Safety Relay Modules for Guard Monitoring
Product Specifications
Product Overview
A safety relay is the part that decides whether a machine may run. Two input channels watch the guard switch or the light curtain, the internal circuit compares them, and three positive guided contacts carry the enable signal to the contactors. When one channel opens, or when the two channels no longer agree, the contacts open and the drive stops.
The difference from a standard relay is not the coil. It is the guided contact set, the redundancy inside, and the diagnostics on the input side. A dual-channel unit with cross-short detection will open when the two input wires are shorted together, which is exactly the fault a single-channel circuit cannot see. That detection is what allows the module to be used at Category 4 and PL e.
Three numbers decide the order: how many safety contacts leave the module, what supply the panel offers, and how wide the housing can be. Three safety contacts plus one auxiliary contact in a 22.5 mm housing is the common shape, and a 45 mm body is used when the output has to switch a large contactor coil or when four safety circuits are needed.
Key Specifications
| Family | Input channels | Safety outputs | Auxiliary output | Supply | Safety level | Width |
|---|---|---|---|---|---|---|
| Pilz PNOZ X2.8P | 1 or 2, with or without cross-short detection | 3 NO, instantaneous | 1 NC | 24 V AC/DC, or 24 to 240 V AC/DC | Category 4, PL e, SIL 3 | 22.5 mm |
| Omron G9SB 300 series | 2, with cross-short detection | 3 NO | 1 NC | 24 V AC/DC | PL e depending on wiring | 22.5 mm |
| Omron G9SB 200 series | 1 or 2 | 2 NO | none | 24 V AC/DC | PL e depending on wiring | 17.5 mm |
| Schmersal SRB 301HC | 2, cross-short, wire break and earth fault detection | 3 NO | 1 NC | 24 V AC/DC, or 48 to 240 V AC | Category 4, PL e, SIL 3 | 45 mm |
Included Models and Order Codes
The rows below are the modules we quote most often for a guard door or an E-stop circuit. On Pilz the last three digits carry both the supply and the terminal type, so 777301 and 787301 are the same module on screw and on spring terminals. On Omron the tail sets the reset mode, A for automatic and C for manual. On Schmersal the voltage suffix is part of the type, and the T version of the same body carries 8 A contacts instead of 6 A. Response time is the time from the input opening to the safety contact opening.
| Part number | Family | Safety contacts | Auxiliary | Supply | Response time | Note |
|---|---|---|---|---|---|---|
| 777301 | PNOZ X2.8P, screw terminals | 3 NO | 1 NC | 24 V AC/DC | 30 ms at E-stop, 150 ms at mains off | input current 30 mA |
| 787301 | PNOZ X2.8P C, spring terminals | 3 NO | 1 NC | 24 V AC/DC | 30 ms at E-stop, 150 ms at mains off | same module, tool free wiring |
| 777302 | PNOZ X2.8P, screw terminals | 3 NO | 1 NC | 24 to 240 V AC/DC | 30 ms at E-stop, 150 ms at mains off | input current 25 mA |
| 787302 | PNOZ X2.8P C, spring terminals | 3 NO | 1 NC | 24 to 240 V AC/DC | 30 ms at E-stop, 150 ms at mains off | universal supply |
| G9SB-2002-A | G9SB, 17.5 mm | 2 NO | none | 24 V AC/DC | 10 ms | 2 channel, automatic reset |
| G9SB-2002-C | G9SB, 17.5 mm | 2 NO | none | 24 V AC/DC | 10 ms | 2 channel, manual reset |
| G9SB-3010 | G9SB, 17.5 mm | 3 NO | 1 NC | 24 V DC | 10 ms | direct breaking, no input channels |
| G9SB-3012-A | G9SB, 22.5 mm | 3 NO | 1 NC | 24 V AC/DC | 10 ms | 2 channel, automatic reset |
| G9SB-3012-C | G9SB, 22.5 mm | 3 NO | 1 NC | 24 V AC/DC | 10 ms | 2 channel, manual reset |
| SRB 301HC/R-24V | SRB 301HC, 45 mm | 3 NO | 1 NC | 24 V AC/DC | on request | 250 V, 6 A contacts |
| SRB 301HC/R-230V | SRB 301HC, 45 mm | 3 NO | 1 NC | 48 to 240 V AC | on request | 250 V, 6 A contacts |
| SRB 301HC/T-24V | SRB 301HC, 45 mm | 3 NO | 1 NC | 24 V AC/DC | on request | 250 V, 8 A ohmic contacts |
Input Modes and What Each One Detects
The wiring mode is chosen on site, and it changes what the module can see. A single-channel circuit uses one contact and cannot detect a short between the two input wires. A dual-channel circuit without cross-short detection sees an open channel but not a short between channels. Only the third mode covers both faults, and it is the mode that supports Category 4. The universal supply version of the Pilz module does not offer light-beam monitoring with cross-short detection, so a light curtain needs the 24 V version.
