Split Core Current Transformers for Retrofit Metering

A split core transformer clamps around a cable that is already installed, so a metering point is added without cutting the conductor. The family runs from 200 A through a 0.75 inch opening to 3000 A through a 3 inch opening. Output is 0.333 V AC at rated current, which is a voltage signal that does not need a shorting switch. Accuracy is plus or minus 1 percent from 10 to 130 percent of rated current, class 1.0 to IEC 61869-2 on the larger frames.
quote now

Product Specifications

Product Overview

A retrofit metering job has one constraint that a new panel does not: the cable is already there and the plant will not be shut down to cut it. A split core transformer opens on a hinge, clamps around the conductor and closes with a self locking catch, so the measurement is added during a short outage or with the feeder isolated at the upstream breaker only. The trade is that the joint decides the accuracy, which is why the interleaving of the two core halves matters more than the catalogue class.

The output is a voltage, not a current. At rated current the secondary gives 0.333 V AC, and at 50 percent load it gives about 0.167 V. That changes the wiring: there is no 5 A loop to short, no open circuit hazard and no shorting terminal block. It also changes the reading: the meter input impedance has to be high enough that the transformer is not loaded down, and long leads have to be twisted pair to keep noise out of a signal that is only a third of a volt.

The frames differ in opening and in the joint. A 0.75 inch opening takes a single conductor and is the usual choice for a sub meter or a small feeder. The 1.25 inch frame goes to 800 A, the 2 inch frame to 1500 A, and the 3 inch frame to 3000 A, where the phase conductor is a busbar or a large parallel set. On the larger frames the maker quotes class 1.0 to IEC 61869-2 and a phase displacement under 0.2 degrees at rated current, which is what a power measurement with a power factor correction check needs.

Key Specifications

ParameterValueNote
Typesplit core AC current transformer, hinged, self lockingclamps on an installed conductor
Rated primary currentup to 200, 800, 1500 or 3000 Aby frame, custom ratings on request
Rated output0.333 V AC at rated currentproportional from zero to rated current
Accuracyplus or minus 1 percent from 10 to 130 percent of rated currentclass 1.0 to IEC 61869-2 on the 1500 and 3000 A frames
Phase displacementunder 2 degrees at rated current, under 0.2 degrees on the 3000 A framemeasured per maker sheet
Frequency30 Hz to 1000 Hz on the 750 frame, 50 to 400 Hz on the larger framesper frame
Insulation600 V on the primary conductorinsulation test 3800 V AC for one minute on the 1500 A frame
Leads8 ft, 22 AWG twisted pair, 2.4 m600 V lead rating
Operating temperatureminus 20 to plus 75 C, minus 20 to plus 70 C on the 1500 A frameUL rated ambient 55 C on the larger frames
Storage temperatureminus 40 to plus 90 Cper maker sheet
Meter input impedance75 kOhm minimum on the 1500 A framea lower impedance loads the secondary and shifts the reading
ApprovalsUL 61010-1, EN 60044-1, UL recognised file E96927, CE, RoHSper frame
Mountingclamped around the conductor, no fixing holes requiredcable tie or bracket for strain relief on long leads
Shorting switchnot requiredthe output is a voltage, an open secondary is not a hazard

Included Models and Order Codes

The frames are named by the opening, and the opening decides the current and the joint quality. SCT-0750 has a 0.75 inch window and takes up to 200 A, with a 30 Hz to 1 kHz range and a phase angle under 2 degrees above 70 A, which makes it the frame for sub meters and small feeders. SCT-1250 has a 1.25 inch window to 800 A, with 50 to 400 Hz and the same 1 percent linearity. SCT-2000 opens to 2 inches for up to 1500 A, quotes class 1.0 to IEC 61869-2, a 3800 V AC insulation test for one minute and a minimum meter impedance of 75 kOhm. SCT-3000 opens to 3 inches for up to 3000 A and is the frame where the phase displacement falls below 0.2 degrees, which matters when the measurement feeds a power factor or an energy balance calculation.

FamilyRated primaryOpeningAccuracy and phaseFrequency
SCT-0750up to 200 A0.75 inchplus or minus 1 percent, phase under 2 degrees above 70 A30 Hz to 1000 Hz
SCT-1250up to 800 A1.25 inchplus or minus 1 percent, phase under 2 degrees at rated50 to 400 Hz
SCT-2000up to 1500 A2 inchclass 1.0 to IEC 61869-2, phase under 2 degrees50 to 400 Hz
SCT-3000up to 3000 A3 inchclass 1.0 to IEC 61869-2, phase under 0.2 degrees50 to 400 Hz
SCT-1250-300300 A1.25 inchplus or minus 1 percent50 to 400 Hz
SCT-2000-10001000 A2 inchclass 1.0 to IEC 61869-250 to 400 Hz

Output Voltage at Part Load

A 0.333 V transformer is linear, so the output is simply the rated voltage multiplied by the fraction of rated current. The table gives the figure at the load points that appear in most metering checks, calculated as 0.333 V times the current divided by the rated current. It matters at the low end: a 1000 A frame carrying 50 A gives 16.7 mV, and at that level the lead length and the meter resolution decide whether the reading is usable, not the transformer class.

