PTC Thermistor Motor Protection Relays for Winding Temperature
Product Specifications
Product Overview
A current based overload relay works from a thermal image of the motor. That image is a good estimate when the motor runs at its rated duty, and a poor one when it does not. Heavy starting, a long acceleration ramp on a drive, repeated braking, a fan that is clogged, or a motor in a hot enclosure can all take the winding past its limit while the current stays inside the setting. The winding is where the damage happens, so the direct answer is to measure the winding.
A PTC thermistor relay does that with no extra transducer. The motor maker fits type A PTC sensors per DIN 44081 and DIN 44082 into the winding overhangs, usually one per phase, wired in series and brought out to two terminals. Cold, the chain reads a few tens to a few hundred ohms. At the rated response temperature the resistance of each sensor jumps by several orders of magnitude, the chain goes above the trip threshold, and the relay drops its output. Because the sensor is a resistor and not a thermocouple, the cable between motor and panel can be long, and the relay does not need cold junction compensation or a shielded pair.
The settings that decide the part number are the number of sensor circuits, the reset mode, the supply and the contact arrangement. A single circuit is enough for one motor. Two circuits let one relay give a warning at a lower temperature and trip at the higher one, which is how a large motor is taken off load before it is stopped. Reset mode matters more than it looks: an auto reset relay restarts the machine as soon as the winding cools, while a manual or non volatile type holds the trip until someone acknowledges it, which is what a fault log and a safe restart need.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Sensor type | PTC type A, DIN 44081 and DIN 44082 | up to 6 sensors in series on one measuring circuit |
| Cold resistance of the sensor chain | below 750 Ohm, up to 1.5 kOhm on the Eaton part | the chain is shorted or open only on a fault |
| Trip threshold | 2.7 to 3.1 kOhm | 2.83 kOhm on the ABB CM-MSS.11, 3.6 kOhm on the Eaton EMT6 |
| Reset threshold | 1.1 to 1.65 kOhm | 1.6 kOhm on the Eaton EMT6 |
| Voltage in the sensor circuit | 5.5 V DC maximum | 2.5 V at 1.33 kOhm, 3.7 V at 4 kOhm on the ABB part |
| Current in the sensor circuit | 3.7 mA maximum | keeps self heating of the sensor negligible |
| Sensor cable length | 2 x 100 m at 0.75 mm2, 2 x 400 m at 2.5 mm2 | Schneider LT3 allows 500 m at 1.5 mm2 and 1000 m at 2.5 mm2 |
| Output contacts | 1 CO, 1 NO plus 1 NC, or 2 CO | relay output, closed circuit principle |
| Contact rating AC-15 at 230 V AC | 3 A | 4 A at AC-12 on the ABB part |
| Contact rating DC-13 | 1 A at 24 V, 0.2 A at 125 V, 0.1 A at 250 V | Siemens 3RN2 figures |
| Rated control supply | 24 V AC DC, or 24 to 240 V AC DC | ABB CM-MSS.13 uses 110 to 130 V and 220 to 240 V AC |
| Power consumption | 0.55 VA at 24 V AC DC, 1.6 VA at 220 to 240 V AC | Siemens 3RN2010 is 0.9 W |
| Reaction time of the safety function | below 100 ms | ABB CM-MSS.12 and CM-MSS.13 |
| Mechanical life | 30 million operations | 10 million on the compact 17.5 mm Siemens body |
| Width and mounting | 17.5 mm or 22.5 mm, 35 mm rail to EN 60715 | Eaton EMT6 is 23 mm wide |
| Ambient temperature | -25 to +60 C in operation | -40 to +85 C in storage |
| Standards | IEC 60947-8, UL 508, CSA C22.2 No.14 | IEC 60034-11 and VDE 0660 on the Schneider part |
| Hazardous area approval | ATEX Ex II (2) G and D, SIL 1 per EN 50495 | 3RN2011, 3RN2012, 3RN2013 and 3RN2023 |
Included Models and Order Codes
The list below is grouped by maker because the type code carries the settings differently. On the Siemens 3RN2 the order code is a compact block: 3RN2010 with a 1 NO plus 1 NC or a 2 CO contact set, then a supply letter A for 24 V or W for 24 to 240 V, then the terminal digit. The ABB CM-MSS range puts the measuring circuit count in the first digit after the dot: 11 is one circuit with a separate NO and NC contact, 12 and 13 are one changeover contact on 24 V and on 110 to 240 V. The Schneider LT3SM family is listed with its control voltage in the last letter, E for 24 to 48 V, M for 115 to 230 V and V for 400 V. Ratings below are the ones printed on the maker data sheet; where a maker does not publish a value for a part, the cell says so rather than carrying a figure across from another family.
