Timer Relays for Panel Control Sequences
Product Specifications
Product Overview
A timer relay is the cheapest way to put a delay into a panel. A contactor has to drop out after a pump has run on, a star delta starter needs a transfer gap, a fan has to keep running for two minutes after the drive stops, and none of those jobs needs a controller. The timer sits on the DIN rail, takes the same coil voltage as the contactor beside it, and closes a contact when the time has elapsed.
The reason a panel builder keeps a timer in the parts list is isolation. The timing contact is a dry changeover contact, so it can switch a contactor coil at 230 V AC while its own supply comes from a 24 V rail, and the two circuits never share a terminal. That is different from a PLC output, which brings its own common and its own current limit, and it is why a timer survives a retrofit into an old panel where the control voltage is unknown until the cover comes off.
Choosing one comes down to three settings on the front: the function, the time range and the supply. The function decides what the output does relative to power or to a control signal, the range decides the resolution of the dial, and the supply decides whether one part number covers 24 V and 230 V panels. On the range that is worth checking, a 0.1 to 2 s scale on a 24 h job is useless, and a 1 to 20 min scale cannot set a 3 s star delta transfer.
Key Specifications
| Parameter | Value on the multi function type | Note |
|---|---|---|
| Contact configuration | 1 CO (SPDT) | dry changeover, common plus NO and NC |
| Rated current | 16 A, 30 A peak | 250 V AC rated voltage, 400 V maximum switching |
| Rated load AC1 | 4000 VA | resistive load at 250 V AC |
| Rated load AC15 at 230 V AC | 750 VA | contactor coil and small solenoid load |
| Single phase motor at 230 V AC | 0.55 kW | direct switching of a small motor |
| DC1 breaking capacity | 16 A at 24 V, 0.3 A at 110 V, 0.12 A at 220 V | DC load falls away quickly with voltage |
| Contact material | AgNi | standard on the 16 A range |
| Supply voltage | 12 to 240 V AC or DC on one part | operating range 10.8 to 265 V |
| Rated power | below 1.8 VA at 50 Hz, below 1 W DC | multi voltage input, no link to change |
| Time ranges | 0.1 to 2 s, 1 to 20 s, 0.1 to 2 min, 1 to 20 min, 0.1 to 2 h, 1 to 24 h | six scales on one dial |
| Width and mounting | 17.5 mm, 35 mm rail to EN 60715 | one module, screw or box clamp terminals |
Included Models and Order Codes
The type number carries the function and the supply. On the 80 series the first two digits after the series mark are the function: 01 is multi function, 11 on delay, 21 interval, 41 off delay with a control signal, 51 multi function at 8 A, 61 true off delay, 71 solid state output. The next group is the supply, 240 for the 24 to 240 V AC DC input, and the tail is the version and packing. The last four digits matter: a part ending 0000 is the standard version, and a different tail is a different terminal or a rail variant.
| Part number | Function | Time ranges | Contact | Supply | Note |
|---|---|---|---|---|---|
| 80.01.0.240.0000 | multi function, six functions selectable | 0.1 s to 24 h, six scales | 1 CO, 16 A | 12 to 240 V AC DC | the general purpose part for a panel stock list |
| 80.11.0.240.0000 | on delay | 0.1 s to 24 h, six scales | 1 CO, 16 A | 24 to 240 V AC DC | one function, fewer settings to disturb |
| 80.21.0.240.0000 | interval, contact closes on power up | 0.1 s to 24 h, six scales | 1 CO, 16 A | 24 to 240 V AC DC | run on time for a pump or a fan |
| 80.41.0.240.0000 | off delay with a control signal | 0.1 s to 24 h, six scales | 1 CO, 16 A | 24 to 240 V AC DC | supply stays on, the signal starts the delay |
| 80.51.0.240.0000 | multi function, six functions selectable | 0.1 s to 24 h, six scales | 1 CO, 8 A | 24 to 240 V AC DC | 8 A version where the load is a small coil |
| 80.61.0.240.0000 | true off delay, power removed starts the time | 0.05 to 2 s, 1 to 16 s, 8 to 70 s, 50 to 180 s | 1 CO, 8 A | 24 to 240 V AC DC | needs 500 ms of supply before timing starts |
| 80.71.0.240.0000 | multi function, solid state output | 0.1 s to 24 h, six scales | 1 A output, 24 to 240 V AC DC | 24 to 240 V AC DC | no contact wear, for a lamp or a small relay |
The Six Functions in Words
The letters on the front of a multi function timer are not obvious from the drawing, and picking the wrong one is the usual reason a sequence runs backwards. The table below is the behaviour of each function against power and against the control signal, in the wording used on the data sheet.
