Detuned Reactors and Harmonic Filters for Capacitor Banks
Product Specifications
Product Overview
A capacitor bank does not create harmonics, it amplifies them. The supply transformer and the bank form a parallel resonant circuit, and its resonant frequency depends on the short circuit power of the transformer and the kvar connected. When that frequency lands near the 5th harmonic, small harmonic currents from drives and rectifiers produce a large circulating current between the transformer and the capacitors. The result is a hot bank, swollen capacitors and fuses that open without a fault on the load.
A series reactor moves the resonance. With inductance in series with the capacitor, the series resonant frequency of the step is set by the detuning factor p, and it is deliberately placed below the lowest harmonic that matters: about 210 Hz for p at 5.7 percent, 189 Hz for 7 percent, and 134 Hz for 14 percent. At those frequencies the step is inductive rather than capacitive, so it cannot resonate with the transformer at 250 Hz or 350 Hz. The cost is a higher voltage across the capacitor, because the reactor carries the capacitor current and adds its own drop.
That voltage rise is the part that is usually missed. On a 400 V network a 7 percent step uses a 440 or 525 V capacitor and a 14 percent step uses an 800 V capacitor, because the capacitor sees the network voltage plus the reactor drop. Fitting a 400 V capacitor behind a 7 percent reactor runs it above its rated voltage continuously, and the failure shows up as capacitance loss after a year rather than as a fault on the first day. The reactor itself carries more than the fundamental current, since the harmonic spectrum adds to it, and it dissipates 150 to 320 W inside the panel, so forced convection and the panel thermal budget belong on the drawing.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Detuning factors | 5.7 percent, 7 percent and 14 percent | p sets the tuning frequency of the step |
| Tuning frequency at 50 Hz | 210 Hz, 189 Hz and 134 Hz | all three sit below the 5th harmonic at 250 Hz |
| Network | 400 V AC, 50 Hz, three phase | 60 Hz versions carry their own code, for example B40T |
| Step rating | 12.5 to 100 kvar per step at 400 V | the reactor is chosen with the capacitor, not after it |
| Inductance | 6.489 mH at 12.5 kvar 14 percent, 0.614 mH at 50 kvar 5.7 percent | tolerance minus 5 to plus 5 percent per phase |
| Fundamental current | 18 A at 12.5 kvar, 36.1 A at 25 kvar, 72.2 A at 50 kvar | I1 is the 50 Hz current alone |
| RMS current | 19.5 A at 12.5 kvar 7 percent, 88 A at 50 kvar 5.7 percent | this is the cable and terminal figure |
| Power losses | 150 W at 12.5 kvar, 200 W at 25 kvar, 320 W at 50 kvar | heat that stays inside the enclosure |
| Capacitor voltage rating | 440 to 525 V for 7 percent, 800 V for 14 percent | the reactor raises the voltage at the capacitor |
| Insulation | class H, rated insulation voltage 1.1 kV | dielectric test 4 kV at 50 Hz for one minute |
| Dynamic withstand | 2.2 times the short circuit current | the reactor must ride through the bank switching |
| Cooling and protection degree | forced convection, IP00, indoor installation | a fan is part of the installation, not an option |
| Ambient temperature | 0 to 55 C up to 1000 m, 0 to 50 C above 1000 m | average over 24 hours is 50 C at low altitude |
| Standards | IEC 60068 on the Schneider range, EN 61558-2-20 on the reactor build | the capacitor follows IEC 60831 |
Included Models and Order Codes
The Schneider code reads in two parts. The prefix LVR07 is the 7 percent family at 190 Hz, LVR05 the 5.7 percent family at 210 Hz and LVR14 the 14 percent family at 135 Hz; the next three characters are the kvar, where 125 is 12.5, 250 is 25, 500 is 50 and X00 is 100; the suffix A40T is the 400 V 50 Hz version, and the same reactor in 60 Hz carries B40T. The rows below are the ratings where the maker publishes inductance, current and losses together. The same three families continue with LVR05250A40T, LVR05500A40T, LVR07X00A40T, LVR14500A40T and LVR14X00A40T at 25, 50 and 100 kvar, and those codes can be quoted on request. The second table gives a Siemens 7 percent range in the same way, specified against a 440 V capacitor.
| Part number | Tuning | kvar at 400 V | Inductance | Fundamental current | Losses | Weight |
|---|---|---|---|---|---|---|
| LVR07125A40T | 7 percent, 190 Hz | 12.5 | 2.987 mH | 18 A | 150 W | 10 kg |
| LVR07250A40T | 7 percent, 190 Hz | 25 | 1.499 mH | 36.1 A | 200 W | 15 kg |
| LVR07500A40T | 7 percent, 190 Hz | 50 | 0.75 mH | 72.2 A | 320 W | 35.25 kg |
| LVR05125A40T | 5.7 percent, 210 Hz | 12.5 | 2.445 mH | 18 A | 150 W | 12.5 kg |
| LVR14125A40T | 14 percent, 135 Hz | 12.5 | 6.489 mH | 18 A | 150 W | 14.5 kg |
| LVR14250A40T | 14 percent, 135 Hz | 25 | 3.195 mH | 36.1 A | 200 W | not published |
Siemens 7 Percent Reactor Range at 440 V Capacitor Rating
This range is specified against a 440 V capacitor on a 400 V network, which is the usual pairing for a 7 percent step. The output column is the effective kvar the step delivers to the network, not the capacitor nameplate, and the loss column is the heat the reactor adds to the enclosure.