Load as percent of ratedOutput at 0.333 V ratedOutput on a 1000 A frame
100 percent0.333 V0.333 V at 1000 A
75 percent0.250 V0.250 V at 750 A
50 percent0.167 V0.167 V at 500 A
25 percent0.083 V0.083 V at 250 A
10 percent0.033 V0.033 V at 100 A
5 percent0.017 V0.017 V at 50 A

Key Features

Clamps on an installed cable – the core opens and closes with a self locking catch, so a metering point is added without cutting the conductor or opening the feeder.

Voltage output, no shorting switch – 0.333 V at rated current removes the 5 A loop, the shorting terminal block and the open secondary hazard from the retrofit.

Openings from 0.75 to 3 inch – four frames cover a single control cable through to a busbar or a parallel conductor set, so the opening is chosen before the current.

Accuracy stated over the load range – plus or minus 1 percent from 10 to 130 percent of rated current, rather than a single figure at full scale.

Class 1.0 on the large frames – the 1500 A and 3000 A frames quote class 1.0 to IEC 61869-2, with phase displacement below 0.2 degrees on the largest.

Insulation and lead rating given – 600 V on the primary conductor, 3800 V AC test for one minute on the 1500 A frame, and 600 V rated twisted pair leads.

Meter impedance stated – the 75 kOhm minimum on the 1500 A frame is the number that decides whether a cheap meter reads low at part load.

Temperature range per frame – minus 20 to plus 75 C on the small frames and minus 20 to plus 70 C on the large one, with a UL rated ambient of 55 C.

Applications

Three retrofit jobs where the conductor cannot be cut and the frame is chosen from what is already in the tray.

Energy monitoring added to an existing board – the transformer clamps around each feeder in a live board, and the meter is wired in twisted pair without a shorting terminal block.

Sub billing in a rented building – a 0.75 inch frame on each tenant feeder gives a voltage signal that a small meter can read, with no interruption to the tenant supply.

Load study on a busbar – a 3 inch frame clamps around the busbar or the parallel set, and the class 1.0 accuracy is what makes the load balance calculation worth doing.

A retrofit kit often ships with a small interface board, so the SUPERB PCBA and the SUPERB PCB are checked against the same transformer list and the lead termination is reviewed once for both.

Sourcing and Cross-Reference

The first question is the opening, because it cannot be changed later. A 0.75 inch frame will not close around a 240 mm2 cable with a gland, and a 3 inch frame around a 16 mm2 conductor reads with more error than the class suggests. The second question is the rated current: a frame run at 20 percent of rating is inside its accuracy band but close to the resolution limit of a small meter.

The third question is the meter. A 0.333 V output needs an input impedance of at least 75 kOhm on the 1500 A frame and twisted pair leads. A meter with a 5 A input needs a different transformer, not an adapter, because the signal level and the burden are a different problem.

Where a frame is not in the catalogue, the same opening with a custom rated current is the usual route, since the core and the catch stay. See lead time and availability for a specific rating, and how to verify a drop in replacement where a meter is being matched to a new transformer.

The SUPERB Assembly team closes the core on a clean conductor and twists the lead pair to the meter terminal, because a loose joint on a split core shows up as a slow drift rather than a dead reading.

Q: Can you confirm the opening size against our cable diameter and the meter input impedance, because we need the reading to hold at part load rather than only at full scale?

A: Yes. Send the conductor diameter, the rated current, the meter input type and impedance, the lead length and the ambient temperature, and the SUPERB Tech team returns the frame and the rating that fit.

Why Metering Retrofit Teams Source Split Core Transformers Through SUPERB

  1. Opening and current quoted together: each frame is listed with its window and its rated current, so a cable that fits is not assumed to be a cable that reads correctly.
  2. Part load accuracy stated: the 10 to 130 percent band is given with the class, which is where a retrofit reading is actually taken.
  3. Meter impedance named: the minimum input impedance for the large frame is part of the offer, because it is the usual reason a new transformer reads low.
  4. Lead and insulation data included: lead length, lead rating and the insulation test voltage are listed, so the secondary run is checked before the cable is pulled.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Metering Current Transformers for Panel and Switchgear, Rogowski Coil Current Sensors for Retrofit Metering, Protection Current Transformers for Overcurrent Relays, Multifunction Power Meters and Power Quality Analyzers, CT Test Terminal Blocks and Shorting Links, How to Verify a Drop in Replacement.