| Part number | Contacts | Control supply | Reset | Sensor circuits | Note |
|---|---|---|---|---|---|
| 3RN2010-1CA30 | 1 NO + 1 NC | 24 V AC DC | auto | 1 | 17.5 mm compact body, bimetallic switch input |
| 3RN2010-1CW30 | 1 NO + 1 NC | 24 to 240 V AC DC | auto | 1 | same body on a multi voltage supply |
| 3RN2010-1BA30 | 2 CO | 24 V AC DC | auto | 1 | 22.5 mm standard body |
| 3RN2010-1BW30 | 2 CO | 24 to 240 V AC DC | auto | 1 | standard body, multi voltage |
| 3RN2011-1BW30 | 2 CO | 24 to 240 V AC DC | manual and remote | 1 | ATEX, open circuit and short circuit detection |
| 3RN2012-1BW30 | 2 CO | 24 to 240 V AC DC | manual, auto and remote | 1 | ATEX, non volatile trip memory |
| 3RN2013-1BW30 | 2 CO | 24 to 240 V AC DC | manual, auto and remote | 1 | protective separation up to 300 V, non volatile |
| 3RN2023-1DW30 | 1 NO + 1 CO | 24 to 240 V AC DC | manual, auto and remote | 2 | one circuit for warning, one for trip |
| CM-MSS.11S | 1 NO + 1 NC | 24 to 240 V AC DC | auto | 1 | wire break detection, non volatile fault storage, screw terminals |
| CM-MSS.12S | 1 CO | 24 V AC DC | auto | 1 | 22.5 mm wide, push-in version is CM-MSS.12P |
| CM-MSS.13S | 1 CO | 110 to 130 V or 220 to 240 V AC | auto | 1 | two supply ranges on one part, push-in version .13P |
| EMT6(230V) 066400 | 1 NO + 1 NC | 230 V AC 50/60 Hz | auto, no manual reset | 1 | 23 mm wide, trip at 3.6 kOhm, reset at 1.6 kOhm |
| LT3SM00E | 1 NO + 1 NC | 24 to 48 V AC | manual | 1 | Schneider TeSys LT3, probe short circuit detection |
| LT3SM00M | 1 NO + 1 NC | 115 to 230 V AC 50/60 Hz | manual | 1 | trip at 2.7 to 3.1 kOhm, reset at 1.5 to 1.65 kOhm |
| LT3SM00V | 1 NO + 1 NC | 400 V AC 50/60 Hz | manual | 1 | for panels without a control transformer |
| LT3SM00MW | 2 CO | 24 to 230 V AC | manual and automatic | 1 | wide range supply, two changeover contacts |
What the Trip and Reset Thresholds Mean in Practice
The two resistance values on the data sheet are not a tolerance band around one setting, they are two separate decisions. The trip threshold is where the output opens, and the reset threshold is where it closes again. The gap between them is deliberate, and it is the reason the relay does not chatter when a hot motor cools slowly against a cold ambient.
| Situation | Resistance seen at T1 and T2 | What the relay does |
|---|---|---|
| Motor cold, sensor chain healthy | 40 to 300 Ohm, below 750 Ohm in total | output stays energised, READY lamp on |
| Winding at rated response temperature | rises through 2.7 to 3.1 kOhm | output drops, TRIPPED lamp on, machine stop circuit opens |
| Winding cooling after the trip | falls to 1.1 to 1.6 kOhm | auto reset types re energise, manual types wait for the button |
| Sensor lead broken | resistance goes to open circuit | detected on the 3RN2011, 3RN2012, 3RN2013, 3RN2023 and CM-MSS.11 |
| Sensor shorted | resistance near zero | detected on parts with short circuit monitoring, relay refuses to start |
Key Features
Winding temperature, not a thermal image – the sensor sits inside the winding overhang, so the relay sees the same temperature the insulation sees, including the parts of the duty that a current based relay cannot model.
