CT Test Terminal Blocks and Shorting Links

A current transformer secondary must never be opened under load, so the test point has to short before it separates. Test disconnect blocks do that inside one 8.2 mm body, with a 4 mm socket on each side of the break. Rated 41 A on a 6 mm2 conductor and 57 A on 10 mm2, with 0.72 to 1.2 kA short time current. Shorting links and switching jumpers complete a three phase set without handling the CT wiring.
quote now

Product Specifications

Product Overview

Opening a live current transformer secondary produces a voltage that rises until something breaks down, and the something is usually the insulation of the winding or the person holding the wire. Every test point in a metering circuit exists to make that impossible: the circuit has to be shorted before it is separated, and it has to stay shorted while the meter or the relay is swapped. A screw terminal with a test plug pushed into it does not do that, which is why test disconnect blocks have a sliding break inside the body rather than a removable link.

The blocks in this family carry two 4 mm sockets, one on each side of the break, plus a slide that opens the circuit. The socket also accepts a bridge bar or a screw bridge, so a three phase set can be shorted and earthed in one movement. On the coupled versions the slide is arranged so the two neighbouring blocks move together, which gives the make before break action: the short is made on the incoming side before the break opens.

The mechanical detail that decides the part number is the conductor range and the current. A 6 mm2 block covers most metering circuits at 41 A. A 10 mm2 block goes to 57 A nominal and 76 A maximum load on a 16 mm2 conductor, which is what a protection circuit with a 5 A secondary needs when the relay is a distance away. Both sit on NS 35/7.5, NS 35/15 or NS 32 rail and both are 8.2 mm wide, so a mixed row is possible without changing the rail.

Key Specifications

ParameterValueNote
Typetest disconnect terminal block, screw connectionone level, two connections, one potential
Nominal voltage400 V on the URTK/S family, 500 V on the BEN familyper code
Nominal current41 A on the 6 mm2 blocks, 57 A on the 10 mm2 blocksIEC 60947-7-1 rating
Maximum load current57 A with a 10 mm2 conductor, 76 A with a 16 mm2 conductorshort time, not continuous
Conductor range0.5 to 10 mm2 (20 to 8 AWG), or 0.5 to 16 mm2 (20 to 6 AWG)rigid and flexible ranges differ per code
Width8.2 mmsame pitch for both current classes
Test socketstwo 4 mm sockets, one on each side of the breakaccepts test plugs, bridge bars and screw bridges
Short time current0.72 kA on a 6 mm2 conductor, 1.2 kA on 10 mm2tested per the maker sheet
Rated surge voltage6 kVovervoltage category III, pollution degree 3
Power dissipation1.82 W at nominal conditionon the 10 mm2 blocks
MountingNS 35/7.5, NS 35/15 and NS 32 railsame block fits all three rails
Ambient temperatureminus 60 to plus 85 Coperating range on the BEN family
FlammabilityUL 94 V0 insulating materialPA body
Tightening torque1.5 to 1.8 Nm on the terminal screw0.6 to 0.8 Nm on the disconnect slide
StandardIEC 60947-7-1connection and test data published per code

Included Models and Order Codes

The code tells you two things: whether the break has a slide on its own or a slide coupled to the neighbouring block, and whether the body takes 6 mm2 or 10 mm2. URTK/S is the plain 400 V 41 A block with two test sockets. URTK/S RD is the same block in red, which is how a three phase set is marked so the phases are not mixed. URTK/S-BEN adds the slide, and URTK/S-BEN 10 moves to the 10 mm2 body at 500 V and 57 A, with 76 A maximum load on 16 mm2. URTK/S-BEN 10-TK is the same body with the test socket arrangement used where the block sits at the end of a row. URTK/S M. ABGESCHNITTEN has cut test socket metals, which is the version used where a test plug has to reach past a crowded terminal shroud. The accessory row matters as much as the block: a three phase short is made with the KSS 4-8 shorting connector or with ASB 2-RTK/S switching jumpers, and the coloured PSBJ test connectors identify the phase at the socket.

Order codeVoltage and currentConductor rangeFeatures
URTK/S 0311087400 V, 41 A0.5 to 10 mm2grey, two 4 mm test sockets, screw connection
URTK/S RD 0311812400 V, 41 A0.5 to 10 mm2red version of 0311087, phase marking
URTK/S-BEN 0309086500 V, 41 A0.5 to 10 mm2with slide, 57 A maximum load on 10 mm2
URTK/S-BEN 10 0309109500 V, 57 A0.5 to 16 mm2with slide, 76 A maximum load on 16 mm2
URTK/S-BEN 10-TK 1272913500 V, 57 A0.5 to 16 mm2end of row version of 0309109
URTK/S M. ABGESCHNITTEN 0316082400 V, 41 A0.5 to 10 mm2slide with cut test socket metals

Shorting and Test Accessories

A block on its own only shorts one phase. The three phase operation that a metering test actually needs comes from the accessories: a shorting connector that bridges four blocks at once, a switching jumper that ties two neighbouring blocks, and coloured test connectors that mark the phase at the socket so a test lead goes to the right place. All of them are listed with the same 8 to 8.2 mm pitch as the blocks, which is why a row of mixed codes still bridges correctly.

