Earth Fault Relays for Resistance Grounded Systems

A resistance grounded system limits earth fault current, so the relay has to work with a few amps instead of a few thousand. Trip levels run from 0.5 to 4 A on the compact relays, and 2 to 100 percent of the CT primary on the monitoring types. Trip time is adjustable from 0.1 to 10 seconds, with harmonic filtering so a drive does not trip the feeder. The same unit watches the neutral grounding resistor, because an open resistor leaves the protection blind.
quote now

Product Specifications

Product Overview

Resistance grounding turns a bolted earth fault into a small current, and that is the point: cable damage and arc flash energy fall with the current. The price is that the protection has to resolve a few amps reliably, on a network full of drive harmonics and capacitive charging current. A relay set from a generic earth fault table either trips on the charging current of a long feeder or waits for the fault to grow, and both outcomes are found out during a real fault.

The second job is watching the resistor itself. An open neutral grounding resistor removes the current path, so a current sensing relay sees nothing during a genuine earth fault and reports a healthy system. A monitor that measures neutral current, neutral to ground voltage and the resistance between them can tell the difference between no fault and no resistor, which is the failure mode that inspections now ask about.

The third decision is the interface. A relay with a front display and two output contacts is enough where someone walks past the panel. A relay with Modbus TCP, EtherNet/IP or IEC 61850 is what a plant asks for when the same event has to appear in the control room. The pulsing output is a fourth option: it switches the resistor in and out so the fault current appears only upstream of the fault, which turns a feeder by feeder search into a walk along the busbar.

Key Specifications

ParameterValueNote
Functionearth fault relay with neutral grounding resistor monitoringresistance grounded low and medium voltage systems
Earth fault trip level, compact relays0.5, 2.0 or 4.0 Aswitch selectable, matched to a 5, 15 or 25 A resistor
Earth fault trip level, monitoring relays2 to 100 percent of CT primaryset in 1 percent steps on the SE-330
Trip time0.1 to 2.0 s on compact relays, 0.1 to 10 s on the monitortime graded against downstream devices
Neutral voltage sensing20 to 2000 V on systems to 5 kV, 100 to 10000 V aboveSE-330 range, set at commissioning
Resistor monitoringneutral current, neutral to ground voltage and resistancedetects an open or a shorted resistor with or without a fault
Output contacts1 Form A on the compact relay, 2 Form A and 2 Form C on the monitorselectable fail safe or non fail safe
Analog output4 to 20 mA, self or loop poweredfeeds a meter or a control system
Pulsing output1.0 to 3.0 s in 0.2 s stepsSE-330 only, drives a pulsing contactor in the resistor circuit
Network optionsModbus TCP, EtherNet/IP, IEC 61850 or DeviceNetdual RJ45, fibre or mixed interface per option
Harmonic filteringdiscrete Fourier transform filter as standardstops false trips from drive harmonics
Event record100 events with date and timeread on the front port or over the network
Supply120 or 240 V AC, 120 V AC or DC, 65 to 265 V AC on the monitorper ordering code
Dimensions150 x 109 x 100 mm compact, 213 x 98 x 132 mm monitorpanel or surface mounting
ApprovalsCSA certified, UL listed, CEconformal coating as standard on both families
Required accessoriesCT200 series current transformer and ER sensing resistorthe compact relay will not work without both

Included Models and Order Codes

Three families cover most panels. SE-330 is the full monitor: it measures neutral current, neutral voltage and resistance, logs 100 events with date and time, and offers Modbus TCP or IEC 61850 where the plant wants the event in the control room. SE-330HV is the same unit for systems above 35 kV, up to 72 kV with matched sensing resistors, and SE-330AU is the version built for AS/NZS 2081. SE-325 is the compact monitor for systems up to 25 kV: one Form A contact, 0.5 to 4 A trip level and 0.1 to 2 s delay, and it needs the ER sensing resistor and a CT200 transformer to work. SE-105 and SE-107 combine an earth fault relay with a ground check monitor for trailing cables up to 5 kV: SE-105 lets the output work in undervoltage or shunt trip mode, and SE-107 is undervoltage only, which removes the chance that someone changes the trip circuit.

Order codeFunctionTrip levelTrip timeSupply
SE-330earth fault relay with resistor monitoring, pulsing output, event record2 to 100 percent of CT primary, 1 percent steps0.1 to 10 s65 to 265 V AC, 85 to 275 V DC
SE-330HVsame function for systems above 35 kV, up to 72 kV2 to 100 percent of CT primary0.1 to 10 sper ordering code
SE-330AUsame function built to AS/NZS 20812 to 100 percent of CT primary0.1 to 10 sper ordering code
SE-325resistor monitor for systems to 25 kV, one Form A contact0.5 to 4.0 A0.1 to 2.0 s120 V AC
SE-325Dresistor monitor, dual supply0.5 to 4.0 A0.1 to 2.0 s120 V AC or DC
SE-325Eresistor monitor, 240 V supply0.5 to 4.0 A0.1 to 2.0 s240 V AC
SE-105earth fault and ground check monitor, undervoltage or shunt trip0.5, 2.0 or 4.0 A0.1 to 2.0 s120 V AC
SE-105Dearth fault and ground check monitor, dual supply0.5, 2.0 or 4.0 A0.1 to 2.0 s120 V AC or DC
SE-105Eearth fault and ground check monitor, 240 V supply0.5, 2.0 or 4.0 A0.1 to 2.0 s240 V AC
SE-107earth fault and ground check monitor, undervoltage trip only0.5, 2.0 or 4.0 A0.1 to 2.0 s120 V AC
SE-107Dground check monitor, undervoltage only, dual supply0.5, 2.0 or 4.0 A0.1 to 2.0 s120 V AC or DC
SE-107Eground check monitor, undervoltage only, 240 V supply0.5, 2.0 or 4.0 A0.1 to 2.0 s240 V AC

