Line Reactors and Motor Chokes for Variable Speed Drives
Product Specifications
Product Overview
A line reactor is three coils on one core, wired in series with each phase of a drive supply. It does two jobs. It adds impedance in front of the rectifier, which softens the current pulses that a six pulse bridge draws and reduces the harmonic content that goes back into the panel. And it absorbs the voltage notch that a commutation notch or a capacitor switching event puts on the supply, which is what protects the rectifier diodes.
The same body can be used on the motor side, and then it is called a motor choke or a load reactor. Its job changes: with a long cable between drive and motor, the fast switching edges of the inverter reflect at the motor terminals and the peak voltage can reach twice the DC bus value. A load side choke slows the edge, and the maker data for this range states the limit as 500 to 1500 V per microsecond where the cable is longer than 50 m.
Selection is by current first and inductance second. The choke has to carry the drive input current continuously and 1.65 times that current for 60 seconds during acceleration, so the rated current of the part has to sit at or above the drive current, not at the motor nameplate current. Inductance then sets the impedance: a 4 percent impedance choke on a 400 V supply is the common choice, and the tables below give the inductance so the percentage can be worked out against the drive rating.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Number of phases | 3 | one coil per phase on a common core |
| Inductance range | 0.1 mH to 10 mH | across the ten bodies in this range |
| Rated current range | 4 A to 450 A | continuous, at 40 C ambient |
| Overload | 1.65 times rated current for 60 s | covers the acceleration of the drive |
| Frequency | 50 and 60 Hz | line side or load side |
| Thermal loss | 65 W at 10 A, up to 260 W at 107 A | ventilation of the enclosure has to include it |
| Degree of protection | IP00 body | terminal cover raises the terminal area to IP20 where fitted |
| Insulation class | class F winding | on the encapsulated range |
| Mounting | base mounting, vertical airflow | keep 50 mm clear above and below |
| Terminal | screw clamp or stud, per body | cable range increases with the body size |
| Ambient temperature | -10 C to +45 C | derate above 45 C |
| Standards | IEC 61558-2-20, EN 61558 | reactor for supply or load side use |
Included Models and Order Codes
The part number rises with current and the inductance falls with it, which is the point: a 4 A choke needs a large inductance to reach the same impedance that a 230 A choke reaches with a fraction of a millihenry. Bodies up to 17 A share one footprint of 130 x 155 x 90 mm, and above that the case grows with the copper.
| Part number | Inductance | Rated current | Thermal loss | Body size | Typical use |
|---|---|---|---|---|---|
| VW3A4551 | 10 mH | 4 A | on request | 100 x 135 x 60 mm | small single phase fed drive or a filter choke |
| VW3A4552 | 4 mH | 10 A | 65 W | 130 x 155 x 90 mm | 0.75 to 2.2 kW drive on a 400 V supply |
| VW3A4553 | 2 mH | 17 A | 75 W | 130 x 155 x 90 mm | 3 to 5.5 kW drive, most common machine size |
| VW3A4554 | 1 mH | 31 A | 90 W | 155 x 170 x 135 mm | 7.5 to 11 kW drive |
| VW3A4555 | 0.5 mH | 60 A | 94 W | 180 x 210 x 160 mm | 15 to 22 kW drive |
| VW3A4556 | 0.3 mH | 107 A | 260 W | 270 x 210 x 180 mm | 30 to 45 kW drive, check the enclosure airflow |
| VW3A4557 | 0.15 mH | 230 A | on request | on request | large frame drive on a shared busbar |
| VW3A4570 | 0.22 mH | 160 A | on request | on request | load side choke for a long motor cable |
| VW3A4571 | 0.23 mH | 230 A | on request | on request | load side choke, 230 A frame |
| VW3A4572 | 0.1 mH | 450 A | on request | on request | load side choke on a large frame |
Line Side or Load Side: What Changes
The same choke can be fitted in either position, but the reason for fitting it and the number that has to be checked are different. The table below is the decision in the wording used on the drive data sheets.
