Motor Protection Circuit Breakers for Panel Feeders
Product Specifications
Product Overview
A motor protection circuit breaker puts the overload element, the short circuit trip and the isolator into one device. The dial sets the thermal trip from the motor nameplate current, the magnetic element trips on the fault current, and the front knob is the point of isolation for maintenance. One part replaces a fuse holder, a thermal relay and a separate switch.
The two numbers on the label are the thermal setting range and the magnetic trip. The thermal range has to contain the motor full load current, and the magnetic trip is set by the device, not by the installer, at roughly thirteen times the top of that range. A breaker with a 6 to 10 A dial trips magnetically near 138 A, which is high enough to pass a direct on line start and low enough to catch a short in the motor cable.
Where the panel has to be certified as a self protected combination, the breaker carries the short circuit rating for the branch on its own, and the device is listed for group installation with the right terminal. That is the reason a panel builder chooses a motor protector rather than a miniature breaker: the miniature breaker protects the cable, not the motor.
Key Specifications
| Family | Setting range | Magnetic trip | Breaking capacity at 400 V | Standards | Mounting |
|---|---|---|---|---|---|
| GV2ME, pushbutton control | 0.10 to 32 A | fixed, about 13 times the top of the range | 100 kA at 400 and 415 V, 3 kA at 690 V | IEC 60947-2 and IEC 60947-4-1, category A | 35 mm rail or plate |
| MS116, manual motor starter | 0.10 to 32 A | fixed per part, 1.56 A to 480 A | 50 kA to 10 A, 25 kA at 12 A, 16 kA at 16 A, 10 kA from 20 to 32 A | IEC 60947-4-1, UL 60947-4-1 | 35 mm rail or screw fixing |
| PKZM0, motor protective breaker | 0.10 to 32 A | fixed per part, 62 A to 496 A | 40 kA at 400 V on the 32 A frame | IEC 60947-4-1, UL 60947-4-1 | 35 mm rail, 45 mm wide |
Included Models and Order Codes
The magnetic trip column is the part of the data sheet that is rarely printed in a price list, and it is the one that explains a start that trips the breaker on a healthy motor. Read it against the starting current of the motor: a direct on line start pulls six to eight times full load for a few seconds, and a breaker whose magnetic trip sits too close to that figure opens on the start. The setting ranges below are exactly as the maker publishes them, including the narrow ones at the low end, where the code does not always follow the range.
| Part number | Family | Setting range | Magnetic trip |
|---|---|---|---|
| GV2ME01 | Schneider GV2ME | 0.10 to 0.16 A | 1.5 A |
| GV2ME02 | Schneider GV2ME | 0.16 to 0.25 A | 2.4 A |
| GV2ME03 | Schneider GV2ME | 0.25 to 0.40 A | 5 A |
| GV2ME04 | Schneider GV2ME | 0.40 to 0.63 A | 8 A |
| GV2ME05 | Schneider GV2ME | 0.63 to 1 A | 13 A |
| GV2ME06 | Schneider GV2ME | 1 to 1.6 A | 22.5 A |
| GV2ME07 | Schneider GV2ME | 1.6 to 2.5 A | 33.5 A |
| GV2ME08 | Schneider GV2ME | 2.5 to 4 A | 51 A |
| GV2ME10 | Schneider GV2ME | 4 to 6.3 A | 78 A |
| GV2ME14 | Schneider GV2ME | 6 to 10 A | 138 A |
| GV2ME16 | Schneider GV2ME | 9 to 14 A | 170 A |
| GV2ME20 | Schneider GV2ME | 13 to 18 A | 223 A |
| GV2ME21 | Schneider GV2ME | 17 to 23 A | 327 A |
| GV2ME22 | Schneider GV2ME | 20 to 25 A | 327 A |
| GV2ME32 | Schneider GV2ME | 24 to 32 A | 416 A |
| MS116-0.16 | ABB MS116 | 0.10 to 0.16 A | 1.56 A |
| MS116-0.25 | ABB MS116 | 0.16 to 0.25 A | 2.44 A |
| MS116-0.4 | ABB MS116 | 0.25 to 0.40 A | 3.90 A |
| MS116-0.63 | ABB MS116 | 0.40 to 0.63 A | 6.14 A |
| MS116-1.0 | ABB MS116 | 0.63 to 1.00 A | 11.50 A |
| MS116-1.6 | ABB MS116 | 1.00 to 1.60 A | 18.40 A |
| MS116-2.5 | ABB MS116 | 1.60 to 2.50 A | 28.75 A |
| MS116-4.0 | ABB MS116 | 2.50 to 4.00 A | 50.00 A |
| MS116-6.3 | ABB MS116 | 4.00 to 6.30 A | 78.75 A |
| MS116-10 | ABB MS116 | 6.30 to 10.0 A | 150 A |
| MS116-12 | ABB MS116 | 8.00 to 12.0 A | 180 A |
| MS116-16 | ABB MS116 | 10.0 to 16.0 A | 240 A |
| MS116-20 | ABB MS116 | 16.0 to 20.0 A | 300 A |
| MS116-25 | ABB MS116 | 20.0 to 25.0 A | 375 A |
| MS116-32 | ABB MS116 | 25.0 to 32.0 A | 480 A |
| PKZM0-4 | Eaton PKZM0 | 2.5 to 4 A | 62 A |
| PKZM0-6,3 | Eaton PKZM0 | 4 to 6.3 A | 97.7 A |
| PKZM0-10 | Eaton PKZM0 | 6.3 to 10 A | 155 A |
| PKZM0-32 | Eaton PKZM0 | 25 to 32 A | 496 A |
One Device Instead of Three
The reason this part exists is the bill of materials, not the trip curve. The comparison below is what changes when a feeder is built with a motor protector rather than a fuse holder, a thermal relay and a switch.
