Surge Counters and SPD Monitoring Units
Product Specifications
Product Overview
A surge protective device is a wear item that fails safe and then looks exactly like a working one from the outside. The varistor inside has absorbed what it was bought to absorb, the disconnect has opened, and the only sign is a window that has turned from green to red on a device behind a closed door. Monitoring exists to move that information to somewhere a person looks: a lamp on the panel, a digital input on the PLC, or a page on a screen.
There are three levels of it and they are often confused. The first is a floating changeover contact inside the SPD, which reports one bit: the module has failed or it has not. The second is a counter, which records how many impulses above a threshold have passed through the device, so a site that sees twenty events a year is treated differently from one that sees two. The third is a bus interface, which reads the module, its part number and the part number of the replacement module, so maintenance can order the right plug-in module before anyone opens the cabinet.
The order of value is the reverse of the order of price. A contact costs almost nothing and answers the only question that matters on the day of a fault, whether the protection is still there. A counter answers the question a maintenance planner asks, how hard is this installation being hit. A bus interface answers the question a plant with forty cabinets asks, which of them needs a module this month. Most panels need the first, and the second and third are added where the downtime or the number of cabinets justifies them.
Key Specifications
| Signal path | Where it lives | Interface | Supply needed | What it reports |
|---|---|---|---|---|
| Status window | on the SPD module | none, read at the door | none | green or red, the module has failed or it has not |
| Floating changeover contact | inside the SPD, FM version | one dry changeover contact, 250 V at 0.5 A AC | from the SPD | one bit, protection present or lost |
| Impulse counter | inside a panel SPD or as a separate unit | local display, or a pulse output to a counter | from the SPD or the panel | number of impulses above the threshold, not their energy |
| Remote signalling bus | separate DIN rail unit | Modbus RTU or Modbus TCP | 11 to 28 V DC, 600 mW | status, device part number and replacement module numbers |
| LifeCheck reader | separate DIN rail unit | RS485 to the bus unit, RFID at 125 kHz | 18 to 48 V DC, 100 mA | status of up to 10 arresters per reader |
| Multi device interface | separate DIN rail unit, pre-wired | Bluetooth, Ethernet and WiFi | from the panel | up to 40 arresters on one interface |
Included Models and Order Codes
The parts below are the SPDs that carry a monitoring contact in the base, which is the cheap half of the system. The FM suffix is the marker: it means a floating changeover contact is wired out to terminals, and that contact is what a PLC input or a lamp reads. The contact ratings are modest on purpose, 250 V at 0.5 A AC and 0.1 A at 250 V DC, because it is a signalling contact and not a switching device.
| Part number | Type | SPD class | In and Imax | Up | Modules | Signal |
|---|---|---|---|---|---|---|
| 952 305 | DEHNguard DG M TNC 275 FM | type 2 | 20 kA and 40 kA | 1.5 kV or less | 3 | floating changeover contact |
| 952 308 | DEHNguard DG M TNC 440 FM | type 2 | 20 kA and 40 kA | 2 kV or less | 3 | floating changeover contact |
| 952 115 | DEHNguard DG M TT 2P 275 FM | type 2, 1 plus 1 | 20 kA and 40 kA, 12 kA N to PE | 1.5 kV or less | 2 | floating changeover contact |
| 953 205 | DEHNrail DR M 2P 255 FM | type 3 | 3 kA, 5 kA total | 1.25 kV or less | 1 | floating changeover contact |
| 942 405 | DEHNguard DG MP TNS 275 FM | type 2 plus type 3 | 20 kA and 40 kA | 1.5 kV or less | 4 | floating changeover contact, push in terminals |
Units That Read the Contact or Replace It
Where more than one bit is needed, a separate unit sits on the same rail and does the reading. The two DEHN modules work as a pair, one reader per ten arresters and one bus unit per cabinet, and the third entry is a pre-wired interface for panels that already have a row of SPDs with contacts.
| Part number | Unit | Interface | Supply | Capacity |
|---|---|---|---|---|
| 910 694 | DEHNrecord Alert DRC AL MODBUS | Modbus RTU and TCP, RJ45 and RS485 | 11 to 28 V DC, 600 mW | 4 remote contacts plus up to 150 arresters through readers |
| 910 698 | DEHNrecord DRC MCM AL XT | RS485, RFID at 125 kHz | 18 to 48 V DC, 100 mA | 10 LifeCheck arresters per reader |
| AIMCB | LPI alarm interface module | Bluetooth, Ethernet, WiFi | pre-wired from the panel | up to 40 surge protective devices |
Key Features
One bit that answers the only urgent question – a floating changeover contact reports that the protection has been lost, which is the state that has to reach a PLC input or a lamp before the next storm rather than after the next failure.
