Insulation Fault Locators for IT Systems
Product Specifications
Product Overview
In an unearthed system, an IT system, the first insulation fault does not trip a breaker. That is the point of the arrangement: a single fault to earth is an alarm, and the plant keeps running until the fault is found. The weakness is the finding. An insulation monitoring device reports that the insulation resistance has fallen somewhere in the system, and on a panel with forty outgoing circuits that statement is not enough to send an electrician to the right door. An insulation fault locator closes that gap by putting a measuring current transformer on every outgoing circuit and reporting which one carries the fault.
The method is a locating current. The insulation monitor, or a separate locating current injector, applies a limited pulse between the system and earth. That pulse flows through the insulation fault and back through the earth conductor, so it appears only in the faulted outgoing circuit. The measuring current transformers on each circuit see the pulse, and the locator compares the channels and reports the one that carries it. Because the pulse is a defined signal rather than the uncontrolled leakage current of a first fault, the result is a channel number and not an estimate. Scanning all twelve channels takes at least six seconds, which is the price of a clean answer.
Sensitivity separates the two versions. EDS440 responds from 2 to 10 mA and is built for main circuits, where the leakage capacitance of a long cable run is large and a small signal would be lost in it. EDS441 responds from 0.2 to 1 mA and is built for control circuits and for medical locations, where a small leakage is the whole concern and the circuits are short. Choosing the 0.2 mA version for a main feeder is a mistake in the other direction: the higher sensitivity meets more capacitance and produces nuisance alarms. The version follows the circuit, not the panel.
The system scales by bus, not by panel rebuild. Up to twelve transformers connect to one locator, up to fifty locators connect on one RS-485 bus, and the total is 600 outgoing circuits. Addresses run from 2 to 79 and the protocol is Modbus RTU, so the channel states reach a PLC or a building management system without a separate gateway. Each locator also carries two alarm relays with one normally open contact each, which is enough to repeat a common alarm to a annunciator or a horn. A twelve way relay module adds one contact per channel where the panel needs individual indications.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Measuring channels | 12 per locator | measuring current transformers, CTAC or WR series |
| Locators per system | up to 50 | 600 measuring channels in total |
| Response sensitivity, EDS440 | 2 to 10 mA | main circuits |
| Response sensitivity, EDS441 | 0.2 to 1 mA | control circuits and medical locations |
| Measuring range, locating current | 1.5 to 50 mA on EDS440 | 0.15 to 5 mA on EDS441 |
| System voltage with injector | AC 42 to 1000 V, DC 24 to 1500 V | depends on the locating current injector |
| Residual current measurement | 0.1 to 20 A on EDS440 | 0.1 to 2 A on EDS441 |
| Response time, residual current | 400 ms or less | scan of all channels at least 6 s |
| Supply voltage | DC 24 V on the S versions | AC or DC 24 to 240 V on the L versions |
| Alarm relays | 2, one normally open contact each | 12 way relay module as an option |
| Interface | RS-485, BS bus, Modbus RTU | address range 2 to 79 |
| Housing | 72 x 93 x 63 mm, DIN rail | polycarbonate, UL 94 V-0 |
| Protection | IP40 internal, IP20 terminals | inside an enclosure |
| Weight | 122 g on S versions | 242 g on L versions |
| Ambient temperature | -40 to +70 C | continuous operation |
| Standards | IEC 61557-9, EN 50155, EN 45545-2 | rail and fire performance included |
Included Models and Order Codes
The ordering code carries the version. The letter S marks a unit supplied from DC 24 V and connected only through the BB bus, which is the economical choice inside a new panel where the bus supply is already there. The letter L marks a unit with a wide AC or DC 24 to 240 V supply, a channel LED display and an RS-485 connection to the insulation monitor, which is the choice for a retrofit where a 24 V rail is not available. The suffix 4 marks the twelve channel version, and the suffix W adds a varnish coating for shock, vibration and moisture. EDS441 covers the sensitive end, and EDS441-LAB-4 is the variant for control circuits with the CTBC series transformers.
| Type | Article number | Supply | Response value | Use |
|---|---|---|---|---|
| Bender EDS440-S-1 | B91080201 | DC 24 V | 2 to 10 mA | main circuits, BB bus supply |
| Bender EDS440W-S-1 | B91080201W | DC 24 V | 2 to 10 mA | main circuits, coated for vibration |
| Bender EDS440-L-4 | B91080202 | AC or DC 24 to 240 V | 2 to 10 mA | main circuits, channel display |
| Bender EDS440-LAF-4 | B91080209 | AC or DC 24 to 240 V | 10 mA | main circuits with CTAF flexible transformers |
| Bender EDS441-S-1 | B91080204 | DC 24 V | 0.2 to 1 mA | control circuits, BB bus supply |
| Bender EDS441-L-4 | B91080205 | AC or DC 24 to 240 V | 0.2 to 1 mA | control circuits and medical locations |
| Bender EDS441-LAB-4 | B91080207 | AC or DC 24 to 240 V | 0.2 to 1 mA | control circuits with CTBC transformers |
| Bender IOM441-S | B95012057 | from the bus | 12 relay outputs | one contact per channel |
Measuring Current Transformers for the Locator
The transformer is part of the measurement, not an accessory. A standard protection or metering transformer is not suitable, because the locator reads a pulse in the milliamp range and needs the winding and the burden that belong to that range. The CTAC series is the circular type for a cable or a small bar, CTAS is the split core type for a cable that cannot be disconnected, and CTAF is the flexible type for a large bar or a bundle. All live conductors of the circuit pass through the transformer, and no earth conductor or cable shield passes through it, because the return path must not be cancelled inside the loop.
