Neutral Grounding Resistors for Resistance Grounded Systems

A neutral grounding resistor limits the current that flows when one phase touches earth, so the fault is detected without destroying the transformer. The range covers 240 V to 72 kV systems, with current ratings up to 5000 A and duty from ten seconds to continuous. Time rating and temperature rise are the two numbers that size the resistor, and both come from IEEE 32. High resistance grounding on a 600 V system holds the fault current under 25 A and lets the plant run until the fault is located.
quote now

Product Specifications

Product Overview

An ungrounded system looks safe until one phase touches earth. The fault current is then only the capacitance charging current, which is small, but the two healthy phases rise to line to line voltage and stay there. A second fault on another phase turns into a line to line fault through the first one. A neutral grounding resistor fixes the first problem by giving the fault a defined path and a defined current, and it fixes the second by making the first fault detectable before the second one happens.

The resistor is rated on three numbers: the line to neutral voltage it sees during a fault, the current that flows at that voltage, and the time it has to carry that current. A 2400 V line to neutral system with a 200 A resistor holds the fault at 480 kW for the duty time, and the element has to survive that power without changing value. The time rating is where the cost sits: a ten second resistor is a small resistor, and a continuous one is a much larger element in a much larger enclosure.

The two families in practice are low resistance and high resistance. Low resistance grounding is usual above 600 V, limits the fault to 50 A or more so that a relay can trip a breaker within seconds, and requires the circuit to be shut down after the fault. High resistance grounding is usual at 600 V and below, limits the fault under 25 A, and allows the plant to keep running while the fault is found. The rule of thumb for the charging current is 0.5 A per 1000 kVA on systems at or below 600 V, and 1 A per 1000 kVA above that.

Key Specifications

ParameterValueNote
System voltage240 V to 72 kV line to lineCSA approved types up to 7200 V
Resistor voltage ratingline to neutral voltage of the system4160 V system, 2400 V across the resistor
Current ratingup to 5000 Alow resistance types from 50 A, high resistance types below 25 A
Time ratings10 s, 1 min, 10 min, extended time, continuousIEEE 32 duty classes, each with its own temperature rise
Permissible temperature rise760 C at 10 s and 1 min, 610 C at 10 min and extended, 385 C continuousabove 30 C ambient, CSA 375 C on continuous
Resistance toleranceplus or minus 10 percentchecked at the works test
Elementstainless steel or nickel chromium, low temperature coefficientrigidly supported at both ends for expansion
Insulationframe on insulators rated for the system voltagerequired above 10 A continuous on low voltage
Applied potential testtwice rated voltage plus 1000 V at 600 V and below2.25 times rated plus 2000 V above 600 V
Enclosureventilated steel, NEMA 3R or IP23 outdoorindoor cover screened to 1/2 inch openings
Hardwarestainless steel throughouthot dip galvanised or aluminium options
Optionscurrent transformer, voltage transformer, disconnect switch, grounding transformer, heaterpackaged inside the resistor cubicle
StandardsIEEE 32, IEEE C57.32, CSAcertified test reports with each unit
Charging current guide0.5 A per 1000 kVA at 600 V and below, 1 A per 1000 kVA abovesizing rule of thumb, verify by measurement

Included Models and Order Codes

The table below is the standard low resistance family that is certified for seismic zones, and it is quoted by line to neutral voltage, current and duty rather than by a catalogue number. Each row carries the same 10 second duty and the same 48 x 48 x 48 inch footprint, and the weight grows with the voltage and the current because the element and the insulation grow. A 2400 V 100 A unit weighs 675 lb, and an 8000 V 400 A unit weighs 1000 lb. Where a project needs a different current or duty, the resistor is built to the rating rather than selected from a table, and the enclosure size follows.

Voltage line to neutralInitial currentDutyEnclosure and weight
2400 V100 A10 s48 x 48 x 48 in, 675 lb
2400 V200 A10 s48 x 48 x 48 in, 675 lb
2400 V400 A10 s48 x 48 x 48 in, 700 lb
4160 V100 A10 s48 x 48 x 48 in, 825 lb
4160 V200 A10 s48 x 48 x 48 in, 825 lb
4160 V400 A10 s48 x 48 x 48 in, 850 lb
7200 V100 A10 s48 x 48 x 48 in, 975 lb
7200 V200 A10 s48 x 48 x 48 in, 975 lb
7200 V400 A10 s48 x 48 x 48 in, 1000 lb
8000 V100 A10 s48 x 48 x 48 in, 975 lb
8000 V200 A10 s48 x 48 x 48 in, 975 lb
8000 V400 A10 s48 x 48 x 48 in, 1000 lb

Resistance and Power for a Given Voltage and Current

The resistance follows from the line to neutral voltage divided by the current, and the power the element has to carry during the fault is the product of the two. The table gives both for the four standard voltages. A 4160 V line to neutral resistor at 400 A is 10.4 ohm and 1664 kW, which is why the element is large and why the duty time is written on the nameplate rather than assumed.

