Contactors and Reversing Contactors for Motor Loads
Product Specifications
Product Overview
A contactor carries the motor current; it does not decide when to stop. The coil takes a control signal, the main poles close, and the overload relay mounted underneath does the protecting. Getting the frame right by motor power and utilisation category is what keeps the contacts alive through a hundred thousand starts.
AC-3 is the category that matters on a motor. Read the AC-3 figure at the supply voltage, because the AC-1 figure is for resistive loads and is much higher than a motor will allow. A 4 kW motor at 400 V draws about 8.5 A, so the 9 A frame is the usual match even though the same body is listed at 25 A in AC-1.
The coil is the second decision. A 24 V DC coil is driven from a PLC output, a 220 V AC coil comes from a control transformer, and the same body is ordered with either. The order code carries the coil, so LC1D09M7 and LC1D09BD are one contactor with two different control circuits, and the panel drawing has to say which one.
Key Specifications
| Family | Poles and category | Current range | Motor power at 400 V | Control | Mounting |
|---|---|---|---|---|---|
| TeSys D, LC1D and LC2D | 3-pole, AC-3 | 7 to 50 A | 3 to 22 kW | AC coil 24 to 440 V, DC coil 24 to 220 V | 35 mm rail or screw fixing |
| SIRIUS 3RT2, size S00 | 3-pole, AC-3 | 7 to 16 A | 3 to 7.5 kW | AC or DC coil | 35 mm rail, 45 mm wide |
| SIRIUS 3RT2, size S0 | 3-pole, AC-3 | 9 to 38 A | 4 to 18.5 kW | AC or DC coil | 35 mm rail, 45 mm wide |
| AX09 to AX50 | 3-pole, AC-3 | 9 to 50 A | 4 to 22 kW | AC coil 24 to 415 V | 35 mm rail or screw fixing |
| Reversing pairs | 2 x 3-pole, mechanically interlocked | 7 to 32 A | 3 to 15 kW | AC or DC coil | Rail or plate, pre-wired |
Included Models and Order Codes
The rows below are the frames we quote most often, with the coil already in the order code. On TeSys D the last two characters carry the coil, so LC1D18M7 is an 18 A contactor with a 220 V 50/60 Hz coil and LC1D18BD is the same contactor on 24 V DC. On AX the tail is a two digit voltage code, and on 3RT2 the suffix after the dash sets coil, auxiliary contacts and terminal type. Motor power follows the maker table for standard four-pole motors at 400 V, so a motor with a high starting current still has to be checked against the AC-3 current.
| Part number | Family | AC-3 current at 400 V | Motor power at 400 V | Coil | Auxiliary contacts |
|---|---|---|---|---|---|
| LC1D09M7 | TeSys D, 3-pole | 9 A | 4 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D12M7 | TeSys D, 3-pole | 12 A | 5.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D18M7 | TeSys D, 3-pole | 18 A | 7.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D25M7 | TeSys D, 3-pole | 25 A | 11 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D32M7 | TeSys D, 3-pole | 32 A | 15 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D38M7 | TeSys D, 3-pole | 38 A | 18.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D40AM7 | TeSys D, 3-pole, EverLink terminals | 40 A | 18.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC1D50AM7 | TeSys D, 3-pole, EverLink terminals | 50 A | 22 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC |
| LC2D09M7 | TeSys D reversing pair | 9 A | 4 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC per contactor |
| LC2D12M7 | TeSys D reversing pair | 12 A | 5.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC per contactor |
| LC2D18M7 | TeSys D reversing pair | 18 A | 7.5 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC per contactor |
| LC2D25M7 | TeSys D reversing pair | 25 A | 11 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC per contactor |
| LC2D32M7 | TeSys D reversing pair | 32 A | 15 kW | 220 V AC 50/60 Hz | 1 NO + 1 NC per contactor |
| 3RT2015-1BB41 | SIRIUS 3RT2, size S00 | 7 A | 3 kW | 24 V DC | 1 NO |
| 3RT2016-1BB41 | SIRIUS 3RT2, size S00 | 9 A | 4 kW | 24 V DC | 1 NO |
| 3RT2017-1BB41 | SIRIUS 3RT2, size S00 | 12 A | 5.5 kW | 24 V DC | 1 NO |
| 3RT2018-1BB41 | SIRIUS 3RT2, size S00 | 16 A | 7.5 kW | 24 V DC | 1 NO |
| 3RT2025-1BB40 | SIRIUS 3RT2, size S0 | 17 A | 7.5 kW | 24 V DC | 1 NO + 1 NC |
| 3RT2026-1BB40 | SIRIUS 3RT2, size S0 | 25 A | 11 kW | 24 V DC | 1 NO + 1 NC |
| 3RT2027-1BB40 | SIRIUS 3RT2, size S0 | 32 A | 15 kW | 24 V DC | 1 NO + 1 NC |
| AX09-30-10-80 | AX, 3-pole | 9 A | 4 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX12-30-10-80 | AX, 3-pole | 12 A | 5.5 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX18-30-10-80 | AX, 3-pole | 18 A | 7.5 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX25-30-10-80 | AX, 3-pole | 25 A | 11 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX32-30-10-80 | AX, 3-pole | 32 A | 15 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX40-30-10-80 | AX, 3-pole | 40 A | 18.5 kW | 220 to 230 V AC 50 Hz | 1 NO |
| AX50-30-00-80 | AX, 3-pole | 50 A | 22 kW | 220 to 230 V AC 50 Hz | none built in |
Coil and Voltage Codes That Complete the Order
A contactor body is not a shippable part number until the coil is in the code. The three tables below are the codes that cover most panels: 24 V DC where a PLC output drives the coil, and 110 to 415 V AC where a control transformer supplies it. Ordering by body alone is the most common cause of a starter that arrives with the wrong coil.
