Motor Protection Circuit Breakers for Panel Feeders

Thermal magnetic motor protection circuit breakers from 0.10 A to 32 A in three families. Setting range and magnetic trip are listed per part number, because both decide whether the motor starts. One device provides the overload element, the short circuit trip and the isolation point. Mounting is on 35 mm rail, so the feeder occupies one column in the panel.
quote now

Product Specifications

Product Overview

A motor protection circuit breaker puts the overload element, the short circuit trip and the isolator into one device. The dial sets the thermal trip from the motor nameplate current, the magnetic element trips on the fault current, and the front knob is the point of isolation for maintenance. One part replaces a fuse holder, a thermal relay and a separate switch.

The two numbers on the label are the thermal setting range and the magnetic trip. The thermal range has to contain the motor full load current, and the magnetic trip is set by the device, not by the installer, at roughly thirteen times the top of that range. A breaker with a 6 to 10 A dial trips magnetically near 138 A, which is high enough to pass a direct on line start and low enough to catch a short in the motor cable.

Where the panel has to be certified as a self protected combination, the breaker carries the short circuit rating for the branch on its own, and the device is listed for group installation with the right terminal. That is the reason a panel builder chooses a motor protector rather than a miniature breaker: the miniature breaker protects the cable, not the motor.

Key Specifications

FamilySetting rangeMagnetic tripBreaking capacity at 400 VStandardsMounting
GV2ME, pushbutton control0.10 to 32 Afixed, about 13 times the top of the range100 kA at 400 and 415 V, 3 kA at 690 VIEC 60947-2 and IEC 60947-4-1, category A35 mm rail or plate
MS116, manual motor starter0.10 to 32 Afixed per part, 1.56 A to 480 A50 kA to 10 A, 25 kA at 12 A, 16 kA at 16 A, 10 kA from 20 to 32 AIEC 60947-4-1, UL 60947-4-135 mm rail or screw fixing
PKZM0, motor protective breaker0.10 to 32 Afixed per part, 62 A to 496 A40 kA at 400 V on the 32 A frameIEC 60947-4-1, UL 60947-4-135 mm rail, 45 mm wide

Included Models and Order Codes

The magnetic trip column is the part of the data sheet that is rarely printed in a price list, and it is the one that explains a start that trips the breaker on a healthy motor. Read it against the starting current of the motor: a direct on line start pulls six to eight times full load for a few seconds, and a breaker whose magnetic trip sits too close to that figure opens on the start. The setting ranges below are exactly as the maker publishes them, including the narrow ones at the low end, where the code does not always follow the range.

Part numberFamilySetting rangeMagnetic trip
GV2ME01Schneider GV2ME0.10 to 0.16 A1.5 A
GV2ME02Schneider GV2ME0.16 to 0.25 A2.4 A
GV2ME03Schneider GV2ME0.25 to 0.40 A5 A
GV2ME04Schneider GV2ME0.40 to 0.63 A8 A
GV2ME05Schneider GV2ME0.63 to 1 A13 A
GV2ME06Schneider GV2ME1 to 1.6 A22.5 A
GV2ME07Schneider GV2ME1.6 to 2.5 A33.5 A
GV2ME08Schneider GV2ME2.5 to 4 A51 A
GV2ME10Schneider GV2ME4 to 6.3 A78 A
GV2ME14Schneider GV2ME6 to 10 A138 A
GV2ME16Schneider GV2ME9 to 14 A170 A
GV2ME20Schneider GV2ME13 to 18 A223 A
GV2ME21Schneider GV2ME17 to 23 A327 A
GV2ME22Schneider GV2ME20 to 25 A327 A
GV2ME32Schneider GV2ME24 to 32 A416 A
MS116-0.16ABB MS1160.10 to 0.16 A1.56 A
MS116-0.25ABB MS1160.16 to 0.25 A2.44 A
MS116-0.4ABB MS1160.25 to 0.40 A3.90 A
MS116-0.63ABB MS1160.40 to 0.63 A6.14 A
MS116-1.0ABB MS1160.63 to 1.00 A11.50 A
MS116-1.6ABB MS1161.00 to 1.60 A18.40 A
MS116-2.5ABB MS1161.60 to 2.50 A28.75 A
MS116-4.0ABB MS1162.50 to 4.00 A50.00 A
MS116-6.3ABB MS1164.00 to 6.30 A78.75 A
MS116-10ABB MS1166.30 to 10.0 A150 A
MS116-12ABB MS1168.00 to 12.0 A180 A
MS116-16ABB MS11610.0 to 16.0 A240 A
MS116-20ABB MS11616.0 to 20.0 A300 A
MS116-25ABB MS11620.0 to 25.0 A375 A
MS116-32ABB MS11625.0 to 32.0 A480 A
PKZM0-4Eaton PKZM02.5 to 4 A62 A
PKZM0-6,3Eaton PKZM04 to 6.3 A97.7 A
PKZM0-10Eaton PKZM06.3 to 10 A155 A
PKZM0-32Eaton PKZM025 to 32 A496 A

One Device Instead of Three

The reason this part exists is the bill of materials, not the trip curve. The comparison below is what changes when a feeder is built with a motor protector rather than a fuse holder, a thermal relay and a switch.

