Contact Us

DIN Rail Power Supplies for Control Cabinets

DIN rail supplies from 120 to 960 W in 12, 24 and 48 V versions. Universal 90 to 264 V AC input on the single phase families, 3-phase types for higher power. TS35/7.5 and TS35/15 mounting, with output adjustment and short circuit protection. Redundancy modules for a 24 V rail that must not drop on one supply failure.
quote now

Product Specifications

Product Overview

A DIN rail power supply is the part of a cabinet that turns the incoming AC into the 24 V that the relays, the sensors and the indicator lamps use. It is also the part that fails first when the cabinet is hot, because the electrolytic capacitors inside age with temperature and the unit is usually mounted at the top of the rail, where the air is warmest.

The family is chosen on three figures: output voltage, output current, and input range. A 24 V 5 A unit at 120 W covers a panel with a dozen relays and a few sensors; a 24 V 10 A unit at 240 W is the normal size for a drive cabinet with contactors and a brake. The 48 V versions are used for PoE injectors, telecom equipment and motor drives, and the 12 V versions for LED indication and small sensors.

Two details decide whether the supply survives. The first is derating: a unit rated at 5 A in free air gives less inside a closed cabinet at 55 C, and the maker curve has to be read at the actual temperature. The second is inrush: a row of contactors and a bank of capacitors on the same 24 V rail can trip a supply into constant current at switch-on, which looks like a dead supply but is a load problem.

Key Specifications

FamilyPowerOutputsInputEfficiencyMounting
NDR-120120 W12 V 10 A, 24 V 5 A, 48 V 2.5 A90 to 264 V AC85.5 to 89 percentTS35/7.5 or TS35/15
NDR-240240 W24 V 10 A, 48 V 5 A90 to 264 V AC88.5 to 90 percentTS35/7.5 or TS35/15
EDR-120120 W12 V 10 A, 24 V 5 A, 48 V 2.5 A90 to 264 V AC85 to 88.5 percentTS35/7.5 or TS35/15
TDR-240 and TDR-960240 and 960 W24 V 10 A, 24 V 40 A, 48 V versions3-phase 340 to 550 V AC92 to 94.5 percentTS35/7.5 or TS35/15
DR-120 and DRP-240120 and 240 W24 V 5 A, 24 V 10 A115 or 230 V AC selectable84 percentTS35/7.5 or TS35/15

Included Models and Order Codes

The codes below are the 24 V versions that are quoted most often, plus two 12 V and 48 V parts for indication and telecom work. Mounting is TS35 on every model in the table. The dimensions differ by family, so a replacement in an existing cabinet needs the width checked as well as the current.

Part numberOutputRated currentRated powerInputEfficiency
NDR-120-1212 V10 A120 W90 to 264 V AC85.5 percent
NDR-120-2424 V5 A120 W90 to 264 V AC88 percent
NDR-120-4848 V2.5 A120 W90 to 264 V AC89 percent
NDR-240-2424 V10 A240 W90 to 264 V AC88.5 percent
NDR-240-4848 V5 A240 W90 to 264 V AC90 percent
EDR-120-2424 V5 A120 W90 to 264 V AC87.5 percent
EDR-120-4848 V2.5 A120 W90 to 264 V AC88.5 percent
TDR-240-2424 V10 A240 W3-phase 340 to 550 V AC92 percent
TDR-960-2424 V40 A960 W3-phase 340 to 550 V AC94 percent
DR-120-2424 V5 A120 W115 or 230 V AC, selectable84 percent
DRP-240-2424 V10 A240 W85 to 264 V AC84 percent
DRDN20-2424 V redundancy module2 x 10 A in, 20 A outmoduletwo DC inputsnot applicable

Sizing the 24 V Rail

The table is a starting point for a load list, not a rule. The usual mistake is to add the steady currents and forget the inrush of the contactors and the lamps.

LoadTypical currentSizing note
Industrial relay, 24 V coil20 to 40 mA eachadd all coils, they are energised together
Contactor, 24 V coil0.3 to 1 A, inrush 3 to 5 timesinrush decides the supply size
LED indicator lamp10 to 20 mAsmall, but count every lamp on the door
Proximity sensor, 3 wire10 to 20 mAcount the sensors that stay on
Solenoid valve, 24 V0.5 to 1.5 Aoften switched, check the recovery time
Panel PC or HMI1 to 3 Ahas its own inrush, check the hold up time

Key Features

120 to 960 W in one range – a small panel and a drive cabinet are covered without changing supplier or mounting style.

12, 24 and 48 V outputs – indication, control and telecom rails from the same family, so the spare part is the same shape.

Universal AC input – 90 to 264 V AC on the single phase types, so the same unit works on a 110 V site and a 230 V site.

TS35 mounting – the clip on the back fits the same rail as the terminals and the breakers, so the supply is not a separate plate.

Output adjustment – the 24 V types trim from about 24 to 28 V, which allows the drop on a long rail to be compensated.

Redundancy module – two supplies can feed one 24 V rail through a module, so a single failure does not drop the load.

Applications

The rail is chosen by the load and by the failure mode, not by the cabinet size. Three cases.

Control panels with relays and sensors – a 24 V 5 A or 10 A supply, with the inrush of the contactors counted before the current is fixed.

Telecom and PoE cabinets – a 48 V supply, or a 24 V supply with a redundancy module where the link must not drop.

Test racks and burn-in benches – a supply with output adjustment and a clear derating curve, because the ambient inside a rack is higher than the room.

Power supplies, pockets and cabinet hardware are quoted for the same panel, and both the SUPERB PCBA and the SUPERB PCB are checked against the load list so the 24 V rail is sized for the relays, the lamps and the sensors that are actually fitted.

Sourcing and Cross-Reference

Read the derating curve at the real cabinet temperature. A 24 V 5 A unit is 5 A at 25 C in free air; at 55 C inside a closed cabinet it is less, and the figure is on the maker curve, not in the headline.

Add the inrush, not just the steady load. A row of contactors can pull three to five times the coil current for 50 ms. A supply that is sized on the steady current will trip into constant current at switch-on and look like a failure.

Keep 20 mm below and 40 mm above the unit. The maker installation clearance is part of the rating, and a supply mounted tight against a wire duct runs hotter than the curve assumes. See power management cross reference when an older supply is no longer available.

Use a redundancy module where the rail must stay up. Two supplies on one rail without a module back feed into each other, and the failed unit drags the good one down.

The SUPERB Assembly team derates the supply for the cabinet temperature before the rail is wired, because a 24 V unit rated at 5 A in free air delivers less inside a closed cabinet at 55 C.

Q: Can you supply a 24 V supply and a redundancy module as a pair for a panel that must not drop?

A: Yes. Send the 24 V load list with the inrush of the relays and the ambient inside the cabinet; the SUPERB Tech team quotes a supply with the headroom and the redundancy module that the load needs.

Why Builders Buy DIN Rail Power Supplies From SUPERB

  1. Output, current and input in the quote: the three figures that decide the part are listed per model, so a replacement is not chosen on wattage alone.
  2. Derating checked against the cabinet: the supply is sized at the temperature inside the cabinet, not at the test bench figure.
  3. Single and 3-phase options: the same range covers a 230 V panel and a 3-phase drive cabinet.
  4. Redundancy modules in the same family: a rail that must not drop is quoted with the module, not left to a site modification.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Steel and Aluminium DIN Rails, DIN Rail Terminal Blocks, Surge Protective Devices, Power Distribution Blocks.