Surge Protective Devices for Signal and Data Lines
Product Specifications
Product Overview
A signal line is a long antenna that ends at an input card. The cable runs from a field transmitter, through a duct, past a drive, and into an analogue input that may be rated for 30 V. A surge on that cable does not respect the 24 V nominal, and the input card is usually the cheapest part to replace and the most expensive part to lose, because the loop it controls stops with it. The protector goes at the boundary of the zone, not at the card.
The first choice is the operating voltage, not the discharge current. A 24 V loop with a 33 V module keeps working through the normal signal swing, the HART carrier and a modest supply tolerance. A 5 V module would clamp too early and a 60 V module would let the input see more than it is rated for. On a 4 to 20 mA loop the series resistance matters as much: one ohm per line is invisible to a 24 V supply with a 250 ohm sense resistor, ten ohms is not.
The second choice is the class of protection. A module with 10 kA per line at 10/350 can sit at the boundary between zone 0 and zone 1, where a direct lightning current is shared between several paths. A module with 5 kA at 8/20 is a fine protection part that goes next to the device, inside the same enclosure. Fitting a fine protection part at an outside boundary is the common mistake: the module survives nothing and the card still fails.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Nominal voltage | 24 V DC, with 5, 12, 48, 60 and 180 V in the same family | the module voltage follows the loop, not the power supply |
| Maximum continuous operating voltage | 33 V DC and 23.3 V AC on the 24 V part | 54 V DC on the 48 V part |
| Nominal current | 1.0 A at 45 C, 0.75 A on the lower current version | a 4 to 20 mA loop uses a fraction of this |
| Lightning impulse current, 10/350 | 10 kA total, 2.5 kA per line | D1 class, usable at a zone 0 to 1 boundary |
| Nominal discharge current, 8/20 | 20 kA total, 10 kA per line | C2 class |
| Voltage protection level, line to line | up to 52 V at the lightning impulse, 45 V at 1 kV per microsecond | compare with the input card rating |
| Voltage protection level, line to protective earth | up to 550 V | set by the gas discharge tube to earth |
| Series resistance | 1.0 ohm per line | fitted in series, so the loop current is unaffected at 20 mA |
| Cut off frequency | 7.8 MHz line to line | above this the module starts to attenuate the signal |
| Capacitance | 1.0 nF line to line, 16 pF line to protective earth | matters on a fast digital pair, not on a 4 to 20 mA loop |
| Connection | module plugs into a base on the rail, base carries the earth | a two piece construction, so the module can be changed with the loop in place |
| Degree of protection | IP20 with the module plugged in | the assembly sits inside an enclosure |
| Approvals | UL 497B, ATEX and IECEx for zone 2, SIL 3, CCC | hazardous area versions are the same body |
| Weight | 37 g | the base is a separate order line |
Included Models and Order Codes
The DEHN list is quoted by nominal voltage, and the order code carries the current and the class: BD is the version with a gas discharge tube to earth and a nominal current of 1.0 A at 45 C, BE is the lower current version without that path, and the numbers after BD are the voltage. The Phoenix PT range is quoted by line count and voltage, PT 2X2 for two floating two wire circuits and PT 4 for a four core circuit, and each plug needs its base element. Where a maker publishes a value for one version of the body and not another, the cell says so rather than carrying the figure across.
| Part number | Family | Nominal voltage | Max continuous voltage | Discharge current | Note |
|---|---|---|---|---|---|
| 920 344 (BXT ML4 BD 24) | DEHN BLITZDUCTOR XT | 24 V | 33 V DC / 23.3 V AC | 10 kA per line at 10/350, 10 kA per line at 8/20 | two pairs, 1.0 A at 45 C, LifeCheck status, 7.8 MHz |
| 920 324 (BXT ML4 BE 24) | DEHN BLITZDUCTOR XT | 24 V | 33 V DC / 23.3 V AC | per the family table | lower current version, 0.75 A, no gas discharge tube to earth |
| 920 345 (BXT ML4 BD 48) | DEHN BLITZDUCTOR XT | 48 V | 54 V DC | 10 kA per line at 10/350 | 1.0 A at 45 C, for 48 V control and signalling |
| 920 346 (BXT ML4 BD 60) | DEHN BLITZDUCTOR XT | 60 V | 70 V DC | per the family table | 1.0 A at 45 C |
| 920 347 (BXT ML4 BD 180) | DEHN BLITZDUCTOR XT | 180 V | 180 V DC | per the family table | 0.75 A, for telephone and legacy interfaces |
| 920 340 (BXT ML4 BD 5) | DEHN BLITZDUCTOR XT | 5 V | 6.0 V DC | 10 kA per line at 10/350 | for low level sensors and bus interfaces |
| 920 342 (BXT ML4 BD 12) | DEHN BLITZDUCTOR XT | 12 V | 15 V DC | per the family table | 1.0 A at 45 C |
| 920 300 (BXT BAS) | DEHN BLITZDUCTOR XT base | n/a | n/a | n/a | universal base part, the module plugs into it |
| 2838228 (PT 2X2-24DC-ST) | Phoenix Contact PT | 24 V DC | per the data sheet | 10 kA line to line at 8/20 | two floating two wire circuits, HART compatible, two piece construction |
| 2839240 (PT 4-24DC-ST) | Phoenix Contact PT | 24 V DC | per the data sheet | per the data sheet | one four core floating circuit, same base family |
| PT 2X2-BE | Phoenix Contact PT base | n/a | n/a | n/a | base element for the 2X2 plug, carries the rail contact |
Which Class Goes Where
The class of a signal protector is a statement about the surge it is built to survive, and it follows the zone concept rather than the price. Putting a fine protection part at an outside boundary is the most common reason a loop fails twice.
