Capacitor Switching Contactors for Power Factor Correction
Product Specifications
Product Overview
A capacitor step is not a motor load. When the contactor closes, the capacitor is close to a short circuit for the first few milliseconds, and any step already energised discharges into it as well. The peak is quoted as a multiple of the running current, often 100 times or more, and a general purpose contactor that closes on that peak welds its contacts after a few thousand operations. AC-6b is the utilisation category that describes this duty, and it is the first item to check on any contactor proposed for a capacitor bank.
Two constructions cover the range. A standard AC-6b contactor is rated for peaks up to 100 times the capacitor current, which suits a single step on a stiff supply or a bank where each step is switched on its own. Where the peak goes beyond that, a contactor with damping resistors is used: the resistors are in circuit for the first milliseconds, hold the peak down, and are shorted by the main contacts as the armature finishes its travel. ABB UA..RA, Schneider LC1DFK and LC1DMK, and Siemens 3RT26 all work on this principle, and each of them either publishes a peak figure or states that the peak is unlimited.
Selection is made on kvar at the actual network voltage and at the ambient inside the panel, not on the 400 V figure alone. The same frame carries a different rating at 230 V, 400 V, 500 V and 690 V, and the rating falls as the ambient rises: a device rated 50 kvar at 40 C is a 39 kvar device at 70 C. Two further conditions belong on the drawing. The capacitor must be discharged to 50 V or less before the contactor recloses, and the short circuit protection is a gG fuse sized at 1.5 to 1.8 times the capacitor current.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Utilisation category | AC-6b to IEC 60947-4-1 | the category that covers capacitor switching, not AC-3 |
| Rated operational voltage | up to 690 V AC, 50 or 60 Hz | ratings are quoted per voltage, not scaled |
| Rated power at 400 to 415 V | 12.5 to 100 kvar at 40 C | falls to 10 to 65 kvar at 70 C on the ABB table |
| Rated power at 230 to 240 V | 7 to 40 kvar | roughly 55 percent of the 400 V figure |
| Rated power at 690 V | 21 to 90 kvar | same frame, higher voltage, higher kvar |
| Peak current, standard device | 100 times rated rms current | 1.8 kA on UA16 up to 10.5 kA on UA110 |
| Peak current, damping resistor device | unlimited up to the stated short circuit level | UA..RA and 3RT26 carry precharge resistors |
| Electrical durability | 100,000 cycles on UA, 250,000 on UA..RA below 500 V | 300,000 cycles at 400 V on the Schneider capacitor frames |
| Switching frequency | 240 cycles per hour on ABB, 180 per hour on 3RT26 at 400 V | above this the resistors and contacts run hot |
| Short circuit protection | gG fuse at 1.5 to 1.8 times capacitor rated current | type 1 coordination to IEC 60947-4-1 |
| Coil voltages | 24, 48, 110, 220 to 230, 380 to 415 V AC, 24 and 110 V DC | wide range AC/DC coils on the 3RT26 N versions |
| Auxiliary contacts | 1 NO as standard, 1 NO plus 2 NC on some frames | add-on blocks fit the front or the side |
| Residual voltage before reclosing | 50 V or less at the capacitor terminals | otherwise the next close is a second inrush event |
| Ambient temperature | -25 to +60 C in operation | ratings quoted at 40 C unless the table says otherwise |
| Standards | IEC 60947-4-1, UL 508 and CSA where listed | UL and CSA figures are quoted at 60 Hz |
Included Models and Order Codes
The code carries the rating differently in each family, so the rows below are grouped by maker. On the ABB UA range, UA16-30-10 reads as UA for capacitor duty, 16 for the frame, 30 for three poles and 10 for one normally open auxiliary contact; the RA suffix adds the damping resistors, so UA50-30-00 RA is the resistor version of the 50 kvar frame. On the Schneider TeSys range, LC1DFK is the 12.5 kvar capacitor frame and LC1DMK the 25 kvar frame, with the coil code at the end, so LC1DFKM7 is a 220 V AC coil. Siemens 3RT26 codes carry the size and the auxiliary set, and the precharge resistors are part of the device rather than an accessory. Where a maker publishes only a family figure for a rating, the row says so instead of borrowing a number from another frame.