| Mode | Inputs used | Faults detected | Typical device |
|---|---|---|---|
| Single channel | S11 to S12 only | open circuit, earth fault on the input | one positive opening switch |
| Dual channel, no cross-short detection | S11 to S12 and S21 to S22 | open circuit, earth fault, channel disagreement | two positive opening switches |
| Dual channel with cross-short detection | S11 to S12 and S21 to S22, plus S52 test pulse | all of the above plus a short between channels | safety gate with two switches, light curtain |
| Monitored start | feedback loop in the reset circuit | welded contactor contact, start button held down | contactor with guided contacts |
Key Features
Positive guided contacts – the auxiliary contact cannot close while a safety contact is welded, so a status signal in the PLC tells the truth about the output.
Three safety outputs on one body – three independent NO circuits in a 22.5 mm housing, enough for main contactor, brake contactor and a second drive without an expander module.
Cross-short detection – a short between the two input wires opens the module instead of leaving the machine enabled, which is the fault the single-channel circuit cannot see.
Universal supply on one type – the 24 to 240 V AC/DC version runs from a control transformer or from a 24 V rail, so the same spare fits several panels.
Screw or spring terminals – the same module is ordered with either terminal, and the spring version is wired without a torque check after every service visit.
Feedback loop for contactor monitoring – the NC contact of the contactor is wired back to the module, so a welded main contact stops the next start instead of allowing a restart.
Applications
Guard monitoring is the same circuit in three different shapes. Each one sets the number of channels and the reset mode.
Hinged guard door on a machine cell – two positive opening switches on the door, dual channel with cross-short detection, manual reset so the operator has to look inside before restart.
Light curtain on a press feed – two OSSD outputs into a dual-channel module that detects shorts across the two channels, with the machine stop wired through two safety contacts in series.
E-stop circuit in a control cabinet – a latching mushroom head into a single-channel module with automatic reset, where the module also drops the main contactor and the drive enable.
The guard circuit is quoted with the board that runs the cell, so the SUPERB PCBA and the SUPERB PCB are checked against the same machine list and the module supply agrees with the panel rail.
Sourcing and Cross-Reference
Count the outputs before choosing the family. A guard door with one contactor needs one safety contact, but a cell with a main contactor, a brake contactor and a drive enable needs three, and a fourth circuit means an expander module that costs more than the wider body. Three safety contacts plus one auxiliary is the shape that covers most cells without an expander.
Match the input mode to the device, not to the habit. A light curtain needs cross-short detection, an E-stop with one latching contact works on a single channel, and a safety mat needs a four-wire module that is a different product. Ordering a single-channel module for a light curtain is the mistake that fails the first risk assessment.
Check the supply the panel already has. A 24 V AC/DC module runs from the same rail as the PLC, and the universal 24 to 240 V AC/DC version is the spare that fits a panel with a 110 V control transformer. A module ordered on the wrong voltage does not pull in and shows as a guard fault, which is easy to misdiagnose.
Response time belongs in the safety distance calculation. The module adds 10 to 30 ms to the opening time of the guard switch and the drop-out time of the contactor, so a light curtain mounted at the minimum distance can be pushed outside the calculated reach by a slow module. See lead time and availability when the panel schedule is short, and shortage recovery when the original module is on allocation.
The SUPERB Assembly team wires the dual-channel input with two separate cores and a test pulse to S52, because a shared return hides the short the module is meant to find.
Q: Can you supply the safety relay together with the guard switches and the contactors it drives, matched on one drawing?
A: Yes. Send the guard device type, the number of contactors to be switched, the control voltage in the panel and the required PL or SIL, and the SUPERB Tech team returns the module, the reset mode and the terminal type that fit.
Why Panel Builders Buy Safety Relays From SUPERB
- Outputs and voltage checked together: the module, the contactor coil and the guard switch are compared on the same list, so a 24 V module never ships against a 110 V control circuit.
- Response time stated per part: the drop-out figure is in the table, which is the number the safety distance calculation needs.
- Guided contacts only: every module quoted has positive guided outputs, so the feedback loop to the PLC carries a real signal.
- Spare parts carried for installed panels: the same body in screw and in spring terminals is quoted as a pair, which keeps a service spare that drops into the existing cut-out.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Door Interlock Switches for Safety Circuits, Contactors and Reversing Contactors for Motor Loads, Signal Towers and Stack Lights for Machine Status, Rocker and Toggle Switches for Equipment Panels, DIN Rail Terminal Blocks for Control Panel Wiring.