| Position | What it protects | Number to check | Fitting note |
|---|---|---|---|
| Supply side | rectifier diodes and the panel supply | harmonic content and supply impedance | between the breaker and the drive terminals |
| Supply side, shared | several drives on one feeder | total current of the group | one choke per drive, not one for the group |
| Load side | motor winding insulation | dv/dt at the motor, cable length | cable over 50 m is the usual trigger |
| Load side, parallel motors | each motor circuit | sum of the motor currents | one choke per motor, after the individual protection |
| Not a filter | - | - | a choke reduces harmonics, it does not meet a class A limit on its own |
Key Features
1.65 times current for 60 seconds – the overload window matches the acceleration of a drive, so the choke does not saturate during a ramp and does not need to be oversized for it.
Ten bodies from 4 to 450 A – one family covers a 0.75 kW machine and a 250 kW line, which keeps the panel drawing consistent across a range.
Inductance stated per part – the millihenry value is written on every row, so the impedance percentage can be checked against the drive rating instead of assumed from the current.
Body sizes given – the footprint and height are listed, which decides whether the choke fits beside the drive in a 600 mm cabinet.
IP00 with an optional terminal cover – the open body is cooled by the enclosure airflow, and the terminal area can be closed to IP20 where a finger guard is required.
Line or load side – the same part is used on either side of the drive, and the applications section explains which number to check in each position.
Applications
A reactor is bought by the problem it solves in the panel, and these three cover most of the requests we see.
Harmonic reduction on a shared supply – a drive on a weak supply or a group of drives on one transformer draws current in short pulses, and a 4 percent line reactor spreads those pulses and lowers the harmonic current that the transformer sees.
Long motor cable protection – when the cable between drive and motor is over 50 m, the switching edge reflects at the motor and the peak voltage rises, and a load side choke brings the edge back within what the winding can take.
Protecting the rectifier from supply events – capacitor switching and commutation notches in a plant supply arrive at the drive input as a fast voltage step, and the impedance of the choke absorbs part of that step before it reaches the diodes.
The drive, the choke and the control board travel as one package, so the SUPERB PCBA and the SUPERB PCB are checked on the same current list and the choke is sized from the drive rather than from the motor plate.
Sourcing and Cross-Reference
Size the choke from the drive input current, not from the motor nameplate. A 5.5 kW motor on a 400 V supply draws about 11 A at full load, but the drive input current at 50 Hz is higher and the acceleration current is 1.65 times the rated figure, so a 17 A choke is the common match and a 10 A part would run hot on a ramp.
A choke is not a harmonic filter. It reduces the current distortion and it protects the rectifier, but a drive with a choke alone does not meet a class A limit, and a panel that has to meet a limit needs a passive or active filter. Writing a choke into a compliance statement is a mistake that shows up at the witness test.
Delivery on this range is usually a stock question for the small bodies and a production question for the large ones. Where a current is not available, see lead time and availability, and shortage recovery when a drive is waiting on its choke to ship.
The SUPERB Assembly team mounts the choke on the same plate as the drive and keeps 50 mm clear above the winding, because a choke starved of air is the usual cause of a hot cabinet.
Q: Can you confirm whether the choke I need is a line side or a load side part, and supply the matching drive accessories on the same list?
A: Yes. Send the drive rating, the supply voltage and the cable length to the motor, and the SUPERB Tech team returns the choke, the position and the body size that fit.
Why Panel Builders Buy Reactors From SUPERB
- Line and load side explained: the two uses are separated, so a choke is not ordered for the wrong side of the drive and then found to be ineffective.
- Overload window stated: 1.65 times rated current for 60 s is a column, which is what decides a size on a machine with a long ramp.
- Thermal loss given: the watt figure per part is what the enclosure cooling has to remove, and it is often left out of a reactor data sheet.
- Body size and mounting: the footprint is listed with the part, so a 107 A choke is not ordered for a 600 mm cabinet without checking the airflow.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Soft Starters for Motor Starting, Braking Resistors for Variable Speed Drives, Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, DIN Rail Power Supplies for Control Cabinets.