| Part number | Family | kvar at 400 V | kvar at 230 V | Peak current limit | Coil and contacts |
|---|---|---|---|---|---|
| UA16-30-10 (1SBL181022R8110) | ABB UA | 12.5 | 7.5 | 1.8 kA | 24 V AC, 1 NO |
| UA26-30-10 (1SBL241022R8110) | ABB UA | 20 | 12 | 3 kA | 24 V AC, 1 NO |
| UA30-30-10 (1SBL281022R8110) | ABB UA | 27.5 | 16 | 3.5 kA | 24 V AC, 1 NO |
| UA50-30-00 | ABB UA | 33 | 20 | 5 kA | 24 V AC, no auxiliary |
| UA75-30-00 | ABB UA | 50 | 30 | 7.5 kA | 24 V AC, no auxiliary |
| UA95-30-00 | ABB UA | 65 | 35 | 9.3 kA | 24 V AC, no auxiliary |
| UA110-30-00 | ABB UA | 75 | 40 | 10.5 kA | 24 V AC, no auxiliary |
| UA16-30-10 RA | ABB UA..RA | 12.5 | 8 | unlimited, damping resistors | 24 V AC, 1 NO |
| UA30-30-10 RA | ABB UA..RA | 30 | 16 | unlimited, damping resistors | 24 V AC, 1 NO |
| UA50-30-00 RA | ABB UA..RA | 40 | 25 | unlimited, damping resistors | 24 V AC, no auxiliary |
| UA110-30-00 RA | ABB UA..RA | 80 | 45 | unlimited, damping resistors | 24 V AC, no auxiliary |
| LC1DFKM7 | Schneider TeSys DFK | 12.5 | 7 | damping resistors | 220 V AC 50/60 Hz |
| LC1DMKM7 | Schneider TeSys DMK | 25 | 14 | damping resistors | 220 V AC 50/60 Hz |
| 3RT2617-1BB45 | Siemens 3RT26 S00 | 12.5 | 7.2 | precharge resistors | 24 V DC, 2 NC |
| 3RT2626-1NP35 | Siemens 3RT26 S0 | 20 | 11.5 | precharge resistors, integrated varistor | 200 to 280 V AC/DC, 1 NO and 2 NC |
| 3RT2626-1NB35 | Siemens 3RT26 S0 | 20 | 11.5 | precharge resistors, integrated varistor | 21 to 28 V AC/DC, 1 NO and 2 NC |
| 3RT2636-1AB05 | Siemens 3RT26 S2 | 50 | 29 | precharge resistors | 24 V AC, 2 NC |
Current and Fuse Window per Rating at 400 V
The capacitor current follows from the kvar, and the fuse follows from the current. Both numbers are on this table so a panel drawing can be checked without the maker table at hand. The current is Q divided by 1.732 times 400 V, and the fuse column is the 1.5 to 1.8 times band that ABB and Schneider both quote for gG protection of a capacitor step.
| kvar at 400 V | Rated current | 1.5 times current | 1.8 times current |
|---|---|---|---|
| 12.5 | 18.0 A | 27.1 A | 32.5 A |
| 20 | 28.9 A | 43.3 A | 52.0 A |
| 25 | 36.1 A | 54.1 A | 64.9 A |
| 33 | 47.6 A | 71.4 A | 85.7 A |
| 50 | 72.2 A | 108.3 A | 129.9 A |
| 75 | 108.3 A | 162.4 A | 194.9 A |
| 100 | 144.3 A | 216.5 A | 259.8 A |
Key Features
AC-6b rating stated first – the category that describes capacitor switching is on every row, because an AC-3 contactor of the same ampere size is not a substitute.
