Soft Starters for Motor Starting

Soft starters from 17 A to 250 A rated current, covering 7.5 kW to 132 kW motors at 400 V. Built-in bypass on the Altistart 22 range removes the heat of a running thyristor stack from the enclosure. Current limit, ramp up and ramp down are set on the front, with motor overload protection inside the device. Siemens SIRIUS 3RW40 sizes are listed alongside, because the panel may standardise on either family.
quote now

Product Specifications

Product Overview

A soft starter reduces the voltage at the motor terminals during run up, so the current the supply sees is lower than a direct on line start. It does not change the speed while the motor is running; that is the job of a drive. The choice between the two is made by the process, not by the price: a pump that must not surge needs a ramp, and a conveyor that must run at a set speed needs a drive.

The two numbers that select the frame are the motor full load current and the starting duty. A 22 kW motor at 400 V draws about 42 A, so the 47 A frame is the usual match for a normal start. A high inertia load, a loaded conveyor or a compressor with a long run up pushes the frame up one size, because the thyristors carry the starting current for longer and the thermal capacity of the device is what limits the start.

A built-in bypass matters in a sealed cabinet. Once the motor is at speed the bypass contactor takes over and the thyristors stop conducting, so the heat loss inside the enclosure drops to the contactor loss. Without a bypass the same starter dissipates several times more heat at full load, and the cabinet cooling has to be sized for it.

Key Specifications

FamilyRated currentMotor power at 400 VBypassControlProtection
Altistart 22, D frames17 to 88 A7.5 to 45 kWbuilt in230 V AC control, 230 to 440 V powermotor overload, phase loss, thyristor over temperature
Altistart 22, C frames110 to 250 A55 to 132 kWbuilt in230 V AC control, 230 to 440 V powermotor overload, phase loss, thyristor over temperature
SIRIUS 3RW40, size S012.5 A5.5 kWbuilt in24 V DC or 230 V ACmotor overload, intrinsic device protection
SIRIUS 3RW40, size S2 and S345 to 106 A22 to 55 kWbuilt in24 V DC or 230 V ACmotor overload, intrinsic device protection

Included Models and Order Codes

The Altistart 22 tables give the motor current and the starter current side by side, and the gap between them is the margin the frame carries. The Q suffix is the 230 V control version with a 230 to 440 V power circuit. Ramp up and ramp down are set on the front, and the initial voltage is adjustable, so a motor that is already turning when the start is given does not see a step. On the Siemens 3RW40 the rated current is given at 40 C, and it derates at 50 C and 60 C, which matters inside a closed cabinet.

Part numberRated currentMotor 230 VMotor 400 VMotor 440 VNote
ATS22D17Q17 A4 kW7.5 kW7.5 kWmotor FLA 14.8 A
ATS22D32Q32 A7.5 kW15 kW15 kWmotor FLA 28.5 A
ATS22D47Q47 A11 kW22 kW22 kWmotor FLA 42 A
ATS22D62Q62 A15 kW30 kW30 kWmotor FLA 57 A
ATS22D75Q75 A18.5 kW37 kW37 kWmotor FLA 69 A
ATS22D88Q88 A22 kW45 kW45 kWmotor FLA 81 A
ATS22C11Q110 A30 kW55 kW55 kWmotor FLA 100 A
ATS22C14Q140 A37 kW75 kW75 kWmotor FLA 131 A
ATS22C17Q170 A45 kW90 kW90 kWmotor FLA 162 A
ATS22C21Q210 A55 kW110 kW110 kWmotor FLA 195 A
ATS22C25Q250 A75 kW132 kW132 kWmotor FLA 233 A
3RW4024-1BB0412.5 A at 40 C3 kW5.5 kW7.5 hp at 460 Vsize S0, 24 V DC control
3RW4036-1BB0445 A at 40 C11 kW22 kWon requestsize S2, 42 A at 50 C
3RW4046-1BB0480 A at 40 C22 kW45 kWon requestsize S3, 73 A at 50 C

Starting Current and the Frame That Carries It

The setting that decides the start is the current limit, expressed as a multiple of the motor full load current. The table below shows what each setting does on a normal four-pole motor, and where the frame stops being able to hold the limit for the whole run up. A ramp that is set too short is the same as raising the limit, so the two settings are always adjusted together.

