Earthing Braids and Bonding Straps
Product Specifications
Product Overview
A door on a painted cabinet is not bonded to the frame by its hinge. Paint, a gasket and a stainless pin leave a path that is fine at DC and useless at 100 MHz, so the door needs a braid from the door stud to the frame stud. The same applies to a mounting plate on standoffs, a filter housing, and any panel that carries a connector shell.
A braid is not a cable with a lug crimped on. The good ones are pressed into a solid palm in one operation, so the copper is continuous from wire to palm and there is no crimp interface to corrode. That is the reason a braid has lower impedance than the same cross section of insulated cable at high frequency: the current has more surface and no round conductor bundle to skin.
Two numbers go on the order: the cross section and the distance between the two studs. The cross section is set by the fault current and the length, not by the stud size, and the length has to allow the door to open through its full swing without the braid going tight. A braid that is pulled straight at 90 degrees will fail at the palm after a few thousand cycles.
Key Specifications
| Property | Range | Notes |
|---|---|---|
| Cross section | 6 to 100 mm2 | 6, 10, 16, 25, 35, 50, 70 and 100 mm2 in the standard range |
| Length | 100 to 500 mm | longer lengths to order |
| Palm hole | M6, M8, M10, M16 | hole size follows the stud, not the cross section |
| Current | 40 to 349 A | per maker table, by cross section |
| Material | tinned copper | pressed palm, no crimped lug |
| Temperature | -20 to +125 C | for the tinned copper braid family |
Included Models and Order Codes
The nVent MBJ codes read as cross section, then length, then palm: MBJ16-200-8 is 16 mm2, 200 mm long, with an 8 mm hole. Rittal uses a plain six or seven digit code, and the length is the last three digits. Current figures are the maker values for the braid alone, before any derating for a hot enclosure.
| Part number | Cross section | Length | Palm hole | Current |
|---|---|---|---|---|
| MBJ6-150-6 | 6 mm2 | 150 mm | M6 | 40 A |
| MBJ16-200-8 | 16 mm2 | 200 mm | M8 | 120 A |
| MBJ25-300-10 | 25 mm2 | 300 mm | M10 | 150 A |
| MBJ35-300-10 | 35 mm2 | 300 mm | M10 | 197 A |
| MBJ50-300-10 | 50 mm2 | 300 mm | M10 | 250 A |
| MBJ70-300-10 | 70 mm2 | 300 mm | M10 | 290 A |
| MBJ100-500-16 | 100 mm2 | 500 mm | M16 | 349 A |
| 2412210 | 10 mm2 | 200 mm | M6 to M6 | on maker table |
| 2412316 | 16 mm2 | 300 mm | M8 to M8 | on maker table |
| 2412225 | 25 mm2 | 200 mm | M8 to M8 | on maker table |
| CTX-16/300/M8 | 16 mm2 | 300 mm | M8 | on maker table |
Bonding Points That Are Usually Missed
A cabinet is bonded at more than the door. The table lists the points that come up in an EMC or an inspection check, with the size that is normally used.
| Bonding point | Typical braid | Reason |
|---|---|---|
| Door to frame, small cabinet | 6 or 10 mm2, 200 mm | short run, door swings 120 degrees |
| Door to frame, 1800 mm cabinet | 16 mm2, 300 mm | longer swing, heavier door |
| Mounting plate to frame | 16 mm2, 200 mm | plate sits on standoffs, no metal contact |
| Filter or gland plate to frame | 25 mm2, 200 mm | paint under the plate, HF path needed |
| Busbar support to earth bar | 50 or 70 mm2, 300 mm | fault current path |
| RF module housing to chassis | 6 mm2, 100 mm | short, low inductance run |
Key Features
Pressed palm, no crimp – the copper runs from the braid into the palm in one piece, so there is no crimp interface to oxidise under a door that moves.
Cross sections from 6 to 100 mm2 – the range covers a door bond and a busbar earth with the same family, which keeps the earthing schedule short.
Hole size independent of section – a 16 mm2 braid is available with an M6 or an M8 palm, so the braid is chosen on current and the palm on the stud.
Tinned copper – the braid does not go green in a humid cabinet, and the palm keeps a low resistance after years on a door.
Flexible for a door that moves – a braid takes the bend at a larger radius than a cable and does not work harden at the palm the way a stranded cable does.
Lengths to 500 mm – long enough for a 1800 mm door with a bottom-mounted stud, without a joint.
Applications
Bonding is specified by the fault path and by the EMC requirement, and the two do not always ask for the same part. Three cases.
Cabinet doors with a filter or a drive – a 16 or 25 mm2 braid from the door to the frame, short and wide, so the HF current from the drive does not run through the hinge.
RF and instrument housings – a short 6 mm2 braid from a module housing to the chassis, kept under 100 mm to hold the inductance down.
Switchgear with a high fault level – a 50 or 70 mm2 braid from the busbar support to the earth bar, sized on the fault current rather than on the stud.
Braids and straps are quoted against the earthing schedule of the cabinet, and both the SUPERB PCBA and the SUPERB PCB are checked against the same bonding plan so the stud, the palm and the bolt size agree before the panel is wired.
Sourcing and Cross-Reference
Size on the fault current and the length, not on the stud. A 16 mm2 braid on an M8 stud is normal; a 16 mm2 braid for a 25 kA fault is not. The maker current in the table is a continuous figure, so the fault case needs the switchgear schedule, not the braid table.
Allow slack for the swing. The braid should be at about two thirds of its length when the door is closed, so it is not tight at 90 degrees. A braid that is tight at the open position pulls the palm off the stud.
Bond after painting, on bare metal. A star washer between the palm and the paint is not a bond. The paint has to be removed at the stud, and the joint protected afterwards, or the braid measures open at the next inspection. See obsolete part cross reference when a cabinet is rebuilt and the original braid length is no longer made.
Keep the door braid and the door stay apart. The stay takes the mechanical load and the braid takes the current; a braid used as a door limit fails at the palm within a few months.
The SUPERB Assembly team fits the braid after the door is hung and the paint is touched up, because a braid fitted to bare metal before painting has to come off again to keep the bonding point conductive.
Q: Can you supply a braid in a non standard length with the palm hole we need at each end?
A: Yes. Send the stud size, the cross section and the distance between the two fixing points; the SUPERB Tech team quotes a braid in that length and palm size rather than the nearest stock item.
Why Builders Buy Earthing Braids From SUPERB
- Section, length and palm all in the quote: the three figures are confirmed together, so the braid arrives with the right stud size and enough slack for the swing.
- Pressed palm construction: no separate lug and no crimp interface, which is the part that fails on a door that opens every shift.
- Tinned copper throughout: the braid stays conductive in a humid or a wash-down cabinet.
- Sizes for both the fault path and the EMC path: 6 mm2 for a module housing, 70 mm2 for a busbar support, from the same range.