Power Distribution Blocks for Panel Feeds

Open style power distribution blocks, UL 1953, 1000 V AC and DC. Ampere ratings from 65 A to 310 A, with aluminium and copper figures stated apart. One, four or ten openings per pole, in one, three and four pole bodies. Adder poles stack in the field without tools.
quote now

Product Specifications

Product Overview

A power distribution block takes one feeder cable and splits it into several branch circuits inside the panel, at a fixed and listed connection point instead of a bundle of split bolts and tape. It is an open style block: the live parts are insulated by the body, but the assembly has to sit inside an enclosure, and the block is approved as a component under UL 1953 rather than as a standalone device.

The rating is per pole, and it is not one number. An aluminium connector accepts aluminium or copper wire, a copper connector accepts copper only, and the same block carries a lower figure with aluminium: the three pole 63153 is rated 135 A with aluminium and 175 A with copper. Voltage is 1000 V AC and 1000 V DC across the family, so the same block covers a 480 V AC feeder and a 48 V DC battery feed.

The short circuit figure is the one that gets missed. A block on its own is rated 10 kA, and reaches 100 kA only with the right upstream fuse class, which the maker states per class: Class J, Class T, Class RK1, Class RK5, Class CC and Class G each have their own maximum fuse. A block that is correct for the load but matched to the wrong fuse class is a 10 kA component in a 100 kA panel.

Key Specifications

Part numberPolesRating AL / CUPrimary wire rangeSecondary openingsVoltageWidth
MPDB621011- / 85 A#4 - #141 per pole1000 V AC / DC26.7 mm
MPDB63103365 A / 85 A#4 - #141 per pole1000 V AC / DC78.2 mm
MPDB621333- / 175 A2/0 - #144 per pole1000 V AC / DC73.9 mm
MPDB631533135 A / 175 A2/0 - #141 per pole1000 V AC / DC73.9 mm
MPDB676533250 A / 310 A350 kcmil - #610 per pole1000 V AC / DC134.1 mm

Included Models and Order Codes

Order codes below cover the four ratings that most panel feeds land on. The torque column is the maker figure per wire size, not a single value for the block, because the primary and the secondary screws are different sizes and the smallest wire in a range has its own figure.

Part numberRating AL / CUPrimary / secondaryTorqueW x L x HBody
MPDB62101- / 85 A1 x #4-#14 / 1 x #4-#14#4-#6 35, #8 25, #10-#14 20 lb-in26.7 x 78.2 x 71.4 mmTin plated copper
MPDB6310365 A / 85 A1 x #4-#14 / 1 x #4-#14#4-#6 35, #8 25, #10-#14 20 lb-in78.2 x 78.2 x 71.4 mmTin plated aluminium
MPDB62133- / 175 A1 x 2/0-#14 / 4 x #4-#14primary 2/0-#3 50, #4-#6 45, #8 40, #10-#14 35 lb-in73.9 x 78.2 x 71.4 mmTin plated copper
MPDB63153135 A / 175 A1 x 2/0-#14 / 1 x 2/0-#14primary #2/0-#3 50, #4-#6 45, #8 40, #10-#14 35 lb-in73.9 x 78.2 x 71.4 mmTin plated aluminium
MPDB67653250 A / 310 A1 x 350 kcmil-#6 / 10 x #6-#14primary 275 lb-in, secondary #6 28, #8 25, #10-#14 20 lb-in134.1 x 78.2 x 82.6 mmTin plated aluminium

Feeder to Branch Selection

The table maps a feeder size to the block that carries it and the branch pattern it gives. It is the step that decides the part number, before the cover and the end barrier are added.

FeederBlockBranch patternWhere it is used
#4 copper, up to 85 AMPDB621011 opening per poleSingle pole tap inside a small control panel
#4 copper, three phase, up to 85 AMPDB631031 opening per poleSmall three phase feed, one branch per pole
2/0 copper, up to 175 AMPDB621334 openings per poleDrive feed split into four branch circuits
2/0 aluminium, 135 A, or copper 175 AMPDB631531 opening per poleFeeder through a junction point
350 kcmil aluminium, 250 A, or copper 310 AMPDB6765310 openings per poleMains feed into a branch panel
Extra pole on any three pole bodyAdder pole1 opening per poleFourth pole or a later extension

Key Features

Adder poles in the field – single poles stack onto a three pole body without tools, so a fourth pole or a later extension does not need a new block.

Aluminium and copper versions – the aluminium connector takes aluminium or copper wire, the copper connector takes copper only, and the two current ratings are stated apart.

Glass filled polycarbonate body – UL94 V-0 insulator, rated to 80 C, with one piece tin plated connectors on every pole.

Spacing that meets UL508A – 1 inch through air and 2 inches over surface between live parts of opposite polarity, which is what a feeder and branch application needs.

Hinged safety covers per pole – a see-through cover gives dead front protection, clips on without tools and carries a test probe hole for checking a circuit live.

Short circuit rating with a fuse class – 10 kA standalone and 100 kA with the fuse class the maker states, so the upstream fuse and the block are chosen together.

Applications

Distribution blocks are chosen by the feeder and the number of branches. Three patterns repeat.

Machine control panels – one feeder into three or four branch circuits, with the block mounted on the plate next to the contactors.

Drive and motor panels – a 175 A feed split into four branches, each to its own drive, where the four opening pattern removes a row of separate junction boxes.

Telecom and battery cabinets – a 48 V DC feed distributed to ten fused branch circuits, using the DC rating of the same block.

Blocks are quoted with the feeder cable and the branch fuses, and the SUPERB PCBA and the SUPERB PCB are checked against the same panel schedule so the pole count, the wire range and the fuse class match before the cabinet is wired.

Sourcing and Cross-Reference

Fix the conductor material before the rating. A 175 A copper feed on the 63153 is inside the block rating, the same 175 A on aluminium is not: that block is 135 A with aluminium, and the next size up is the correct answer, not a tighter torque.

Match the fuse class to the fault level. The 100 kA figure assumes the listed fuse class and its maximum rating; with a larger fuse the assembly falls back to the standalone rating, and the panel label then tells the wrong story.

Torque by wire size, with a calibrated driver. The primary of the 67653 takes 275 lb-in on a 350 kcmil conductor and the secondary screw takes 20 lb-in on a #14. One value for the whole block is how a loose joint is made.

Order the cover with the block. One cover is needed per pole, it is a separate catalog number, and a block that arrives without covers cannot be energised on the day. See lead time and availability when a feeder and its branch parts have to land together.

The SUPERB Assembly team lands the feeder first and torques it to the maker figure, because a block that is tightened by feel is where a hot joint starts.

Q: Does an adder pole need a separate end barrier?

A: Yes. Send the feeder ampacity, the number of branch circuits and the conductor material; the SUPERB Tech team quotes the block with the right pole count and opening pattern.

Why Builders Buy Distribution Blocks From SUPERB

  1. Rating split by material: the aluminium and copper figures are quoted apart, so a 175 A feed is not put on a 135 A aluminium rating.
  2. Fuse class checked: the short circuit rating is quoted with the upstream fuse class it depends on.
  3. Opening pattern stated: one, four or ten openings per pole, so the branch count is fixed before the panel is drilled.