| Code | Name | What starts the delay | What the contact does |
|---|---|---|---|
| AI | on delay | power applied to the timer | closes after the set time and stays closed until power is removed |
| DI | interval | power applied to the timer | closes at once, resets after the set time while power remains |
| SW | symmetrical flasher | power applied to the timer | cycles on and off with equal times for as long as power is applied |
| BE | off delay with control signal | control signal opened | closes with the signal, and resets after the set time once the signal opens |
| CE | on and off delay with control signal | signal closed, then opened | closes after the delay on closing, resets after the same delay on opening |
| DE | interval with control signal on | signal closed | closes with the signal and resets after the set time even if the signal is held |
| BI | true off delay | power removed | closes at once on power up, resets after the set time from the moment power is lost |
| SD | star delta | power applied to the timer | star contact opens first, then the delta contact closes after a transfer time of 0.05 to 1 s |
Key Features
One part covers 24 V and 230 V panels – the input accepts 12 to 240 V AC or DC with an operating range of 10.8 to 265 V, so a panel stock line does not have to carry a 24 V and a 230 V version of the same function.
Six time ranges on one dial – 0.1 to 2 s up to 1 to 24 h, changed by the range selector rather than by a part number, which keeps the resolution usable at both ends of the scale.
16 A changeover contact – 4000 VA at AC1 and 750 VA at AC15 on the 16 A types, enough to switch a contactor coil or a small single phase motor without an interposing relay.
Front adjustment with two screwdrivers – the range and function selectors and the timing trimmer all take a flat blade or a cross head, so a service call does not depend on the one tool in the bag.
True off delay without a permanent signal – the 80.61 starts timing when power is removed and holds its contact closed on the energy stored in the part, which is what a run on fan needs when the control circuit is switched off.
Solid state output where the load is a lamp – the 80.71 replaces the contact with a 1 A output rated 24 to 240 V AC DC, independent of the input voltage, so an indicator or a small relay can be timed without contact wear.
Applications
Timers are bought by the function they perform in the sequence, not by the timing range. These three cover most of the panels we quote.
Star delta and soft starter sequences – the transfer gap between star and delta has to be long enough for the motor to slow and short enough to avoid a current spike, and the star delta timer sets it with an adjustable 0.05 to 1 s transfer after the main delay.
Pump and fan run on – a true off delay holds the contactor closed after the control circuit is switched off, which is how a fan keeps moving air over a heater or a pump clears a line before the valve closes.
Guard and door delay – an off delay with a control signal keeps a lock released or a lamp on for a set time after the guard switch opens, using the switch as the signal rather than the supply.
The sequence is quoted with the board that drives it, so the SUPERB PCBA and the SUPERB PCB are checked on the same terminal list and the timer coil shares the panel control voltage.
Sourcing and Cross-Reference
Order by function and supply, not by the picture. Two timers that look identical on the rail can be an on delay and an interval type, and the difference only shows up when the machine is commissioned. If a drawing lists an old part number, the function letter on the front of the existing timer is the reliable reference, and the six function types will cover it without a change to the wiring.
Check the load before the contact rating. A 16 A contact is rated 4000 VA at AC1 but only 750 VA at AC15, and a contactor coil with a high inrush can be well above what the label suggests. Where the load is a DC coil or a lamp, the DC1 figures fall away quickly with voltage, 16 A at 24 V against 0.12 A at 220 V, and a small interposing relay is the safer answer than a bigger timer.
Delivery on timers is usually a stock question rather than a lead time question, because the same 17.5 mm body is made in many versions. Where a specific function or supply is not on the shelf, see lead time and availability for the alternatives, and shortage recovery when a panel is waiting on one timer to ship.
The SUPERB Assembly team keeps the timing contact on its own pair of terminals rather than on the contactor coil terminal, because a shared terminal hides which device started the sequence.
Q: Can you supply the timer with the contactor, the overload relay and the terminal blocks it wires to, on one list for the panel?
A: Yes. Send the sequence, the supply voltage and what the contact has to switch, and the SUPERB Tech team returns the function code, the time range and the part number that fit.
Why Panel Builders Buy Timer Relays From SUPERB
- Function stated per part number: every row says which of the six functions the part performs, so a stock item is not ordered twice under two descriptions.
- Contact rating and load in the open: AC1, AC15, motor and DC1 figures sit beside the part, which is what decides whether an interposing relay is needed.
- Range and supply on the same line: the six time scales and the 24 to 240 V input are written per part, so a retrofit does not turn into a second order.
- Rail and width consistent: 17.5 mm on 35 mm rail across the family, so a replacement fits the space the old timer came out of.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, Phase Failure and Voltage Monitoring Relays, Digital Panel Meters and Counters for Control Panels, DIN Rail Terminal Blocks for Control Panel Wiring.