Damping or precharge resistors – the resistor versions hold the closing peak down and then short the resistors out, which is what allows a step to be switched without a series reactor.
kvar at four voltages – 230 V, 400 V, 500 V and 690 V ratings sit side by side, so a 690 V panel is not sized from a 400 V figure.
Ambient derating published – the same frame loses about 20 percent of its kvar between 40 C and 70 C, and the table shows where the loss starts.
Coil range from 21 V to 415 V – DC coils at 24 and 110 V, AC coils up to 415 V, with wide range AC/DC electronics on the N versions of the Siemens range.
Fuse band on the row – the gG fuse window of 1.5 to 1.8 times the capacitor current is given per rating, which keeps type 1 coordination inside the panel.
Discharge condition written out – 50 V or less before reclosing is stated as an operating condition rather than a note, because a fast reclosing duty doubles the inrush.
Applications
Three duty patterns cover most of the capacitor contactor orders we quote, and each one puts a different limit on the device.
Stepped compensation in plant rooms – six to twelve steps switched by a controller, where the step already energised discharges into the one closing, so the resistor version is the safe choice above 33 kvar.
Buildings with drives and rectifier loads – variable speed pumps, lifts and UPS units leave 5th and 7th harmonic current in the network, so the steps sit behind detuned reactors and the contactor is sized for the higher current that the reactor passes.
Pumping and compressor stations – frequent switching pushes the device towards its 240 cycles per hour limit, and the ambient inside a closed cabinet is often 50 C rather than 40 C, so the derated kvar column is the one to use.
The compensation controller is often quoted together with its board, so the SUPERB PCBA and the SUPERB PCB are checked against the same contactor list and the step wiring is reviewed once for both.
Sourcing and Cross-Reference
Most of these contactors are ordered as a line on a panel BOM, and the practical question is which frame the panel was built around. A UA50 sits on the same rail footprint as the general purpose A50, a 3RT26 uses the 3RT2 accessories, and an LC1D uses the TeSys D add-on blocks. The electrical rating can be matched across the three makers, the mounting and the auxiliary blocks cannot, so the first check on a replacement is the frame and the second is the kvar at the actual voltage.
The second question is the inrush. A bank that started as three steps often grows to eight, and the peak at the last step rises with every capacitor added. Where the original device was a standard AC-6b contactor, the honest answer at that point is to move to a resistor version or to add a reactor, not to fit a larger standard frame: the larger frame welds just as well, only later.
For a panel waiting on one rating, the options are usually the same frame in another coil voltage, the next frame up when the kvar still fits the fuse, or a resistor version where the peak has grown. See lead time and availability for a specific rating, and BOM shortage recovery where a compensation panel is held up by one contactor.
The SUPERB Assembly team torques the coil and main terminals to the maker figures, because a loose capacitor terminal on a 100 kvar step is a hot joint within a week.
Q: Can you confirm the kvar at 690 V and the peak current limit before we release a replacement contactor for our bank?
A: Yes. Send the step kvar, the network voltage, the number of steps and the panel ambient, and the SUPERB Tech team returns the frame, the coil voltage and the fuse band that fit.
Why Compensation Panel Builders Source Contactors Through SUPERB
- Rating at the panel voltage: the kvar figure is quoted at the voltage on the drawing, with 230 V, 400 V and 690 V columns, so a 690 V step is not sized from a 400 V row.
- Resistor versions kept separate: damping resistor and precharge resistor devices are listed as their own rows, which stops a standard AC-6b part from being sent where the peak is unlimited.
- Fuse and discharge conditions: the gG fuse band and the 50 V discharge condition sit with the rating, so the two conditions that decide contact life reach the panel drawing.
- Frame and accessories named: ABB UA, Schneider TeSys and Siemens 3RT26 frames are called out per row, so the replacement fits the rail and the auxiliary blocks already installed.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Power Factor Correction Capacitors for Panel Compensation, Detuned Reactors and Harmonic Filters for Capacitor Banks, Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, Line Reactors and Motor Chokes for Variable Speed Drives.