Contact ratings that suit a PLC – 250 V at 0.5 A AC and 0.1 A at 250 V DC on the signalling contact, so a 24 V input card can read it directly without an interposing relay.
Counter records the number of events – a counter is what separates a site hit twice a year from one hit twenty times, and that difference is the argument for a larger arrester or a second stage.
Bus unit reports part numbers – the Modbus unit reads the device and the replacement module number, so the maintenance order is placed from a screen rather than from a photograph of a label.
Reader per ten arresters – the LifeCheck reader covers ten arresters over RS485 and the bus unit covers fifteen readers, which is how a cabinet with several rows stays on one interface.
Everything on 35 mm rail – from a one module SPD to a pre-wired interface for forty devices, the mounting is the same rail, so monitoring can be added to a panel that was built without it.
Applications
Monitoring is bought for the failure mode it prevents, not for the data it produces. These three are the cases we see most.
Remote cabinets and telecom sites – a changeover contact wired to a telemetry input turns a site visit into a dispatch, and the counter tells the operator whether the site is being hit by the supply or by the tower.
Washdown and outdoor panels – where the SPD is behind a sealed door, the status window is useless and the contact on the rail is the only way to know the module has been used up.
Plants with many cabinets – a bus unit per cabinet and one screen for the plant replaces the round of door openings, and the replacement module number arrives with the alarm rather than after it.
The monitoring contact is quoted with the board that reads it, so the SUPERB PCBA and the SUPERB PCB are checked against the same input card and the common of the contact agrees with the input common.
Sourcing and Cross-Reference
Decide the level first, because it changes the whole bill. If the panel needs a lamp and a PLC bit, an SPD with an FM base is the cheapest complete answer and nothing else is required. If the panel needs a record, the counter has to be either inside the SPD or a separate unit reading a pulse, and the two are not interchangeable in what they can report.
Then check the compatibility of the pair. The bus units read a specific family of arresters, and a reader that expects a LifeCheck module will not report a plain contact. Where a panel already has SPDs from another maker, the practical route is a contact input rather than a bus, because a contact is a contact and the bus is not.
Finally, check the supply and the terminals. The bus unit runs on 11 to 28 V DC at 600 mW, the reader on 18 to 48 V DC at 100 mA, and both land on 2.5 mm2 screw terminals, so a monitoring retrofit needs a small DC supply and a pair of wires rather than a new panel. See lead time and availability when the arrester family is short, and cross reference support when a discontinued module has to be replaced.
The SUPERB Assembly team keeps the changeover contact on its own pair of terminals rather than sharing a return, because a shared return turns two monitored SPDs into one alarm.
Q: Can you supply the arresters and the monitoring unit as one set, so the contact wiring and the bus address are settled before the panel is built?
A: Yes. Send the arrester family already on the panel and whether the requirement is a lamp, a counter or a bus record, and the SUPERB Tech team returns the unit and the wiring that fit.
Why Panel Builders Buy Monitoring From SUPERB
- Level stated up front: each part is marked as a contact, a counter or a bus unit, so a panel does not end up with a contact where a record was needed.
- Contact ratings in the open: the signalling contact is quoted with its AC and DC ratings, which is what decides whether it can go straight to a PLC input.
- Capacity per unit: modules, arresters per reader and devices per interface are written per part, so the bill of material is sized rather than guessed.
- Rail and width consistent: one module to four modules on 35 mm rail, so monitoring fits the space left beside the arresters.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Surge Protective Devices for AC Distribution Boards, Digital Panel Meters and Counters for Control Panels, DIN Rail Power Supplies for Control Cabinets, Phase Failure and Voltage Monitoring Relays, DIN Rail Terminal Blocks for Control Panel Wiring.