Trip Setting Against Resistor Let Through Current

The trip level is not chosen from the relay alone. The rule the maker publishes is that the earth fault trip level should not exceed 20 percent of the current the grounding resistor lets through, so that a fault on one feeder is still seen by the relay on that feeder while the resistor keeps the current small. The table applies that rule to the resistor ratings that appear in most switchgear, and the third column is the CT200 primary rating that gives the setting. Where the relay is set as a percentage of CT primary, the same proportion has to be checked against the resistor, because a 200:5 transformer with a 2 percent setting trips at 4 A primary.

Resistor let through currentTrip level at 20 percentSetting on the compact relay
5 A1.0 A0.5 A setting, gives margin for charging current
10 A2.0 A2.0 A setting
15 A3.0 A2.0 A setting, 4 A is too coarse
25 A5.0 A4.0 A setting, the top of the switch range
50 A10 Arelay set as a percentage of CT primary, not by switch
100 A20 Arelay set as a percentage of CT primary, not by switch

Key Features

Resistor monitoring, not just current – the unit measures neutral current, neutral voltage and resistance together, so an open resistor is reported instead of hiding a missing earth fault.

Trip level 2 to 100 percent – the monitoring relay is set in one percent steps, which lets a long feeder keep its charging current below the setting without raising the trip level.

Harmonic filtering as standard – a discrete Fourier transform filter removes drive harmonics, which is the usual cause of nuisance earth fault trips on a plant with variable speed drives.

Pulsing output for fault location – switching the resistor in and out makes the fault current appear only upstream of the fault, so the search walks the busbar instead of opening every feeder.

Event record with date and time – 100 events are held in the relay and can be read on the front port or over the network, which is what an inspection asks for after a trip.

Network options on the same unit – Modbus TCP, EtherNet/IP, IEC 61850 and DeviceNet are options on the same relay body, so the control room interface is a code choice, not a different device.

Undervoltage trip mode – the output relay is energised while the circuit is healthy, so a lost supply or a broken coil also trips, which is the fail safe behaviour the standards expect.

Ground check for trailing cables – the SE-105 and SE-107 families watch the ground conductor of a trailing cable as well as the fault current, which is the requirement for portable equipment up to 5 kV.

Applications

Three plant arrangements where the relay choice follows from the resistor and the cable, not from a preference.

Low resistance grounded plant distribution – a 400 A resistor holds the fault current low enough for cable damage to stay repairable, and the monitor reports the resistor condition so the protection is never blind.

High resistance grounded control networks – a 5 to 10 A resistor keeps the system running through a single earth fault, and the relay has to resolve 0.5 to 2 A without tripping on charging current.

Trailing cables on mobile equipment – the ground check loop is monitored with the fault current, so a broken earth conductor is detected before the equipment is re energised.

The relay sits on a panel that is often assembled as a package, so the SUPERB PCBA and the SUPERB PCB are checked against the same terminal list and the CT wiring is reviewed once for both.

Sourcing and Cross-Reference

The first question on a replacement is the resistor rating, because the trip level follows from it. A relay set for a 25 A resistor trips at 4 A, and putting it on a 5 A resistor means the whole network trips on charging current. The second question is the sensing resistor and current transformer: a compact monitor without the ER resistor and a CT200 has no input at all, and those two items are often left off a replacement order.

The third question is the supply. The compact family comes in 120 V AC, 120 V AC or DC, and 240 V AC versions, and the monitor takes a wide range supply. A panel with a 240 V control bus and a 120 V relay ends up with a separate transformer that nobody planned for.

Where the original relay is out of production, the usual route is a monitor with the same sensing accessories and a wider setting range, since the CT and resistor stay in the switchgear. See obsolete part cross reference for a specific model, and BOM shortage recovery where a switchgear upgrade is waiting on one relay.

The SUPERB Assembly team keeps the CT secondary earthed at one point and torques the sensing resistor terminals to the maker figure, because a loose neutral connection reads as a resistor fault.

Q: Can you confirm the resistor let through current and the CT ratio so the trip level we quote matches the switchgear, and does the relay come with the sensing resistor and current transformer?

A: Yes. Send the resistor let through current, the system voltage, the CT ratio, the control supply and the protocol the plant uses, and the SUPERB Tech team returns the relay with its sensing accessories.

Why Switchgear Builders Source Earth Fault Relays Through SUPERB

  1. Setting range matched to the resistor: the trip level and the resistor rating are quoted together, so a 5 A network is not given a relay that starts at 4 A.
  2. Accessories named: the CT200 transformer and the ER sensing resistor are listed with the relay, because a monitor without them cannot see the neutral circuit.
  3. Fail safe behaviour stated: undervoltage trip mode and latching or auto reset are described per code, which is what an inspector asks about after a trip.
  4. Interface chosen at order: network options sit on the same relay body, so the control room protocol does not force a different protection family.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Neutral Grounding Resistors for Resistance Grounded Systems, Insulation Fault Locators for IT Systems, Protection Current Transformers for Overcurrent Relays, Voltage Transformers for Panel Metering and Protection, CT Test Terminal Blocks and Shorting Links, Obsolete Part Cross Reference Hub.