Contact Us
  • Home
  • COMPONENTS
  • Digital Panel Meters and Counters for Control Panels

Digital Panel Meters and Counters for Control Panels

Panel meters that turn a DC signal into a readable number, in four input ranges from 200 mV to 200 V full scale. Totalisers with eight digits and a built-in battery that keep counting with the panel supply off. Preset counters with relay output and a 48 by 48 mm cut-out for machine cycles and batch counts. Every part is listed with its cut-out, supply and input type, because those three decide the fit.
quote now

Product Specifications

Product Overview

A panel meter and a counter look alike on a door and behave differently. The meter scales a continuous signal, a shunt amplifier output, a 4 to 20 mA loop or a divided voltage, into digits. The counter takes pulses and keeps a total, and a preset counter closes a relay when the total reaches a set value.

For the meter the critical number is the full scale range, not the display size. A 200 mV full scale meter reads a 75 mV shunt directly, while the same body in the 20 V range cannot resolve the same signal. The input impedance then decides how much the meter loads the source, which matters on a high impedance sensor and does not matter on a buffered loop.

For the counter the critical numbers are the count speed and the supply. A self-powered totaliser keeps its count in a battery backed display and needs no panel supply at all, while a preset counter needs a supply, a relay output rating and a cut-out that matches the existing door. Mixing the two types on one panel is normal, and the cut-out is what usually forces the choice.

Key Specifications

FamilyFunctionDigitsInputSupplyPanel cut-out
Murata DMS-30PCDC voltmeter, LED3.5differential, 200 mV to 200 V full scale+5 V DCpanel mount, pin header
Omron H7EC-Ntotal counter, LCD8no-voltage contact or open collectorself-powered, built-in battery48 x 24 mm
Omron H7CXpreset counter and tachometer, LCD6no-voltage NPN or voltage PNP100 to 240 V AC, or 12 to 24 V DC48 x 48 mm
Autonics CT6Spreset counter and timer, LED6no-voltage or voltage100 to 240 V AC, 48 V DC variant48 x 48 mm

Included Models and Order Codes

The rows below cover the two jobs: read a signal, or count events. On the Murata meter the code carries the range and the colour, so DMS-30PC-1-RS is the 2 V range in standard red and DMS-30PC-3-RL is the 200 V range in the low power red. On Omron the H7EC-N needs no supply at all, while the H7CX needs a supply and returns a relay contact. Count speed is given for the fastest input the part accepts without a pulse shaper.

Part numberTypeRange or countInputSupplyOutput
DMS-30PC-0-RS3.5 digit LED voltmeter200 mV full scaledifferential, 1 GOhm+5 V DC, 225 mA maxnone
DMS-30PC-1-RS3.5 digit LED voltmeter2 V full scaledifferential, 1 GOhm+5 V DC, 225 mA maxnone
DMS-30PC-2-RS3.5 digit LED voltmeter20 V full scaledifferential, 1 MOhm+5 V DC, 225 mA maxnone
DMS-30PC-3-RL3.5 digit LED voltmeter, low power200 V full scaledifferential, 1 MOhm+5 V DC, 10 mAnone
H7EC-N8 digit total counter0 to 99999999no-voltage, 30 Hz or 1 kHzself-powered, 3 V lithium cellnone
H7EC-NP8 digit total counter, PC board mount0 to 99999999no-voltage, 1 kHzself-powered, 3 V lithium cellnone
H7CX-A11N-N6 digit preset counter1 stage preset, 6 digitno-voltage or voltage, switchable100 to 240 V ACSPDT relay
H7CX-A4D-N6 digit preset counter1 stage preset with totalno-voltage or voltage, switchable12 to 24 V DCSPDT relay
CT6S-1P46 digit preset counter1 preset, 6 digit, 10 mm digitsno-voltage or voltage100 to 240 V ACrelay and NPN

Key Features

Four input ranges on one body – the same 3.5 digit meter covers 200 mV, 2 V, 20 V and 200 V full scale, so a 75 mV shunt and a divided bus voltage use one part number family.

High impedance on the low ranges – 1 GOhm on the 200 mV and 2 V inputs means a resistive divider is not loaded by the meter, and the reading stays linear.

Self-powered totaliser – the eight digit counter keeps its count with the panel supply off, which is what an hours or cycles log needs after a power cut.

Preset relay output – the preset counter closes a relay at the set value, so a batch stop or a diverter is wired without a separate trip amplifier.

Standard cut-outs – 48 by 24 mm and 48 by 48 mm cut-outs match the common door punch, which keeps a spare in the same hole.

IP66 front with the gasket – the 48 by 48 mm counters reach IP66 at the panel face when the sealing gasket is fitted, which is the difference between a wash down panel and a dry one.

Applications

These parts sit on three kinds of door. Each one is decided by the signal rather than by the display.

Shunt and loop readout on a power panel – a 3.5 digit meter on the 200 mV range reads a 75 mV shunt directly, and the same body on the 2 V range reads a 4 to 20 mA loop across a 100 Ohm resistor.

Machine cycle and batch counting – a 48 by 48 mm preset counter with relay output stops the feed at the set batch, and the total stays visible for the shift record.

Service hour logging – an eight digit self-powered totaliser on the contactor auxiliary keeps counting through a supply failure, so the maintenance interval is not lost.

The readout is quoted with the board that feeds it, so the SUPERB PCBA and the SUPERB PCB are checked for the 5 V rail and the divider values before the meter range is fixed.

Sourcing and Cross-Reference

Read the full scale range from the source, not from the display. A 75 mV shunt on a 200 V range meter shows close to zero, and a 10 V signal on the 200 mV range saturates the input. Working back from the signal with a margin of about 30 percent keeps the reading in the top two thirds of the scale, where the resolution is useful.

Check the input impedance before putting a divider in front of the meter. The 200 mV and 2 V ranges draw almost nothing, and the 20 V and 200 V ranges load the divider with 1 MOhm. A 100 kOhm divider feeding a 1 MOhm input is a two percent error that looks like a calibration fault.

Decide whether the count has to survive a power cut. A self-powered totaliser does, and a preset counter with a supply does not unless the count is held in memory. For a maintenance log the totaliser is the cheaper answer, and for a batch stop the preset counter is the only one with a relay.

Delivery on the 48 by 48 mm counters follows the display colour and the supply more than the function. See lead time and availability for the current position, and the cross reference hub when the meter on the drawing is no longer offered.

The SUPERB Assembly team fits the gasket before the counter goes into the door, because the seal cannot be added from the front once the retaining clip is closed.

Q: Can you supply a panel meter scaled for our shunt, with the cut-out and the supply of the panel we already have?

A: Yes. Send the signal at full scale, the supply available in the panel and the cut-out of the existing door, and the SUPERB Tech team returns the range, the part number and the gasket that fit.

Why Panel Builders Buy Meters and Counters From SUPERB

  1. Range chosen from the signal: the full scale and the input impedance are matched to the shunt or the loop before the part is quoted.
  2. Cut-out stated per part: 48 by 24 mm and 48 by 48 mm are in the table, so the door punch matches the spare.
  3. Supply confirmed: self-powered, 5 V, 24 V and 100 to 240 V AC versions are separated, because the wrong supply is the usual reason a meter stays dark.
  4. Sealing called out: the gasket that brings the front to IP66 is quoted with the counter, not left to be discovered at the panel test.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Current Transformers and AC Current Sensing, Current Sense Shunt Resistors for Power Measurement, Hall Effect Current Sensors for Motor Monitoring, DIN Rail Power Supplies for Control Cabinets, Signal Towers and Stack Lights for Machine Status.