| Location on the plant | Class that fits | What it is asked to carry |
|---|---|---|
| Cable entry at the building wall, zone 0 to 1 | D1 class, 10 kA at 10/350 per module | a share of the lightning current, with the shield bonded at the same point |
| Between cabinets, zone 1 to 2 | C2 class, 10 to 20 kA at 8/20 | the induced surge on a long internal run |
| At the input card inside the enclosure | fine protection, 5 kA at 8/20 | the residual let through from the upstream stage |
| Field device in a hazardous area | Ex rated module, same body | the surge, without losing the zone 2 certification |
| Instrument loop with a HART carrier | 24 V module with a cut off above 1 MHz | the signal and the carrier, without loading the loop |
Key Features
Voltage chosen from the loop – 5 to 180 V in one family, so a 24 V loop gets 33 V of continuous rating and a 48 V circuit gets 54 V, instead of one part being asked to cover both.
Current and series resistance stated – 1.0 A and 1.0 ohm per line are the two figures that decide whether a loop still works after the module is fitted.
Cut off frequency published – 7.8 MHz line to line, so a fast digital pair and a slow analogue loop are not treated as the same application.
Two piece construction – the module plugs into a base that stays wired, which means a protector can be replaced during a shift without disturbing the loop.
Status indication – LifeCheck on the DEHN body reports a thermally overloaded module, so a spent protector is replaced rather than trusted.
Hazardous area and SIL versions – ATEX, IECEx and SIL 3 are the same body, so a loop in a zone 2 area does not need a different family.
Applications
Signal protectors are fitted for three kinds of line, and the choice of module follows from the line rather than from the panel.
4 to 20 mA transmitter loops – a pressure or level transmitter on a long cable shares a duct with drives, and a 24 V module with 1 ohm per line keeps the loop within its supply margin while clamping the surge at the cabinet entry.
RS-485 and Modbus runs between cabinets – the pair carries a common mode surge from one building to the next, and a module with 10 kA per line at the boundary keeps the transceiver from being the fuse.
HART and instrument interfaces in process plants – the carrier sits on the same pair as the loop current, so the protector has to pass the carrier, which is why the cut off frequency and the capacitance are on the page.
The loop lands on the control board, so the SUPERB PCBA and the SUPERB PCB are reviewed with the same surge path and the same earth bar as the protector.
Sourcing and Cross-Reference
A signal protector is ordered as a module plus a base, and the base is the part that carries the earth and the rail contact. Ordering the module alone is the usual way a panel gets to the test stage with nothing to plug into. On the DEHN side the universal base covers the whole ML family, and on the Phoenix side each plug has its own base element, so the pair is quoted together.
The second point is the loop, not the module. A protector with 1 ohm per line is invisible on a 24 V loop with a 250 ohm sense resistor, but a two wire transmitter with a 12 V minimum operating voltage and a 500 ohm load has little margin to give. Where the margin is thin, the lower resistance version or a different family is the right answer, and the figures above are there to make that visible before the loop is commissioned.
For retrofit work the holder and the wiring usually already exist, so the question is which module fits the base and which voltage the loop actually runs at. See lead time and availability for a specific module and obsolete part cross reference where an older protector has been withdrawn.
The SUPERB Assembly team bonds the base to the earth bar with a short conductor, because a long earth lead turns a good protector into a poor one.
Q: Can you confirm the series resistance and the clamping voltage of this module against our 24 V loop before we fit it?
A: Yes. Send the loop voltage, the signal type, the cable route and the zone, and the SUPERB Tech team returns the module and the base that fit.
Why Instrument Engineers Source Signal SPD From SUPERB
- Loop figures, not just surge figures: series resistance, capacitance and cut off frequency are on the page, because a protector that breaks the loop is not a protector.
- Class matched to location: D1, C2 and fine protection parts are separated with the zone they belong to, so the boundary device is not a card level part.
- Module and base quoted together: the base element is listed with the module, which is the pair that has to arrive at the same time.
- Hazardous area versions on the same list: ATEX and IECEx modules sit beside the standard ones, so a plant with zone 2 instruments does not need a second order.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Surge Protective Devices for AC Distribution Boards, Surge Counters and SPD Monitoring Units, DIN Rail Terminal Blocks for Control Panel Wiring, EMI Feedthrough Filters and Filter Connectors, Earthing Braids and Bonding Straps.