Trip and reset thresholds held apart – trip at 2.7 to 3.1 kOhm and reset at 1.1 to 1.65 kOhm gives a wide band between the two states, which is what keeps a hot motor from cycling its contactor while it cools.
Sensor circuit kept at 5.5 V and 3.7 mA – the measuring current is low enough that the sensor does not heat itself and shift its own response temperature, a point that matters when six sensors sit in series.
ATEX versions for gas and dust areas – 3RN2011, 3RN2012, 3RN2013 and 3RN2023 carry Ex II (2) G and D approval and SIL 1 per EN 50495, so a motor in a hazardous area keeps its certification path.
Non volatile trip memory – on the 3RN2012, 3RN2013 and CM-MSS.11 a trip survives a control supply failure, so a machine cannot restart after a power dip without an acknowledgement.
Two sensor circuits on one relay – the 3RN2023 gives a warning contact and a trip contact from two separate PTC chains, which is how a large motor is unloaded before it is stopped.
Applications
These relays are chosen by the duty that defeats a current based overload relay, so the three cases below cover most of the panels we quote.
Heavy starting and high inertia loads – a crusher, a conveyor or a centrifuge can draw close to rated current for a minute or more while the winding heats faster than the current suggests, and the PTC chain trips on the temperature the overload relay cannot see.
Motors fed from a variable frequency drive – the drive output is not a sine wave, so the thermal model inside an overload relay drifts from the real winding temperature at low speed and at high carrier frequency, while the PTC sensor does not care what the supply looks like.
Braking duty and restricted cooling – a brake motor that stops a load several times a minute, or a motor in a sealed enclosure with a dirty fan, overheats without a current rise, and this is the case where a thermistor relay is the only protection that reacts.
The motor circuit is quoted with the board that controls it, so the SUPERB PCBA and the SUPERB PCB are checked on the same terminal list and the relay coil shares the panel control voltage.
Sourcing and Cross-Reference
Most of the parts on this page are sold as a panel line item, not as a single spare, so the practical question is which family is already in the drawing. The Siemens 3RN2 code is the one that shows up on European machine drawings, the ABB CM-MSS on process panels, and the Eaton EMT6 where the panel was built around Moeller components. A relay from one family can replace another only if the contact arrangement and the reset behaviour match, because the sensor circuit is compatible across all of them.
The Schneider LT3SM family was discontinued in 2023 and has no direct replacement from the same maker, which makes it the one line on this page where last time buy and cross reference matter. The electrical function is not hard to match, a 1 NO plus 1 NC contact set with a manual reset and a 2.7 to 3.1 kOhm trip point, but the panel cut out and the terminal spacing have to be checked before a substitute goes in. Where the original is still in a spares list, we keep the LT3SM references visible so the comparison can be made part by part.
For panels that are waiting on one relay to ship, the alternatives are usually a different contact set in the same family, a push-in version of the same body, or a 24 to 240 V part that covers the control voltage already on the rail. See lead time and availability for the stock position and obsolete part cross reference for the LT3SM equivalents.
The SUPERB Assembly team keeps the sensor pair on its own terminals rather than sharing a terminal with the contactor coil, because a shared terminal hides which device opened the stop circuit.
Q: Can you supply a thermistor relay as a drop in replacement for a discontinued LT3SM part, with the same contact arrangement?
A: Yes. Send the motor rating, the number of PTC sensors in the winding, the control voltage and the contact arrangement, and the SUPERB Tech team returns the part number and the reset mode that fit.
Why Panel Builders Buy Thermistor Relays From SUPERB
- Thresholds printed per part: trip and reset resistance, sensor circuit count and reset behaviour sit on the same row, so a substitute is compared on values rather than on a picture.
- Supply written out: 24 V, 24 to 240 V and the two ABB ranges are separated on the list, which avoids the common mistake of ordering a 24 V part for a 230 V panel.
- ATEX and standard parts side by side: the hazardous area versions are marked in the same table as the standard ones, so a project with two motor types does not need two lists.
- Obsolete references kept visible: the LT3SM family stays on the page with its ratings, which is what a maintenance team needs when the spare is no longer orderable.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads, Phase Failure and Voltage Monitoring Relays, DIN Rail Terminal Blocks for Control Panel Wiring.