| Series | Code | Control voltage | Note |
|---|---|---|---|
| TeSys D | B7 | 24 V AC 50/60 Hz | AC coil |
| TeSys D | F7 | 110 V AC 50/60 Hz | AC coil |
| TeSys D | M7 | 220 V AC 50/60 Hz | common on European panels |
| TeSys D | P7 | 230 V AC 50/60 Hz | AC coil |
| TeSys D | U7 | 240 V AC 50/60 Hz | AC coil |
| TeSys D | Q7 | 380 to 400 V AC | AC coil |
| TeSys D | V7 | 400 V AC 50/60 Hz | AC coil |
| TeSys D | N7 | 415 V AC 50/60 Hz | AC coil |
| TeSys D | BD | 24 V DC | for a PLC output |
| TeSys D | MD | 220 V DC | DC coil |
| SIRIUS 3RT2, S00 | -1BB41 | 24 V DC | 1 NO, screw terminals |
| SIRIUS 3RT2, S0 | -1BB40 | 24 V DC | 1 NO + 1 NC, screw terminals |
| AX | 81 | 24 V AC and DC | voltage code at the tail |
| AX | 84 | 110 to 120 V AC | voltage code at the tail |
| AX | 80 | 220 to 230 V AC 50 Hz | voltage code at the tail |
| AX | 88 | 230 to 240 V AC | voltage code at the tail |
| AX | 86 | 400 to 415 V AC | voltage code at the tail |
Key Features
AC-3 rating at 400 V in every row – the figure the motor current is checked against, not the AC-1 thermal rating that is two to three times higher.
Reversing pairs already assembled – the LC2D frame is two contactors with a mechanical interlock and the wiring fitted, so the forward and reverse coils cannot close together.
One body, several coils – 9 A to 50 A frames are ordered on 24 V DC for a PLC output or on 110 to 415 V AC from a control transformer, with the code in the part number.
Overload relay clips to the frame – the relay mounts under the contactor and its terminals line up with the main poles, so no extra wiring run is needed between the two.
Auxiliary blocks added on site – front and side contact blocks snap on without tools, which covers the extra interlock or lamp signal after the panel is assembled.
Screw or spring terminals – spring versions of the same frame exist for panels that are wired without a torque wrench, and the order code changes by one digit.
Applications
Motor starters are chosen by duty, not by panel size. Three patterns cover most of the enquiries we quote.
Pumps and fans on a 400 V supply – direct-on-line starting with a 9 A to 25 A contactor, a class 10 thermal relay and a 220 V AC coil from the control transformer.
Conveyors and doors that reverse – a matched reversing pair with a mechanical interlock, wired so the two coils cannot be energised at the same time.
Compressors and refrigeration racks – larger frames at 32 A to 50 A with EverLink terminals, because the cable lug and the terminal have to take the starting current without a re-torque.
Motor starters, contactors and panel parts are quoted with the board they drive, and the SUPERB PCBA and the SUPERB PCB are checked against the same motor schedule so the coil voltage, the overload range and the terminal size agree before the panel is wired.
Sourcing and Cross-Reference
Read the AC-3 current at the supply voltage first. A 7.5 kW motor at 400 V draws about 15.5 A, which lands between the 16 A and the 18 A frame, and the higher frame is the safe choice once the service factor is in the nameplate. Sizing from kW alone, without the FLC, is how a contactor ends up welded at the first stall.
Order the coil for the control source that exists. A 24 V DC coil on a 220 V AC control circuit will not pull in, and a 220 V AC coil driven from a PLC output will not pull in either. Where the panel has both, the DC coil with a wide range is the safer line because it tolerates a supply sag.
Keep the overload relay on the same frame family. The relay terminal spacing and the mounting foot follow the contactor, and a relay from another family needs an adapter that takes space in a 45 mm column. The relay range is set from the motor FLC, which is a separate decision from the contactor frame.
Delivery on these frames moves with the coil voltage rather than the current rating: the 24 V DC versions are the ones that go short, and a 110 V AC coil is often the faster line. See lead time and availability when the starter has to ship with the panel, and the cross reference hub when the original frame is no longer offered.
The SUPERB Assembly team mounts the contactors after the wire duct is fixed, because a contactor dropped in first blocks the duct clip and leaves the coil terminal facing the door hinge.
Q: Can you supply a contactor, the matching overload relay and the coil at the voltage we use, as one set?
A: Yes. Send the motor nameplate with kW, full load current and supply voltage, plus the coil voltage available in the panel, and the SUPERB Tech team returns the frame, the relay range and the auxiliary block that fit.
Why Builders Buy Contactors From SUPERB
- Set quoted, not single parts: the contactor, the coil code, the overload relay and the auxiliary block are checked against the same motor list before the quotation goes out.
- AC-3 current stated per part: the figure the motor is compared against is in the table, so the frame is not chosen from a kilowatt figure alone.
- Reversing pairs from stock or build: the interlocked pair is quoted as one item, which removes the wiring step and the risk of two coils closing together.
- Coil voltage confirmed before shipping: the coil code is repeated on the order acknowledgement, because a wrong coil is the most common reason a starter does not run on first power up.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, DIN Rail Terminal Blocks for Control Panel Wiring, DIN Rail Power Supplies for Control Cabinets, Hall Effect Current Sensors for Motor Monitoring.