Earth Fault Relays for Resistance Grounded Systems
Product Specifications
Product Overview
Resistance grounding turns a bolted earth fault into a small current, and that is the point: cable damage and arc flash energy fall with the current. The price is that the protection has to resolve a few amps reliably, on a network full of drive harmonics and capacitive charging current. A relay set from a generic earth fault table either trips on the charging current of a long feeder or waits for the fault to grow, and both outcomes are found out during a real fault.
The second job is watching the resistor itself. An open neutral grounding resistor removes the current path, so a current sensing relay sees nothing during a genuine earth fault and reports a healthy system. A monitor that measures neutral current, neutral to ground voltage and the resistance between them can tell the difference between no fault and no resistor, which is the failure mode that inspections now ask about.
The third decision is the interface. A relay with a front display and two output contacts is enough where someone walks past the panel. A relay with Modbus TCP, EtherNet/IP or IEC 61850 is what a plant asks for when the same event has to appear in the control room. The pulsing output is a fourth option: it switches the resistor in and out so the fault current appears only upstream of the fault, which turns a feeder by feeder search into a walk along the busbar.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Function | earth fault relay with neutral grounding resistor monitoring | resistance grounded low and medium voltage systems |
| Earth fault trip level, compact relays | 0.5, 2.0 or 4.0 A | switch selectable, matched to a 5, 15 or 25 A resistor |
| Earth fault trip level, monitoring relays | 2 to 100 percent of CT primary | set in 1 percent steps on the SE-330 |
| Trip time | 0.1 to 2.0 s on compact relays, 0.1 to 10 s on the monitor | time graded against downstream devices |
| Neutral voltage sensing | 20 to 2000 V on systems to 5 kV, 100 to 10000 V above | SE-330 range, set at commissioning |
| Resistor monitoring | neutral current, neutral to ground voltage and resistance | detects an open or a shorted resistor with or without a fault |
| Output contacts | 1 Form A on the compact relay, 2 Form A and 2 Form C on the monitor | selectable fail safe or non fail safe |
| Analog output | 4 to 20 mA, self or loop powered | feeds a meter or a control system |
| Pulsing output | 1.0 to 3.0 s in 0.2 s steps | SE-330 only, drives a pulsing contactor in the resistor circuit |
| Network options | Modbus TCP, EtherNet/IP, IEC 61850 or DeviceNet | dual RJ45, fibre or mixed interface per option |
| Harmonic filtering | discrete Fourier transform filter as standard | stops false trips from drive harmonics |
| Event record | 100 events with date and time | read on the front port or over the network |
| Supply | 120 or 240 V AC, 120 V AC or DC, 65 to 265 V AC on the monitor | per ordering code |
| Dimensions | 150 x 109 x 100 mm compact, 213 x 98 x 132 mm monitor | panel or surface mounting |
| Approvals | CSA certified, UL listed, CE | conformal coating as standard on both families |
| Required accessories | CT200 series current transformer and ER sensing resistor | the compact relay will not work without both |
Included Models and Order Codes
Three families cover most panels. SE-330 is the full monitor: it measures neutral current, neutral voltage and resistance, logs 100 events with date and time, and offers Modbus TCP or IEC 61850 where the plant wants the event in the control room. SE-330HV is the same unit for systems above 35 kV, up to 72 kV with matched sensing resistors, and SE-330AU is the version built for AS/NZS 2081. SE-325 is the compact monitor for systems up to 25 kV: one Form A contact, 0.5 to 4 A trip level and 0.1 to 2 s delay, and it needs the ER sensing resistor and a CT200 transformer to work. SE-105 and SE-107 combine an earth fault relay with a ground check monitor for trailing cables up to 5 kV: SE-105 lets the output work in undervoltage or shunt trip mode, and SE-107 is undervoltage only, which removes the chance that someone changes the trip circuit.
| Order code | Function | Trip level | Trip time | Supply |
|---|---|---|---|---|
| SE-330 | earth fault relay with resistor monitoring, pulsing output, event record | 2 to 100 percent of CT primary, 1 percent steps | 0.1 to 10 s | 65 to 265 V AC, 85 to 275 V DC |
| SE-330HV | same function for systems above 35 kV, up to 72 kV | 2 to 100 percent of CT primary | 0.1 to 10 s | per ordering code |
| SE-330AU | same function built to AS/NZS 2081 | 2 to 100 percent of CT primary | 0.1 to 10 s | per ordering code |
| SE-325 | resistor monitor for systems to 25 kV, one Form A contact | 0.5 to 4.0 A | 0.1 to 2.0 s | 120 V AC |
| SE-325D | resistor monitor, dual supply | 0.5 to 4.0 A | 0.1 to 2.0 s | 120 V AC or DC |
| SE-325E | resistor monitor, 240 V supply | 0.5 to 4.0 A | 0.1 to 2.0 s | 240 V AC |
| SE-105 | earth fault and ground check monitor, undervoltage or shunt trip | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 120 V AC |
| SE-105D | earth fault and ground check monitor, dual supply | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 120 V AC or DC |
| SE-105E | earth fault and ground check monitor, 240 V supply | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 240 V AC |
| SE-107 | earth fault and ground check monitor, undervoltage trip only | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 120 V AC |
| SE-107D | ground check monitor, undervoltage only, dual supply | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 120 V AC or DC |
| SE-107E | ground check monitor, undervoltage only, 240 V supply | 0.5, 2.0 or 4.0 A | 0.1 to 2.0 s | 240 V AC |
Trip Setting Against Resistor Let Through Current
The trip level is not chosen from the relay alone. The rule the maker publishes is that the earth fault trip level should not exceed 20 percent of the current the grounding resistor lets through, so that a fault on one feeder is still seen by the relay on that feeder while the resistor keeps the current small. The table applies that rule to the resistor ratings that appear in most switchgear, and the third column is the CT200 primary rating that gives the setting. Where the relay is set as a percentage of CT primary, the same proportion has to be checked against the resistor, because a 200:5 transformer with a 2 percent setting trips at 4 A primary.
