Thermal Overload Relays for Motor Protection
Product Specifications
Product Overview
A thermal overload relay is a bimetal element in series with the motor current. When the current sits above the dial setting for long enough, the element bends, the trip bar releases, and the normally closed contact opens the contactor coil. It protects the motor from a slow overload and from a lost phase; it does not protect against a short circuit, which is the job of the fuse or the breaker upstream.
The setting range is the only number that has to match the motor. A 7.5 kW motor at 400 V draws about 15.5 A, so the relay has to have a dial that covers 15.5 A, and several relays will cover it. What separates them is the frame they clip to, the reset method, and whether the range leaves room to set the dial at the actual nameplate current rather than at the end of the scale.
Trip class sets the delay. Class 10 A trips between 2 and 10 seconds at 7.2 times the dial current, which suits a pump, a fan or a conveyor. A motor with a long start, such as a high inertia fan or a screw compressor on a star delta starter, needs a class 20 element or the relay trips during a normal start and the operator blames the relay.
Key Specifications
| Family | Trip class | Setting range | Fits contactor frame | Reset | Phase failure |
|---|---|---|---|---|---|
| LRD 01 to LRD 35 | 10 A | 0.10 to 38 A | LC1D09 to LC1D38 | Manual or automatic, selector under a cover | Differential, trips on one lost phase |
| LRD 313 to LRD 365 | 10 A | 9 to 65 A | LC1D40A to LC1D65A | Manual or automatic | Differential |
| LRD 3322 to LRD 3363 | 10 A | 17 to 80 A | LC1D80 and LC1D95 | Manual or automatic | Differential |
| 3RU2116, size S00 | 10 | 0.11 to 16 A | 3RT2015 to 3RT2018 | Manual or automatic, RESET button | Yes, with phase failure sensitivity |
| 3RU2126, size S0 | 10 | 1.8 to 40 A | 3RT2023 to 3RT2028 | Manual or automatic, RESET button | Yes, with phase failure sensitivity |
| TA25DU | 10 A | 0.10 to 32 A | AX09 to AX40 | Manual or automatic, STOP button | Yes, three pole bimetal |
| TA42DU | 10 A | 18 to 42 A | AX32 and AX40 | Manual or automatic | Yes, three pole bimetal |
Included Models and Order Codes
Every row below is a data sheet range, not a rounded family figure. The Schneider relay code carries the top of the range, so LRD16 covers 9 to 13 A and sits under a D12 to D38 contactor, while LRD22 covers 16 to 24 A and needs a D25 or larger frame. On SIRIUS the size digit after 3RU2 sets the contactor size, so a 3RU2116 fits S00 and a 3RU2126 fits S0. The AX relays are ordered against the contactor series, and a TA25DU does not clip to an AX50.
| Part number | Family | Setting range | Trip class | Mounts under |
|---|---|---|---|---|
| LRD01 | LRD, differential | 0.10 to 0.16 A | 10 A | LC1D09 to LC1D38 |
| LRD05 | LRD, differential | 0.63 to 1 A | 10 A | LC1D09 to LC1D38 |
| LRD08 | LRD, differential | 2.5 to 4 A | 10 A | LC1D09 to LC1D38 |
| LRD12 | LRD, differential | 5.5 to 8 A | 10 A | LC1D09 to LC1D38 |
| LRD16 | LRD, differential | 9 to 13 A | 10 A | LC1D12 to LC1D38 |
| LRD21 | LRD, differential | 12 to 18 A | 10 A | LC1D18 to LC1D38 |
| LRD22 | LRD, differential | 16 to 24 A | 10 A | LC1D25 to LC1D38 |
| LRD32 | LRD, differential | 23 to 32 A | 10 A | LC1D25 to LC1D38 |
| LRD35 | LRD, differential | 30 to 38 A | 10 A | LC1D32 and LC1D38 |
| LRD340 | LRD, EverLink terminals | 30 to 40 A | 10 A | LC1D40A to LC1D65A |
| LRD350 | LRD, EverLink terminals | 37 to 50 A | 10 A | LC1D40A to LC1D65A |
| LRD365 | LRD, EverLink terminals | 48 to 65 A | 10 A | LC1D50A and LC1D65A |
| 3RU2116-0J | SIRIUS 3RU2, size S00 | 0.7 to 1 A | 10 | 3RT2015 to 3RT2018 |
| 3RU2116-1C | SIRIUS 3RU2, size S00 | 1.8 to 2.5 A | 10 | 3RT2015 to 3RT2018 |
| 3RU2116-1E | SIRIUS 3RU2, size S00 | 2.8 to 4 A | 10 | 3RT2015 to 3RT2018 |
| 3RU2116-1H | SIRIUS 3RU2, size S00 | 5.5 to 8 A | 10 | 3RT2015 to 3RT2018 |
| 3RU2116-1K | SIRIUS 3RU2, size S00 | 9 to 12.5 A | 10 | 3RT2015 to 3RT2018 |
| 3RU2126-4A | SIRIUS 3RU2, size S0 | 11 to 16 A | 10 | 3RT2023 to 3RT2028 |
| 3RU2126-4D | SIRIUS 3RU2, size S0 | 20 to 25 A | 10 | 3RT2023 to 3RT2028 |
| 3RU2126-4F | SIRIUS 3RU2, size S0 | 34 to 40 A | 10 | 3RT2023 to 3RT2028 |
| TA25DU-0.63 | TA25DU | 0.40 to 0.63 A | 10 A | AX09 to AX40 |
| TA25DU-2.4 | TA25DU | 1.7 to 2.4 A | 10 A | AX09 to AX40 |
| TA25DU-4.0 | TA25DU | 2.8 to 4.0 A | 10 A | AX09 to AX40 |
| TA25DU-6.5 | TA25DU | 4.5 to 6.5 A | 10 A | AX09 to AX40 |
| TA25DU-11 | TA25DU | 7.5 to 11 A | 10 A | AX09 to AX40 |
| TA25DU-19 | TA25DU | 13 to 19 A | 10 A | AX09 to AX40 |
| TA25DU-25 | TA25DU | 18 to 25 A | 10 A | AX09 to AX40 |
| TA25DU-32 | TA25DU | 24 to 32 A | 10 A | AX09 to AX40 |
Setting the Dial Without Tripping a Healthy Motor
Four numbers decide whether the relay trips on a fault or on a warm afternoon. They are the motor full load current, the ambient temperature at the relay, the starting time, and the back-up fuse. The table below is what we ask for before quoting a relay on its own, so the range is right the first time.