Order codeItemPitchUse
KSS 4-8 0309549short circuit connector, 4 positions8 mmshorts four blocks in one movement
ASB 2-RTK/S 0311281switching jumper, 2 positions8.2 mmties two blocks, follows the slide
PSBJ-URTK/S YE 0311731female test connector, yellow4 mm plugphase identification at the socket
PSBJ-URTK/S GN 0311760female test connector, green4 mm plugphase identification at the socket
PSBJ-URTK/S VT 0311773female test connector, violet4 mm plugphase identification at the socket
PSBJ-URTK/S BK 0311728female test connector, black4 mm plugneutral or common marking

Key Features

Short before break – the break is a slide inside the block and the short is made on the incoming side first, which is the only order that protects a live CT secondary.

Two 4 mm sockets per block – a test plug, a bridge bar or a screw bridge all land on the same socket, so one row covers measurement, shorting and earthing.

41 A and 57 A in the same pitch – the 6 mm2 and 10 mm2 bodies are both 8.2 mm wide, so a mixed row still bridges with the same accessories.

Short time current published – 0.72 kA on 6 mm2 and 1.2 kA on 10 mm2 are stated per code, which is what a protection circuit has to be checked against.

Rigid and flexible ranges separated – the sheet gives both conductor ranges and the AWG conversion, because a flexible 10 mm2 with a ferrule takes a different sleeve.

One block for three rail types – NS 35/7.5, NS 35/15 and NS 32 all take the same body, which matters when an old panel is extended with a new row.

Colour coded range – grey, red and the coloured test connectors make the phase order visible at the block rather than on a drawing.

Cut socket variant – the cut metal version lets a test plug reach a block that sits behind a terminal shroud, without removing the shroud.

Applications

Three situations where the block is chosen by the test procedure rather than by the terminal size.

Metering panel with periodic verification – the meter is swapped with the CT shorted at the block, so the circuit stays closed while the instrument is off the panel.

Protection circuit with a 5 A secondary – the 10 mm2 body carries 57 A nominal and 76 A maximum, which covers the burden of a relay at the end of a long secondary cable.

Three phase test set – a shorting connector bridges four blocks at once and the coloured test connectors mark the phase, so the test set is connected the same way every time.

A metering cubicle is wired as one package, so the SUPERB PCBA and the SUPERB PCB are checked against the same terminal schedule and the CT circuit is reviewed once for both.

Sourcing and Cross-Reference

The first question on a replacement is the conductor range, not the colour. A 6 mm2 block will not take a 10 mm2 flexible conductor with a ferrule, and forcing it is how a test point becomes a hot spot. The second question is whether the slide is single or coupled: a coupled slide gives the make before break action across neighbouring blocks, and a plain slide does not.

The third question is the accessory set. Blocks are usually replaced one at a time, but the bridge bars, switching jumpers and test connectors are what make a three phase test possible, and they are matched to the pitch. An 8 mm connector on an 8.2 mm block is a loose fit that reads as an intermittent test result.

Where a code has been superseded, the usual route is the same body with the wider conductor range and the same pitch, since the rail and the bridge bars stay. See lead time and availability for a specific code, and BOM shortage recovery where a panel is waiting on one row of blocks.

The SUPERB Assembly team keeps the shorting links fitted while the secondary is landed and removes them only at the test, because a CT circuit opened under load is the failure this whole row exists to prevent.

Q: Can you confirm the conductor range and whether the slide is coupled to the neighbouring block, because our test procedure relies on the short being made before the break opens?

A: Yes. Send the conductor size, the CT secondary current, the rail type, the number of phases and the test procedure, and the SUPERB Tech team returns the blocks with the bridges and test connectors that fit.

Why Panel Builders Source CT Test Blocks Through SUPERB

  1. Break behaviour described: the slide and the make before break action are stated per code, because a block that separates first is a safety problem, not a convenience.
  2. Current classes kept apart: 41 A on 6 mm2 and 57 A on 10 mm2 are quoted with the maximum load current, so a protection circuit is not sized from the nominal figure alone.
  3. Accessories in the same pitch: shorting connectors, switching jumpers and test connectors are listed with their pitch, so a row bridges without a fit problem.
  4. Rail compatibility stated: all three rail types are named, which is what an extension of an existing panel needs before the row is ordered.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Metering Current Transformers for Panel and Switchgear, Protection Current Transformers for Overcurrent Relays, DIN Rail Terminal Blocks for Control Panel Wiring, DIN Rail End Stops and Terminal Partition Plates, Screw Terminal Blocks and Pluggable Connectors, Component Lead Time Solutions.