| Resistor let through current | Trip level at 20 percent | Setting on the compact relay |
|---|---|---|
| 5 A | 1.0 A | 0.5 A setting, gives margin for charging current |
| 10 A | 2.0 A | 2.0 A setting |
| 15 A | 3.0 A | 2.0 A setting, 4 A is too coarse |
| 25 A | 5.0 A | 4.0 A setting, the top of the switch range |
| 50 A | 10 A | relay set as a percentage of CT primary, not by switch |
| 100 A | 20 A | relay set as a percentage of CT primary, not by switch |
Key Features
Resistor monitoring, not just current – the unit measures neutral current, neutral voltage and resistance together, so an open resistor is reported instead of hiding a missing earth fault.
Trip level 2 to 100 percent – the monitoring relay is set in one percent steps, which lets a long feeder keep its charging current below the setting without raising the trip level.
Harmonic filtering as standard – a discrete Fourier transform filter removes drive harmonics, which is the usual cause of nuisance earth fault trips on a plant with variable speed drives.
Pulsing output for fault location – switching the resistor in and out makes the fault current appear only upstream of the fault, so the search walks the busbar instead of opening every feeder.
Event record with date and time – 100 events are held in the relay and can be read on the front port or over the network, which is what an inspection asks for after a trip.
Network options on the same unit – Modbus TCP, EtherNet/IP, IEC 61850 and DeviceNet are options on the same relay body, so the control room interface is a code choice, not a different device.
Undervoltage trip mode – the output relay is energised while the circuit is healthy, so a lost supply or a broken coil also trips, which is the fail safe behaviour the standards expect.
Ground check for trailing cables – the SE-105 and SE-107 families watch the ground conductor of a trailing cable as well as the fault current, which is the requirement for portable equipment up to 5 kV.
Applications
Three plant arrangements where the relay choice follows from the resistor and the cable, not from a preference.
Low resistance grounded plant distribution – a 400 A resistor holds the fault current low enough for cable damage to stay repairable, and the monitor reports the resistor condition so the protection is never blind.
High resistance grounded control networks – a 5 to 10 A resistor keeps the system running through a single earth fault, and the relay has to resolve 0.5 to 2 A without tripping on charging current.
Trailing cables on mobile equipment – the ground check loop is monitored with the fault current, so a broken earth conductor is detected before the equipment is re energised.
The relay sits on a panel that is often assembled as a package, so the SUPERB PCBA and the SUPERB PCB are checked against the same terminal list and the CT wiring is reviewed once for both.
Sourcing and Cross-Reference
The first question on a replacement is the resistor rating, because the trip level follows from it. A relay set for a 25 A resistor trips at 4 A, and putting it on a 5 A resistor means the whole network trips on charging current. The second question is the sensing resistor and current transformer: a compact monitor without the ER resistor and a CT200 has no input at all, and those two items are often left off a replacement order.
The third question is the supply. The compact family comes in 120 V AC, 120 V AC or DC, and 240 V AC versions, and the monitor takes a wide range supply. A panel with a 240 V control bus and a 120 V relay ends up with a separate transformer that nobody planned for.
Where the original relay is out of production, the usual route is a monitor with the same sensing accessories and a wider setting range, since the CT and resistor stay in the switchgear. See obsolete part cross reference for a specific model, and BOM shortage recovery where a switchgear upgrade is waiting on one relay.
The SUPERB Assembly team keeps the CT secondary earthed at one point and torques the sensing resistor terminals to the maker figure, because a loose neutral connection reads as a resistor fault.
Q: Can you confirm the resistor let through current and the CT ratio so the trip level we quote matches the switchgear, and does the relay come with the sensing resistor and current transformer?
A: Yes. Send the resistor let through current, the system voltage, the CT ratio, the control supply and the protocol the plant uses, and the SUPERB Tech team returns the relay with its sensing accessories.
Why Switchgear Builders Source Earth Fault Relays Through SUPERB
- Setting range matched to the resistor: the trip level and the resistor rating are quoted together, so a 5 A network is not given a relay that starts at 4 A.
- Accessories named: the CT200 transformer and the ER sensing resistor are listed with the relay, because a monitor without them cannot see the neutral circuit.
- Fail safe behaviour stated: undervoltage trip mode and latching or auto reset are described per code, which is what an inspector asks about after a trip.
- Interface chosen at order: network options sit on the same relay body, so the control room protocol does not force a different protection family.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Neutral Grounding Resistors for Resistance Grounded Systems, Insulation Fault Locators for IT Systems, Protection Current Transformers for Overcurrent Relays, Voltage Transformers for Panel Metering and Protection, CT Test Terminal Blocks and Shorting Links, Obsolete Part Cross Reference Hub.