Contact Us
  • Home
  • COMPONENTS
  • Power Factor Correction Capacitors for Panel Compensation

Power Factor Correction Capacitors for Panel Compensation

A compensation capacitor supplies the reactive current that a motor or a rectifier draws, so the panel does not take it from the supply. The range covers 12.5 to 33.1 kvar at 415, 440 and 525 V in three phase delta cans from 85 to 116 mm diameter. Each can has an overpressure disconnector that takes all three phases off the supply at end of life. Life is quoted at 180,000 hours for the gas filled series, with 500 times rated current inrush.
quote now

Product Specifications

Product Overview

Most industrial loads draw a current that is not in step with the voltage, and the reactive part of that current does no work but still heats the cables and loads the transformer. A capacitor draws a current that leads the voltage, and connecting one across the supply cancels the lagging current of the motors. The result is a lower current for the same power, a lower bill where the utility charges for reactive power, and a transformer that can carry more real load.

The capacitors used for this are three phase units with the windings connected in delta inside one can. Delta connection puts the full line voltage across each winding and gives three times the reactive output of the same capacitance in star, which is why the physical size stays manageable at 25 kvar. The can is filled with an inert gas or a resin, and the winding is a stacked film with a self healing property.

The part number is a specification in itself. MKK440-D-25.0-03 means a gas filled can, 440 V rated, delta connected, 25 kvar at 50 Hz, three phase. The voltage in that string is the rated voltage of the capacitor, not the system voltage, and a 440 V can on a 415 V system delivers about 22 kvar, while the same can on a 480 V system delivers more than its rating and fails early.

Key Specifications

ParameterValueNote
Phases and connection3 phase, deltaone can per step
Rated voltages in this range415, 440 and 525 V ACthe can rating, not the system voltage
Output range12.5 kvar to 33.1 kvar at 50 Hz60 Hz output is about 20 percent higher
Capacitance77 uF at 12.5 kvar 415 V to 181.4 uF at 33.1 kvar 440 Vwritten per part
Can size85 mm diameter at 12.5 kvar, 116 mm up to 33.1 kvarheight 192 to 224 mm
Dielectricstacked metallised polypropylene film, self healingdry winding, gas or resin impregnated
Overpressure disconnectorall three phases disconnected at end of lifethe can lengthens and the internal fuse opens
Maximum inrush current500 times rated currentwith a contactor rated for capacitor switching
Life expectancy180,000 hours on the gas series200,000 hours on the resin series
Switching cyclesup to 15,000 per yearwith a capacitor duty contactor
Maximum case temperature60 C to IEC 60831-1the upper limit of the category
Dischargeresidual voltage below 75 V within 3 minutesdischarge resistors built into the can
Mountingupright, base stud, no tiltcooling by convection around the can

Included Models and Order Codes

The type string on the label is the shortest description of the part: MKK for the gas filled series, the number that follows for the rated voltage, a D for delta, the kvar at 50 Hz and 03 for three phase. Buying by type string is safer than buying by capacitance, because two cans with the same capacitance at different voltages have very different outputs.

Part numberTypeOutput at 50 HzRated voltageCapacitanceCan size
B25674C4122J515MKK415-D-12.5-0312.5 kvar415 V77 uF85 x 200 mm
B25674C4252J040MKK440-D-25.0-0325 kvar440 V137 uF116 x 192 mm
B25674C4302J040MKK440-D-30.0-0330 kvar440 Von request116 mm diameter
B25674C4332J140MKK440-D-33.1-0333.1 kvar440 V181.4 uF116 x 224 mm
B25674C5252J025MKK525-D-25.0-0325 kvar525 V96.2 uF116 x 207 mm
B32344E4122A500PhiCap 400 V series12.5 kvar400 Von requeston request
B32344E4252A000PhiCap 400 V series25 kvar400 Von requeston request
B32344E4302A040PhiCap 440 V series30 kvar440 Von requeston request

Output Changes With the System Voltage

The kvar on the label is quoted at the rated voltage of the can. On a system at a different voltage the output follows the square of the ratio, and the table below is that relationship for the three cans in this range. It is the calculation that decides whether a 440 V can is right for a 415 V board.