| Effective output | Inductance per phase | RMS current | Losses | Weight |
|---|---|---|---|---|
| 10 kvar | 3 x 4.64 mH | 14.9 A | 85 W | 10 kg |
| 12.5 kvar | 3 x 3.71 mH | 18.61 A | 88 W | 11 kg |
| 25 kvar | 3 x 1.86 mH | 37.2 A | 135 W | 20 kg |
| 50 kvar | 3 x 0.93 mH | 74.45 A | 250 W | 27 kg |
| 75 kvar | 3 x 0.62 mH | 111.7 A | 290 W | 43 kg |
| 100 kvar | 3 x 0.46 mH | 148.9 A | 390 W | 51 kg |
Key Features
Tuning factor on every row – p and the tuning frequency are written together, so a 189 Hz step is not ordered where the network needs 134 Hz.
Inductance and current paired – the mH value and the fundamental current come from the same maker table, which keeps a replacement from being matched on kvar alone.
RMS current above the fundamental – the harmonic current that the reactor passes is part of the rating, and it is the figure the cable and the terminal block have to carry.
Losses stated as heat – 150 to 320 W per step stays inside the enclosure, and the fan and the ventilation are sized from this column rather than from the kvar.
Capacitor voltage called out – the 440, 525 and 800 V pairings are on the page, because a 400 V capacitor behind a 7 percent reactor is the most common mismatch in a compensation panel.
Class H insulation and 2.2 times withstand – the winding is built for the temperature inside a sealed cabinet and for the switching current of the bank.
IP00 with forced convection – the reactor is an open component that needs airflow, so the mounting position and the clearance are part of the order rather than an afterthought.
Applications
Three network patterns cover most of the detuned reactor orders we quote, and the tuning factor is what separates them.
Buildings with six pulse drives – lifts, pumps and chillers leave 5th harmonic current in the network, so a 7 percent step at 189 Hz is the usual answer and the capacitor is a 440 or 525 V part.
Water treatment and irrigation stations – long cable runs and soft starters produce a mixed spectrum with 3rd harmonic present, which pushes the choice to 14 percent at 134 Hz and an 800 V capacitor.
Workshops with welders and induction heaters – the load changes minute by minute and the bank switches often, so the reactor loss and the 2.2 times withstand matter as much as the tuning factor.
The controller that switches these steps is often supplied with the panel, so the SUPERB PCBA and the SUPERB PCB are checked against the same step list and the reactor current is confirmed once for both.
Sourcing and Cross-Reference
A detuned step is a pair, and the pair is what has to be quoted. The reactor code carries the kvar and the tuning factor, the capacitor code carries the voltage rating, and a replacement that matches one but not the other runs the capacitor above its rating. On the Schneider range the A40T suffix also carries the frequency, so a 60 Hz panel needs the B40T code rather than a 50 Hz part.
The second question is the physical fit. These reactors are open IP00 components with a forced convection requirement, and a 50 kvar unit is 35 kg on a 220 by 240 mm footprint. Where a panel was built for capacitors alone, adding reactors usually means a new section, a fan and a thermal check, so the enclosure depth and the airflow belong in the inquiry along with the kvar.
For a step waiting on one rating, the options are usually the same family at the next kvar with the capacitor re-rated, the equivalent reactor from another maker at the same tuning factor, or a 5.7 percent step where the spectrum allows it. See lead time and availability for a specific code, and BOM shortage recovery where a compensation panel is held up by one reactor.
The SUPERB Assembly team mounts the reactor on its own plate with the clearance the maker asks for, because a 320 W loss against a plastic duct is a slow failure rather than an obvious one.
Q: Can you confirm the tuning factor and the capacitor voltage rating of a proposed step before we release the panel?
A: Yes. Send the network voltage, the step kvar, the harmonic spectrum or the THD you measure, and the SUPERB Tech team returns the tuning factor, the reactor code and the capacitor voltage rating that fit.
Why Compensation Builders Source Detuned Reactors Through SUPERB
- Tuning factor and frequency together: every row carries both, so a 5.7 percent reactor is not sent where the network has 3rd harmonic and needs 14 percent.
- Inductance, current and losses from one table: the three figures come from the same maker table, which is what a replacement has to match rather than the kvar alone.
- Capacitor pairing stated: the 440, 525 and 800 V pairing is written next to the reactor, so the capacitor on the same order is not a 400 V part.
- Heat and airflow flagged: the loss column and the forced convection requirement reach the panel drawing, which keeps a 35 kg reactor from being fitted into a sealed box.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Power Factor Correction Capacitors for Panel Compensation, Capacitor Switching Contactors for Power Factor Correction, Line Reactors and Motor Chokes for Variable Speed Drives, Surge Protective Devices for AC Distribution Boards, Digital Panel Meters and Counters for Control Panels, Power Distribution Blocks for Panel Feeds.