridge rectifier on AC/DC coils are part of the module, not an accessory on the drawing.

Gold contact option – the AU and AP versions hold a 1 mA signal and are listed separately, because a standard silver contact will not read a dry contact reliably.

Plug-in relay with a retaining clip – the relay lifts out of the base with the clip, so a replacement takes seconds and the field wiring stays where it is.

Terminal style in the code – screw, spring and push-in are separate part numbers, so the wiring method is chosen at order time rather than at the panel.

Yellow LED on the coil circuit – the LED follows the coil, not the contact, so a missing signal and a welded contact look different during fault finding.

Applications

The three cases below cover most of the interface relay orders we quote, and each one is decided by a different number on the page.

Machine control panels – a PLC card with 16 outputs drives 16 valve coils, and the interface relay carries the 2 A inductive load and the freewheel energy that the card output cannot.

Retrofit of an older relay logic panel – existing 110 V AC control circuits meet a new 24 V DC controller, and the wide range AC/DC coil on the universal socket bridges the two voltages without a second transformer.

Process skids with long field runs – a 230 V signal travels 80 m to a solenoid and a fault on that cable must not reach the control card, so the relay sits at the panel end and the separation is the point of the part.

The controller board behind these channels is often quoted with the panel, so the SUPERB PCBA and the SUPERB PCB are reviewed against the same channel list and the coil current per output is checked once for both.

Sourcing and Cross-Reference

These modules are ordered in tens and hundreds, and the two things that go wrong are the coil voltage and the terminal style. A panel wired with spring terminals cannot take a screw module without re-terminating the row, and a 24 V DC module on a 110 V AC signal is a dead channel that looks like a wiring fault. Both are in the order code, so the first check on a shortage is the full code rather than the family name.

The second question is the small signal case. Where a channel reads a dry contact, a thermostat or a multiplexer input, a standard silver contact will read open until the current rises above 10 mA, and the fault appears only on the bench. The gold version is the answer, and it has its own current limit, so the row that carries it also states that limit.

For a panel waiting on one coil voltage, the options are usually the same module in the AC/DC universal coil, the equivalent module from another maker in the same 6.2 mm width, or the separate socket and relay form where only the relay is short. See lead time and availability for a specific code, and obsolete part cross reference where a module has been discontinued.

The SUPERB Assembly team labels each module with the channel number before it goes on the rail, because a row of identical 6.2 mm modules is impossible to trace once the duct cover is on.

Q: Can you supply the 24 V DC gold contact version and confirm the coil current and minimum load per channel?

A: Yes. Send the signal voltage, the field load current, the terminal style and whether the load is a dry contact, and the SUPERB Tech team returns the coil code, the contact material and the module width that fit.

Why Panel Builders Source Interface Relays Through SUPERB

  1. Coil and terminal in one line: the order code is written with the coil voltage and the terminal style, so the module that arrives fits the signal and the row that is already wired.
  2. Gold versions listed separately: the low level contact option sits as its own row with its 50 mA limit, which stops a standard silver module being sent for a dry contact.
  3. Protection and LED stated: the freewheel diode, bridge rectifier and coil LED are named per family, so the panel drawing does not carry an external suppression part.
  4. Replacements across makers: Phoenix, Finder, Omron and Schneider rows share the 6.2 mm width, so a shortage on one brand has an equivalent in the same space.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail Terminal Blocks for Control Panel Wiring, Safety Relay Modules for Guard Monitoring, Phase Failure and Voltage Monitoring Relays, Timer Relays for Panel Control Sequences, PTC Thermistor Motor Protection Relays, DIN Rail Power Supplies for Control Cabinets.