| Function | Fuse and relay feeder | Motor protection breaker feeder |
|---|---|---|
| Overload protection | thermal relay set by hand, wired in series | thermal dial on the device, set by hand |
| Short circuit protection | fuse or miniature breaker sized for the cable | magnetic trip built into the same device |
| Isolation for maintenance | separate switch or a pull out fuse carrier | front knob, lockable with a padlock accessory |
| Rail space | three items and the wiring between them | one item, one column, 45 mm on the frames shown |
| Group installation | checked against the fuse and relay combination | device is listed for group installation with its terminal |
Key Features
Dial range and magnetic trip in one table – both numbers the motor has to satisfy are printed side by side, so a start that trips the breaker is explained before the order.
Thermal and magnetic in one body – the overload element and the short circuit trip share the same poles, which removes the wiring between a relay and a breaker.
Lockable isolation point – the front knob is the isolation for maintenance, and a padlock accessory turns it into a lock out point without a second switch.
Phase failure sensitivity – a lost phase trips on the remaining phases, which stops a motor running hot on two windings.
35 mm rail mounting – the feeder drops onto the same rail as the terminals and the contactor, at 45 mm per column on the frames shown.
Three families, one specification – the same enquiry can be quoted in GV2ME, MS116 or PKZM0 so the panel builder keeps the brand already on the drawing.
Applications
The breaker follows the feeder, not the machine. Three cases repeat in the enquiries we quote.
Single motor feeders in a control cabinet – one breaker per motor, with the dial at the nameplate current and the knob used as the isolation point during maintenance.
Group installations on a shared feeder – several protectors under one set of fuses, where the device has to be listed for group installation with the terminal that is fitted.
Panels that travel with the machine – a breaker with a lockable knob, because the isolation point has to be fixed to the panel rather than carried in a tool bag.
Motor feeders and their protection are quoted with the board that drives them, and the SUPERB PCBA and the SUPERB PCB are checked against the same motor schedule so the dial range, the magnetic trip and the rail space agree before the panel is built.
Sourcing and Cross-Reference
Start from the nameplate current and the starting method. Direct on line starting pulls six to eight times full load, a star delta start drops that to about a third on the line, and a soft starter removes the question. The dial range has to contain the running current, and the magnetic trip has to sit above the starting current, which is why the same 10 A dial works on one machine and trips on another.
Check the short circuit rating against the panel, not against the motor. A 100 kA device and a 10 kA device protect the same motor, but only one of them suits a feeder at the transformer. The breaking capacity per family is in the specification table above, and the back-up fuse requirement, where there is one, comes from the maker coordination table.
Decide the isolation point early. If the panel drawing shows a separate switch, the breaker becomes a protector and the switch stays. If the drawing shows the knob as the isolation, the knob has to be lockable and the panel door has to clear it when closed.
Older panels often carry a protector that is no longer current, and the dial range is the fastest way to find the replacement. See lead time and availability for a stock check, or BOM shortage recovery when the line is down and the part has to be found rather than ordered.
The SUPERB Assembly team sets the dial and records the value on the panel schedule, because a breaker adjusted during commissioning is the one that trips again after a service visit.
Q: Can you supply a motor protection breaker set to our motor current and confirm the magnetic trip will pass the start?
A: Yes. Send the motor nameplate with full load current and supply voltage, the starting method and the prospective fault current, and the SUPERB Tech team returns the frame, the dial range and the isolation accessory that fit.
Why Builders Buy Motor Protection Breakers From SUPERB
- Magnetic trip stated per part: the number that decides whether a start trips the breaker is in the table, not left to a phone call.
- Three families quoted side by side: the panel builder keeps the brand already on the drawing and still gets a comparable specification.
- Range confirmed against the motor: the nameplate current and the starting method are checked before the part is quoted, so the dial sits inside the scale.
- Isolation accessory quoted with the part: the lockable knob and the auxiliary contact are part of the quotation, because a bare breaker often fails the lock out requirement.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors, Thermal Overload Relays for Motor Protection, Power Distribution Blocks for Panel Feeds, Surge Protective Devices for AC Distribution, DIN Rail Power Supplies for Control Cabinets.