Power Distribution Blocks for Panel Feeds
Product Specifications
Product Overview
A power distribution block takes one feeder cable and splits it into several branch circuits inside the panel, at a fixed and listed connection point instead of a bundle of split bolts and tape. It is an open style block: the live parts are insulated by the body, but the assembly has to sit inside an enclosure, and the block is approved as a component under UL 1953 rather than as a standalone device.
The rating is per pole, and it is not one number. An aluminium connector accepts aluminium or copper wire, a copper connector accepts copper only, and the same block carries a lower figure with aluminium: the three pole 63153 is rated 135 A with aluminium and 175 A with copper. Voltage is 1000 V AC and 1000 V DC across the family, so the same block covers a 480 V AC feeder and a 48 V DC battery feed.
The short circuit figure is the one that gets missed. A block on its own is rated 10 kA, and reaches 100 kA only with the right upstream fuse class, which the maker states per class: Class J, Class T, Class RK1, Class RK5, Class CC and Class G each have their own maximum fuse. A block that is correct for the load but matched to the wrong fuse class is a 10 kA component in a 100 kA panel.
Key Specifications
| Part number | Poles | Rating AL / CU | Primary wire range | Secondary openings | Voltage | Width |
|---|---|---|---|---|---|---|
| MPDB62101 | 1 | - / 85 A | #4 - #14 | 1 per pole | 1000 V AC / DC | 26.7 mm |
| MPDB63103 | 3 | 65 A / 85 A | #4 - #14 | 1 per pole | 1000 V AC / DC | 78.2 mm |
| MPDB62133 | 3 | - / 175 A | 2/0 - #14 | 4 per pole | 1000 V AC / DC | 73.9 mm |
| MPDB63153 | 3 | 135 A / 175 A | 2/0 - #14 | 1 per pole | 1000 V AC / DC | 73.9 mm |
| MPDB67653 | 3 | 250 A / 310 A | 350 kcmil - #6 | 10 per pole | 1000 V AC / DC | 134.1 mm |
Included Models and Order Codes
Order codes below cover the four ratings that most panel feeds land on. The torque column is the maker figure per wire size, not a single value for the block, because the primary and the secondary screws are different sizes and the smallest wire in a range has its own figure.
| Part number | Rating AL / CU | Primary / secondary | Torque | W x L x H | Body |
|---|---|---|---|---|---|
| MPDB62101 | - / 85 A | 1 x #4-#14 / 1 x #4-#14 | #4-#6 35, #8 25, #10-#14 20 lb-in | 26.7 x 78.2 x 71.4 mm | Tin plated copper |
| MPDB63103 | 65 A / 85 A | 1 x #4-#14 / 1 x #4-#14 | #4-#6 35, #8 25, #10-#14 20 lb-in | 78.2 x 78.2 x 71.4 mm | Tin plated aluminium |
| MPDB62133 | - / 175 A | 1 x 2/0-#14 / 4 x #4-#14 | primary 2/0-#3 50, #4-#6 45, #8 40, #10-#14 35 lb-in | 73.9 x 78.2 x 71.4 mm | Tin plated copper |
| MPDB63153 | 135 A / 175 A | 1 x 2/0-#14 / 1 x 2/0-#14 | primary #2/0-#3 50, #4-#6 45, #8 40, #10-#14 35 lb-in | 73.9 x 78.2 x 71.4 mm | Tin plated aluminium |
| MPDB67653 | 250 A / 310 A | 1 x 350 kcmil-#6 / 10 x #6-#14 | primary 275 lb-in, secondary #6 28, #8 25, #10-#14 20 lb-in | 134.1 x 78.2 x 82.6 mm | Tin plated aluminium |
Feeder to Branch Selection
The table maps a feeder size to the block that carries it and the branch pattern it gives. It is the step that decides the part number, before the cover and the end barrier are added.