FunctionFuse and relay feederMotor protection breaker feeder
Overload protectionthermal relay set by hand, wired in seriesthermal dial on the device, set by hand
Short circuit protectionfuse or miniature breaker sized for the cablemagnetic trip built into the same device
Isolation for maintenanceseparate switch or a pull out fuse carrierfront knob, lockable with a padlock accessory
Rail spacethree items and the wiring between themone item, one column, 45 mm on the frames shown
Group installationchecked against the fuse and relay combinationdevice is listed for group installation with its terminal

Key Features

Dial range and magnetic trip in one table – both numbers the motor has to satisfy are printed side by side, so a start that trips the breaker is explained before the order.

Thermal and magnetic in one body – the overload element and the short circuit trip share the same poles, which removes the wiring between a relay and a breaker.

Lockable isolation point – the front knob is the isolation for maintenance, and a padlock accessory turns it into a lock out point without a second switch.

Phase failure sensitivity – a lost phase trips on the remaining phases, which stops a motor running hot on two windings.

35 mm rail mounting – the feeder drops onto the same rail as the terminals and the contactor, at 45 mm per column on the frames shown.

Three families, one specification – the same enquiry can be quoted in GV2ME, MS116 or PKZM0 so the panel builder keeps the brand already on the drawing.

Applications

The breaker follows the feeder, not the machine. Three cases repeat in the enquiries we quote.

Single motor feeders in a control cabinet – one breaker per motor, with the dial at the nameplate current and the knob used as the isolation point during maintenance.

Group installations on a shared feeder – several protectors under one set of fuses, where the device has to be listed for group installation with the terminal that is fitted.

Panels that travel with the machine – a breaker with a lockable knob, because the isolation point has to be fixed to the panel rather than carried in a tool bag.

Motor feeders and their protection are quoted with the board that drives them, and the SUPERB PCBA and the SUPERB PCB are checked against the same motor schedule so the dial range, the magnetic trip and the rail space agree before the panel is built.

Sourcing and Cross-Reference

Start from the nameplate current and the starting method. Direct on line starting pulls six to eight times full load, a star delta start drops that to about a third on the line, and a soft starter removes the question. The dial range has to contain the running current, and the magnetic trip has to sit above the starting current, which is why the same 10 A dial works on one machine and trips on another.

Check the short circuit rating against the panel, not against the motor. A 100 kA device and a 10 kA device protect the same motor, but only one of them suits a feeder at the transformer. The breaking capacity per family is in the specification table above, and the back-up fuse requirement, where there is one, comes from the maker coordination table.

Decide the isolation point early. If the panel drawing shows a separate switch, the breaker becomes a protector and the switch stays. If the drawing shows the knob as the isolation, the knob has to be lockable and the panel door has to clear it when closed.

Older panels often carry a protector that is no longer current, and the dial range is the fastest way to find the replacement. See lead time and availability for a stock check, or BOM shortage recovery when the line is down and the part has to be found rather than ordered.

The SUPERB Assembly team sets the dial and records the value on the panel schedule, because a breaker adjusted during commissioning is the one that trips again after a service visit.

Q: Can you supply a motor protection breaker set to our motor current and confirm the magnetic trip will pass the start?

A: Yes. Send the motor nameplate with full load current and supply voltage, the starting method and the prospective fault current, and the SUPERB Tech team returns the frame, the dial range and the isolation accessory that fit.

Why Builders Buy Motor Protection Breakers From SUPERB

  1. Magnetic trip stated per part: the number that decides whether a start trips the breaker is in the table, not left to a phone call.
  2. Three families quoted side by side: the panel builder keeps the brand already on the drawing and still gets a comparable specification.
  3. Range confirmed against the motor: the nameplate current and the starting method are checked before the part is quoted, so the dial sits inside the scale.
  4. Isolation accessory quoted with the part: the lockable knob and the auxiliary contact are part of the quotation, because a bare breaker often fails the lock out requirement.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors, Thermal Overload Relays for Motor Protection, Power Distribution Blocks for Panel Feeds, Surge Protective Devices for AC Distribution, DIN Rail Power Supplies for Control Cabinets.