| Input we need | Why it changes the relay | Where it comes from |
|---|---|---|
| Motor full load current at the supply voltage | the dial has to sit near the middle of its range, not at the top | motor nameplate |
| Starting time in seconds | a start longer than about 10 s at 6 times FLC needs class 20 rather than class 10 A | starter schedule or the machine maker |
| Ambient at the relay | compensated relays hold their setting from -20 to +60 C, so a hot cabinet does not shift the trip point | panel thermal calculation |
| Back-up fuse or breaker | the fuse protects the relay and the cable, and its value comes from the maker table for that relay | short circuit coordination table |
Key Features
Setting range per part number – the range is printed on the dial and repeated in the table, so the motor current is checked against a real number rather than a family headline.
Differential trip on lost phase – one phase at 30 percent of the setting with the others at setting trips the relay, which is what saves a motor running on two phases.
Compensated from -20 to +60 C – the trip point does not drift with cabinet temperature, so a relay set in winter still protects the motor in summer.
Manual or automatic reset – the selector sits under a cover on the LRD frames, so automatic reset is a deliberate choice rather than something that happens by accident.
Test button and trip indicator – the button simulates a trip through both contacts, which checks the control wiring before the motor is coupled to the load.
Clips under the contactor – the relay terminals line up with the contactor poles, so the motor cable lands once and the relay carries the current without a separate run.
Applications
Relay choice follows the load, not the panel. Three cases come up most often in the enquiries we quote.
Pumps and fans started direct on line – class 10 A relay with the dial at the nameplate current, which covers a start of a few seconds without a trip.
Compressors and high inertia fans – class 20 relay or a longer trip class, because a class 10 element trips during a normal start and the fault is reported as a relay problem.
Motors in hot cabinets – compensated relay with the dial set in the panel at working temperature, so the trip point does not move with the cabinet heat.
Motor starters and their protection are quoted with the board that drives them, and the SUPERB PCBA and the SUPERB PCB are checked against the same motor list so the dial range and the coil voltage agree before the panel is wired.
Sourcing and Cross-Reference
Set the dial from the nameplate current at the actual supply voltage. A motor rated 15.5 A at 400 V draws more at 380 V, and a dial left at the top of its range gives no protection at all, while a dial at the bottom trips on a cold morning. The range has to put the nameplate current near the middle.
Check the frame before the range. A relay that covers the current but does not clip to the contactor needs an adapter and a separate mounting plate, which costs a rail slot and a wiring run. We quote the relay with the contactor it mounts to, so the pair is confirmed together.
Do not use the relay as the short circuit protection. The relay has a limited breaking capacity and relies on a fuse or a breaker upstream, and the value is taken from the relay maker table for the frame and the setting. A relay with no back-up fuse is a fire risk in a fault, not a protection device.
Long life motors and older panels are where supply gets awkward, because the relay that matches the contactor may be the part that is no longer current. See lead time and availability for a stock check, and the obsolete part cross reference hub when only the old code is on the drawing.
The SUPERB Assembly team sets the relay dial after the motor is coupled, because a dial set on the bench from the nameplate alone often sits high once the running current is measured on load.
Q: Can you match a thermal overload relay to a motor nameplate current and the contactor already in the panel?
A: Yes. Send the motor nameplate with full load current, supply voltage and starting time, plus the contactor already fitted, and the SUPERB Tech team returns the relay code and the dial setting that fit.
Why Builders Buy Overload Relays From SUPERB
- Range checked against the motor: the nameplate current is compared with the dial range before the relay is quoted, so the setting sits inside the scale.
- Relay and contactor together: the pair is confirmed as one mechanical set, which removes the adapter and the extra rail slot.
- Class 10 and class 20 options: a long start is quoted with the class 20 element instead of a class 10 relay that will trip on a healthy motor.
- Back-up protection stated: the fuse or breaker value that protects the relay is part of the quotation, not left to the panel builder.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors, Motor Protection Circuit Breakers for Panel Feeders, DIN Rail Terminal Blocks for Control Panel Wiring, DIN Rail End Stops and Partition Plates, Obsolete Part Cross Reference Hub.