| Feeder | Block | Branch pattern | Where it is used |
|---|---|---|---|
| #4 copper, up to 85 A | MPDB62101 | 1 opening per pole | Single pole tap inside a small control panel |
| #4 copper, three phase, up to 85 A | MPDB63103 | 1 opening per pole | Small three phase feed, one branch per pole |
| 2/0 copper, up to 175 A | MPDB62133 | 4 openings per pole | Drive feed split into four branch circuits |
| 2/0 aluminium, 135 A, or copper 175 A | MPDB63153 | 1 opening per pole | Feeder through a junction point |
| 350 kcmil aluminium, 250 A, or copper 310 A | MPDB67653 | 10 openings per pole | Mains feed into a branch panel |
| Extra pole on any three pole body | Adder pole | 1 opening per pole | Fourth pole or a later extension |
Key Features
Adder poles in the field – single poles stack onto a three pole body without tools, so a fourth pole or a later extension does not need a new block.
Aluminium and copper versions – the aluminium connector takes aluminium or copper wire, the copper connector takes copper only, and the two current ratings are stated apart.
Glass filled polycarbonate body – UL94 V-0 insulator, rated to 80 C, with one piece tin plated connectors on every pole.
Spacing that meets UL508A – 1 inch through air and 2 inches over surface between live parts of opposite polarity, which is what a feeder and branch application needs.
Hinged safety covers per pole – a see-through cover gives dead front protection, clips on without tools and carries a test probe hole for checking a circuit live.
Short circuit rating with a fuse class – 10 kA standalone and 100 kA with the fuse class the maker states, so the upstream fuse and the block are chosen together.
Applications
Distribution blocks are chosen by the feeder and the number of branches. Three patterns repeat.
Machine control panels – one feeder into three or four branch circuits, with the block mounted on the plate next to the contactors.
Drive and motor panels – a 175 A feed split into four branches, each to its own drive, where the four opening pattern removes a row of separate junction boxes.
Telecom and battery cabinets – a 48 V DC feed distributed to ten fused branch circuits, using the DC rating of the same block.
Blocks are quoted with the feeder cable and the branch fuses, and the SUPERB PCBA and the SUPERB PCB are checked against the same panel schedule so the pole count, the wire range and the fuse class match before the cabinet is wired.
Sourcing and Cross-Reference
Fix the conductor material before the rating. A 175 A copper feed on the 63153 is inside the block rating, the same 175 A on aluminium is not: that block is 135 A with aluminium, and the next size up is the correct answer, not a tighter torque.
Match the fuse class to the fault level. The 100 kA figure assumes the listed fuse class and its maximum rating; with a larger fuse the assembly falls back to the standalone rating, and the panel label then tells the wrong story.
Torque by wire size, with a calibrated driver. The primary of the 67653 takes 275 lb-in on a 350 kcmil conductor and the secondary screw takes 20 lb-in on a #14. One value for the whole block is how a loose joint is made.
Order the cover with the block. One cover is needed per pole, it is a separate catalog number, and a block that arrives without covers cannot be energised on the day. See lead time and availability when a feeder and its branch parts have to land together.
The SUPERB Assembly team lands the feeder first and torques it to the maker figure, because a block that is tightened by feel is where a hot joint starts.
Q: Does an adder pole need a separate end barrier?
A: Yes. Send the feeder ampacity, the number of branch circuits and the conductor material; the SUPERB Tech team quotes the block with the right pole count and opening pattern.
Why Builders Buy Distribution Blocks From SUPERB
- Rating split by material: the aluminium and copper figures are quoted apart, so a 175 A feed is not put on a 135 A aluminium rating.
- Fuse class checked: the short circuit rating is quoted with the upstream fuse class it depends on.
- Opening pattern stated: one, four or ten openings per pole, so the branch count is fixed before the panel is drilled.
- Covers and adder poles in the same quote: the accessories that stop a panel on the day ship with the block.