| Type | Article number | Internal size | Form | Used with |
|---|---|---|---|---|
| Bender CTAC20 | B98110005 | 20 mm | circular | EDS440 |
| Bender CTAC35 | B98110007 | 35 mm | circular | EDS440 |
| Bender CTAC60 | B98110017 | 60 mm | circular | EDS440 |
| Bender CTAC120 | B98110019 | 120 mm | circular | EDS440 |
| Bender CTAC210 | B98110020 | 210 mm | circular | EDS440 |
| Bender CTAS50 | B98110009 | 50 mm | split core | EDS440 |
| Bender CTAS80 | B98110010 | 80 mm | split core | EDS440 |
| Bender CTAS120 | B98110011 | 120 mm | split core | EDS440 |
| Bender CTAF500SET | B98110022 | 500 mm | flexible | EDS440-LAF-4 |
| Bender CTAF1000SET | B98110023 | 1000 mm | flexible | EDS440-LAF-4 |
| Bender CTAC20/01 | B98110006 | 20 mm | circular | EDS441 |
| Bender CTAC35/01 | B98110008 | 35 mm | circular | EDS441 |
Key Features
Twelve channels per unit – one locator covers a twelve way distribution board, and the next board is a second unit on the same bus, not a second system.
Two sensitivity classes – 2 to 10 mA for main circuits and 0.2 to 1 mA for control circuits, so the version follows the leakage capacitance of the circuit.
600 circuits per system – fifty locators on one RS-485 bus give a plant wide location system without a second network.
Modbus RTU – channel states and alarms are readable from a PLC or a building management system over the same bus.
Two alarm relays – a common alarm reaches an annunciator or a horn without extra wiring, and the relay module adds one contact per channel.
Channel display on the L versions – the front panel shows which channel carries the fault, so the electrician reads the door and not a laptop.
DIN rail housing – 72 mm wide and 63 mm deep, which fits a standard enclosure beside the monitoring device.
Coated W version – the varnished board suits a machine that vibrates or a cabinet that condenses, which is the rail and marine case.
Applications
Three systems where knowing the circuit matters as much as knowing that a fault exists.
Medical locations – an operating theatre or an intensive care unit on an IT system, where a first fault must be alarmed and located before it becomes a second fault and a trip.
Marine and rail auxiliaries – a 24 V or 230 V unearthed auxiliary system on a vessel or a train, where a fault has to be found at the next port or the next depot, not at sea.
Industrial control circuits – a machine with a separate control transformer, where a 0.2 mA locator finds a wet terminal block that a 2 mA unit would miss.
Diode decoupled DC systems – a power plant DC system fed through decoupling diodes, where the locator separates the battery side from the charger side.
Where the locator shares an enclosure with control boards, the SUPERB PCBA and the SUPERB PCB are reviewed against the same channel list and the same bus address, so the alarm that reaches the panel matches the circuit that is faulted.
Sourcing and Cross-Reference
A locator is chosen from four facts: the number of outgoing circuits, the leakage capacitance of those circuits, the supply available in the panel, and whether the insulation monitor already injects a locating current. The first sets the number of channels and units, the second sets EDS440 or EDS441, the third sets the S or L version, and the fourth decides whether a separate injector is needed. A locator bought without the injector is a set of ears with nothing to listen to, and the monitor model has to be checked for the locating function before the locator is ordered.
The transformers are the second half of the order and the part most often left out. Each channel needs its own transformer, sized to the cable or bar, and the split core type is the answer where the cable cannot be disconnected. The cable from transformer to locator is limited by its type: a single wire up to 1 m, a twisted pair up to 10 m, and a shielded cable up to 40 m. A panel with long runs to a remote board needs the shielded cable and the shield earthed at one end, or the channel will report a connection fault instead of a reading.
Where the monitor is already installed but the location function is missing, the practical route is a locator that speaks to the existing monitor over the BS bus, plus the transformers on the circuits that matter first. See lead time and availability for a specific model, or BOM shortage recovery when a panel is complete except for one module.
The SUPERB Assembly team keeps the transformer leads in channel order and marks each one, because a crossed channel sends the electrician to the wrong door on the first visit.
Q: Can we add fault location to an IT system that already has an insulation monitor, without replacing the monitor?
A: Yes. Send the monitor model, the number of outgoing circuits, the cable sizes and the panel supply, and the SUPERB Tech team returns the locator version and the transformer list that complete the system.
Why Panel Builders Source Insulation Fault Locators Through SUPERB
- Sensitivity matched to the circuit: the 2 to 10 mA and 0.2 to 1 mA versions are on the page with their applications, so a main feeder and a control circuit do not get the same unit.
- Channel count and bus limit stated: twelve channels, fifty locators and 600 circuits are the numbers a panel schedule needs, and they are given before the order.
- Transformer table included: the CTAC, CTAS and CTAF sizes are listed with article numbers, because the locator is only as good as the transformer on the cable.
- Supply and protocol listed: DC 24 V or AC and DC 24 to 240 V, RS-485 with Modbus RTU, so the panel supply and the building system are checked in one look.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Insulation Monitoring Devices for Unearthed Systems, Residual Current Devices for Panel Feeders, Metering Current Transformers for Panel and Switchgear, Current Transformers and AC Current Sensing for Energy Metering, Neutral Grounding Resistors for Resistance Grounded Systems, Component Lead Time Solutions.