Surge Protective Devices for AC Distribution Boards

Type 2 and Type 1+2 surge devices for 230/400 V and 240/415 V systems. Nominal discharge 20 kA and 12.5 kA, maximum discharge 40 kA and 50 kA. Uc 275 V and 335 V versions, 2 pole and 4 pole, with or without remote contact. Replacement plugs and 35 mm DIN rail mounting.
quote now

Product Specifications

Product Overview

A surge protective device is chosen by three numbers: the maximum continuous voltage Uc, the nominal discharge current In, and the voltage protection level Up. Uc has to sit above the highest voltage the system can present in normal operation, In describes what the device takes repeatedly, and Up has to stay below what the equipment downstream can withstand.

Type 2 devices go at the distribution board and handle the residual surge after the incoming arrester, or the whole surge where there is no lightning protection. Type 1+2 devices combine the lightning impulse current path and the distribution board duty in one module, which is why they are used at the incoming position of a small panel.

The 230/1+1 and 320/1+1 families in the table are two-module devices: one module for the line to neutral path and one for neutral to earth. The 3+1 versions add the two remaining phases, and the 3+0 versions are for a three-wire system with no neutral. A device with the wrong pole count is not a smaller or larger version of the right one; it leaves a path unprotected.

Key Specifications

ModelTypeUcInImaxUpPolesMounting
VAL-MS 230/1+1Type 2275 V L-N, 260 V N-PE20 kA40 kA1.35 kV L-N, 1.5 kV N-PE235 mm DIN rail
VAL-MS 230/1+1-FMType 2275 V L-N, 260 V N-PE20 kA40 kA1.35 kV L-N, 1.5 kV N-PE235 mm DIN rail, remote contact
VAL-MS 320/1+1Type 2335 V L-N, 260 V N-PE20 kA40 kA1.5 kV L-N, 1.8 kV L-PE, 1.5 kV N-PE235 mm DIN rail
VAL-MS 320/1+1-FMType 2335 V L-N, 260 V N-PE20 kA40 kA1.5 kV L-N, 1.8 kV L-PE235 mm DIN rail, remote contact
VAL-MS 320/3+1/FMType 2335 V L-N, 260 V N-PE20 kA40 kA1.6 kV L-N, 1.9 kV L-PE435 mm DIN rail, remote contact
VAL-MS-T1/T2 335/12.5/1+1-FMType 1+2335 V12.5 kA50 kA1.35 kV L-N, 1.5 kV N-PE235 mm DIN rail, remote contact
VAL-MS-T1/T2 335/12.5/3+0-FMType 1+2335 V12.5 kA50 kABy pole3+035 mm DIN rail, remote contact
VAL-MS-T1/T2 335/12.5/3+1-FMType 1+2335 V12.5 kA50 kABy pole435 mm DIN rail, remote contact

Included Models and Order Codes

Order codes below include the base element and the protection plugs. The replacement plugs at the end are for a device that has already operated: the base stays on the rail and only the plug is changed.

Part numberModelPolesWidth or pitchNotes
2804429VAL-MS 230/1+1235.6 mm, 2 DivUc 275 V
2804432VAL-MS 230/1+1-FM235.6 mm, 2 DivRemote signalling contact
2804380VAL-MS 320/1+122 modulesUc 335 V
2804393VAL-MS 320/1+1-FM22 modulesRemote signalling contact
2859181VAL-MS 320/3+1/FM44 modulesUc 335 V, remote contact
2800186VAL-MS-T1/T2 335/12.5/1+1-FM22 modulesLightning current 12.5 kA
2800188VAL-MS-T1/T2 335/12.5/3+0-FM3+04 modulesThree-wire system
2800183VAL-MS-T1/T2 335/12.5/3+1-FM44 modulesFour-wire system
2798844VAL-MS 230 ST replacement plug1-For 230/1+1 base
2800190VAL-MS-T1/T2 335/12.5 ST replacement plug1-For T1/T2 base

Device Selection by System

The table is the short version of the selection: the Uc has to cover the highest normal voltage, and the pole count follows the earthing arrangement, not the number of phases alone.

SystemDeviceUc neededReason
230/400 V TN-S, single phase boardVAL-MS 230/1+1275 VL-N and N-PE paths in one device
230/400 V TTVAL-MS 230/1+1275 VN-PE module handles the earth path
240/415 V TN-S with high UcVAL-MS 320/1+1335 VVoltage tolerance and harmonics
Three phase, four wireVAL-MS 320/3+1/FM335 VThree line paths plus neutral
Three phase, three wireVAL-MS-T1/T2 335/12.5/3+0-FM335 VNo neutral path needed
Incoming position with exposed lineVAL-MS-T1/T2 335/12.5/1+1-FM335 VLightning impulse current path
Cabinet cooling unit supplyVAL-MS 230/1+1275 VMatches the Uc, In and Up the unit maker specifies

Key Features

Uc by system voltage – 275 V for 230 V systems and 335 V for 240/415 V systems, so the device does not operate on a normal overvoltage.

Two discharge classes – Type 2 for the distribution board and Type 1+2 for the incoming position, with 20 kA and 12.5 kA nominal discharge.

Pole count by earthing – 2, 3+0 and 4 pole versions, because a missing N-PE path is not covered by a larger device.

Remote signalling option – the FM versions carry a changeover contact for the building management system.

Pluggable protection modules – the base stays wired and only the plug is replaced after an operation, which keeps the downtime to one module.

Optical status window – the plug shows its state at the device, and the FM contact repeats it at the panel.

Applications

Surge devices follow the distribution structure. Three patterns repeat.

Machine control panels – a Type 2 device at the incoming terminals where the panel has its own supply and a sensitive drive behind it.

Telecom and outdoor cabinets – Type 1+2 at the incoming position, with the cooling unit and the heater on the protected side.

Building distribution boards – 4 pole Type 2 devices on a three phase board with a remote contact to the monitoring system.

Surge devices are quoted with the distribution board, and the SUPERB PCBA and the SUPERB PCB are checked against the same single line drawing so the pole count and the voltage match.

Sourcing and Cross-Reference

Check the Uc against the actual system voltage, not the nominal one. A 240/415 V system with a high tap can sit above 275 V, and a 275 V device that operates on normal voltage is a nuisance trip, not protection.

Keep the leads short. The protection level at the equipment is the device Up plus the voltage dropped along the connecting leads, so a long loop raises the real level well above the datasheet figure.

Order the replacement plug with the device. After an operation the base is still good, and a spare plug turns a shutdown into a module change.

Match the backup fuse to the device. The maker states the maximum backup fuse, and a larger fuse upstream leaves the device without the short circuit protection it was tested with.

The SUPERB Assembly team mounts the device at the incoming terminals with the shortest possible lead, because the lead length is part of the protection level.

Q: Which device fits a 240/415 V system with a 335 V Uc requirement?

A: Yes. Send the system voltage and the earthing arrangement; the SUPERB Tech team quotes the device with the matching Uc and pole count.

Why Builders Buy Surge Protection From SUPERB

  1. Selection by system: the Uc and the pole count are checked against the earthing arrangement before the part number is quoted.
  2. Type 2 and Type 1+2 in one line: distribution board and incoming position devices are quoted from the same range.
  3. Spare plugs held: a replacement plug is quoted with the device so the base is not replaced after an operation.
  4. Remote contact option: the FM versions are available where the panel is monitored.