Voltage line to neutral100 A200 A400 A
2400 V24 ohm, 240 kW12 ohm, 480 kW6 ohm, 960 kW
4160 V41.6 ohm, 416 kW20.8 ohm, 832 kW10.4 ohm, 1664 kW
7200 V72 ohm, 720 kW36 ohm, 1440 kW18 ohm, 2880 kW
8000 V80 ohm, 800 kW40 ohm, 1600 kW20 ohm, 3200 kW

Key Features

Duty time written on the nameplate – 10 s, 1 min, 10 min and continuous ratings carry different temperature rises, and the time is what sets the element size.

IEEE 32 test regime – applied potential and resistance tolerance tests are named, so a project specification that quotes IEEE 32 can be met without a second standard.

Low and high resistance – the two families are described with their current windows, because a 5 A high resistance unit and a 400 A low resistance unit serve different purposes.

Charging current guide – 0.5 A per 1000 kVA at 600 V and below gives a starting point for the current, and the measurement confirms it before the order.

Stainless steel element – a low temperature coefficient element keeps the resistance inside tolerance as it heats through the duty time.

Packaged options – current transformer, disconnect switch and grounding transformer can sit in the same cubicle, which saves a separate panel on a retrofit.

Seismic certification – the standard family is certified for seismic zones, which is a requirement on many industrial and utility sites and is not visible on a generic data sheet.

Applications

Three systems where the grounding resistor is what makes the protection scheme work.

Industrial plants at 2.4 to 13.8 kV – low resistance grounding limits the fault to a level a relay can clear in seconds, and the resistor is sized on the feeder with the highest fault level.

Low voltage plants that must keep running – high resistance grounding under 25 A allows a single earth fault to be located while the process continues, which is why it is common in continuous processes.

Generator neutrals – a resistor on the generator neutral limits the current a stator fault can drive, and the duty time follows the generator protection settings.

Where the grounding scheme is monitored from a control board, the SUPERB PCBA and the SUPERB PCB are reviewed against the same relay settings, so the resistor rating and the trip level agree.

Sourcing and Cross-Reference

A grounding resistor is built to a rating rather than picked from a shelf, so the order starts with four numbers: line to neutral voltage, fault current, duty time and enclosure position. The duty time is the one that is most often left off the enquiry, and it is the one that changes the price most, because a continuous resistor is several times the element of a ten second unit.

The second question is the protection that sees the fault. A low resistance system needs a relay set to a fraction of the resistor current, usually 5 to 20 percent, and a high resistance system needs a sensitive relay because the current is small. The third question is the environment: an outdoor enclosure needs the NEMA 3R top and the screened bottom, and a coastal site needs the stainless hardware option.

For a project waiting on one unit, the options are a standard rating close to the calculated one with the difference accepted in the protection setting, a build to the exact rating with a longer lead time, or a packaged unit with the transformer and the switch in the same cubicle. See lead time and availability for a specific rating.

The SUPERB Assembly team lands the neutral and ground conductors in separate terminal boxes, because a resistor cubicle with the two mixed is a fault path that bypasses the element.

Q: Can you confirm the duty time and the enclosure our grounding resistor needs before we release a specification?

A: Yes. Send the system voltage, the fault current, the duty time and the enclosure position, and the SUPERB Tech team returns the resistance and the frame that meet the rating.

Why Projects Source Grounding Resistors Through SUPERB

  1. Duty time and temperature rise paired: each IEEE 32 duty class is quoted with its permissible rise, so a ten second rating is not compared with a continuous one on current alone.
  2. Resistance and power calculated: the table converts voltage and current into ohms and kilowatts, which is what the element and the enclosure are actually built around.
  3. Standards named: IEEE 32, C57.32 and CSA are on the page, so a specification that calls for them can be answered without a second round of questions.
  4. Packaged options listed: current transformer, disconnect switch and grounding transformer are offered in the same cubicle, which shortens a retrofit and keeps the wiring in one place.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Residual Current Devices for Panel Feeders, Surge Protective Devices for AC Distribution Boards, Insulation Monitoring Devices for Unearthed Systems, Metering Current Transformers for Panel and Switchgear, Busbars and Earth Bars for Panel Power Distribution, Component Lead Time Solutions.