CanAt 380 VAt 400 VAt 415 VAt 440 V
MKK415-D-12.5-0310.5 kvar11.6 kvar12.5 kvar14.0 kvar
MKK440-D-25.0-0318.7 kvar20.7 kvar22.3 kvar25.0 kvar
MKK440-D-33.1-0324.7 kvar27.4 kvar29.5 kvar33.1 kvar
MKK525-D-25.0-0313.1 kvar14.5 kvar15.6 kvar17.5 kvar

Key Features

Overpressure disconnector on all three phases – at end of life the can lengthens and the internal connection opens, which takes the capacitor off the supply instead of letting it burst.

500 times rated current inrush – the winding takes the switching surge of a capacitor step, which is what a detuned bank and a capacitor duty contactor are there to manage.

180,000 hour life – the gas filled series is quoted at that figure, which is what makes a fixed compensation bank a maintenance free item for years.

15,000 switching cycles per year – a bank that follows the load switches often, and the figure is the limit that decides whether a contactor or a thyristor module is used.

Can size per output – the diameter and height are on the row, so a 33.1 kvar can is not ordered for a 600 mm wide cubicle without checking the space.

Dry self healing winding – a breakdown in the film clears itself and the can keeps its capacitance, which is the behaviour that separates this family from a liquid filled capacitor.

Applications

Compensation capacitors are bought by the load that lags, and three cases cover most of the requests.

Fixed compensation on a motor group – a group of motors that run together is compensated by one or two steps connected with the group, and the can is sized on the reactive power of that group at the actual system voltage.

Automatic banks in a main board – a bank with a controller switches steps in and out as the load changes, and each step is one can with its own contactor and its own protection.

Detuned banks on a distorted supply – where the supply carries harmonics from drives, the capacitor is fitted with a series reactor that shifts the resonance below the lowest harmonic, and the can voltage rating is raised for the reactor.

A compensation step is quoted with the board that controls it, so the SUPERB PCBA and the SUPERB PCB are checked on the same step list and the contactor coil shares the panel control voltage.

Sourcing and Cross-Reference

Quote the system voltage, not only the kvar. A 440 V can on a 415 V board delivers 22.3 kvar rather than 25, and the same can on a 480 V board is over its rated voltage every hour it runs. The rated voltage on the label has to be at or above the highest sustained system voltage, including the upper tolerance.

Check the harmonic environment before choosing a plain can. A capacitor on a supply with a high fifth harmonic draws more current than its rating and fails early, and a detuned reactor is the answer rather than a bigger can. The reactor also raises the voltage across the capacitor, which is why the can in a detuned bank is rated above the system voltage.

Large cans are a production item and the lead time follows the winding. Where an output is short, see lead time and availability, and shortage recovery when a bank is waiting on one step.

The SUPERB Assembly team mounts the can upright with clearance around the body and keeps the discharge time on the label, because a capacitor that is reclosed before it has discharged takes an inrush it was not built for.

Q: Can you size the capacitor step from the load and the system voltage, and supply the contactor and the protection for that step on one list?

A: Yes. Send the load, the system voltage, the harmonic environment and the number of steps, and the SUPERB Tech team returns the can, the contactor and the protection for that step.

Why Panel Builders Buy Compensation Capacitors From SUPERB

  1. Rated voltage on the row: the can rating and the output are separate columns, which is what stops a 440 V part being ordered for a 480 V board.
  2. Output at other voltages given: the four column table shows what the can delivers at 380, 400, 415 and 440 V, which is the number the bank is actually sized on.
  3. Life and switching limit: 180,000 hours and 15,000 cycles per year decide whether a step can follow the load or has to be fixed.
  4. Safety device described: the overpressure disconnector is part of the part, and that is what a panel safety review asks about on a capacitor bank.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Motor Start and Run Capacitors for Single Phase Motors, Film Capacitors for Snubber and AC Filter Applications, Contactors and Reversing Contactors for Motor Loads, Digital Panel Meters and Counters for Control Panels, Residual Current Devices for Panel Feeders.