Current limitTypical run upWhat the supply seesWhen it is used
250 percent of FLCshortclose to a direct on line startfree running fan or pump with low inertia
350 percent of FLCmediumreduced start, still a visible dippump with a check valve, small conveyor
400 percent of FLClongerhigher start torque for the same timeloaded conveyor, positive displacement pump
450 percent and abovelongestcheck the frame rating before orderinghigh inertia load, only after the duty is confirmed

Key Features

Built-in bypass – the thyristors stop conducting when the motor reaches full speed, so the heat in the cabinet is the contactor loss rather than the stack loss.

Adjustable current limit – the start current is capped at a multiple of the motor full load current, which keeps the supply dip inside the allowance the utility gives.

Ramp up and ramp down – a pump stop is a ramp, not a drop, so the non-return valve does not slam and the pipe does not see the surge.

Motor overload inside the device – the thermal model follows the set current, so a separate overload relay is not needed in the starter column.

Phase loss and sequence check – a lost phase or a reversed supply is detected before the start, which protects the thyristors from a single phasing run.

Coil and control on one voltage – the Q version takes a 230 V AC control supply, matching the control transformer that already feeds the contactors.

Applications

Soft starting is chosen where the supply or the pipe cannot take the step. Three duties cover most of the enquiries we quote.

Pumps on a weak supply – the ramp removes the pressure surge at start and stop, and the current limit keeps the voltage dip inside the supply allowance.

Conveyors with a loaded belt – a longer ramp and a higher current limit bring the belt up without slipping, and the frame is checked against the run up time.

Fans and compressors on a sealed cabinet – the built-in bypass keeps the enclosure heat low, so the cooling unit can be smaller than a drive would need.

The starter is quoted with the control board that commands it, so the SUPERB PCBA and the SUPERB PCB are checked against the same ramp settings and the relay output that gives the run signal.

Sourcing and Cross-Reference

Read the motor nameplate for full load current, then check the starter current against it. The Altistart tables show both, and the gap between them is the margin. A 30 kW motor at 400 V draws about 57 A, which sits on the 62 A frame, and the same motor on a high inertia load moves to the 75 A frame.

Ask what the supply allows during a start. A 400 percent limit on a 250 kVA transformer is a different event from the same limit at the end of a long cable, where the cable impedance adds its own drop. Where the utility has given a dip allowance, the current limit is set from that figure and the ramp is adjusted until the motor reaches speed inside it.

Check the cabinet heat before choosing a starter without a bypass. While the stack conducts it dissipates heat in proportion to the motor current, and on a sealed enclosure that loss stays inside: a fan and a filter only move it around. On a cabinet without a cooling unit the bypass version is the one that keeps the internal temperature inside the rating on a hot day.

Lead time on the C frames moves with the current rating rather than with the voltage. See lead time and availability for the position today, and the power management cross reference when the frame on the drawing is no longer offered.

The SUPERB Assembly team leaves the clearance above the starter that the maker specifies, because a stack that cannot breathe derates and trips on a hot afternoon.

Q: Can you supply the soft starter sized on our motor nameplate, with the bypass and the control voltage of our panel?

A: Yes. Send the motor nameplate with kW, full load current and supply voltage, the starting duty and the control voltage in the panel, and the SUPERB Tech team returns the frame and the settings.

Why Panel Builders Buy Soft Starters From SUPERB

  1. Sized from the nameplate: the motor full load current and the duty are checked against the starter current, not against the kilowatt figure alone.
  2. Bypass stated: whether the heat stays in the cabinet is in the table, so the cooling is sized on the right loss.
  3. Control voltage on the code: the Q suffix and the Siemens control suffix are both spelled out, so the coil matches the control transformer.
  4. Duty table for the ramp: the current limit table shows what the supply sees at each setting, which is the figure the utility allowance is compared against.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, IGBTs and SiC Power Devices for Motor Drives, Power Distribution Blocks for Panel Feeds.