Signal Isolators and 4-20 mA Converters for Panel Signals
Product Specifications
Product Overview
A 4-20 mA loop carries the measurement and the power on the same two wires, which is efficient and also the reason the loop is fragile. A ground difference between a sensor mounted on a machine frame and a control cabinet 60 m away drives a current through the loop that adds to the signal, and a fast transient on the machine couples into the same cable. A signal isolator puts a transformer or an optocoupler barrier in the loop and removes both problems.
The barrier is described by how many paths it separates. A 2-way isolator separates input from output. A 3-way isolator also separates the auxiliary supply, which is what a DIN rail part normally needs because its 24 V comes from the panel and its input comes from the field. A 4-way isolator adds a second output that is isolated from the first, used where a signal goes to a PLC and to a chart recorder that must not share a common.
Configuration is the second decision. A fixed part takes one signal and gives one signal, which is cheap and cannot be mis-set. A configurable part takes 0 to 10 V, 0 to 20 mA or 4 to 20 mA on the input and gives any of those on the output, set by DIP switches, and one stock item then covers thirty six combinations. A panel that carries spares usually prefers the configurable part, and a machine that is built in volume uses the fixed part.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Input signals | 0 to 20 mA, 4 to 20 mA, 0 to 10 V, 0 to 5 V, 1 to 5 V, 2 to 10 V | configurable parts cover all of them by DIP switch |
| Output signals | 0 to 20 mA, 4 to 20 mA, 0 to 10 V, 0 to 5 V | one or two outputs depending on the part |
| Isolation | 3-way between input, output and supply, 4-way on duplicator parts | the supply is separated as well |
| Test voltage | 1.5 kV for 1 min, or 2 kV rated insulation | per part, stated on the row |
| Accuracy | 0.1 percent of final value | 0.4 percent without adjustment on the configurable part |
| Step response | 0.5 ms fixed part, 3.2 ms configurable part | 10 to 90 percent |
| Cut off frequency | about 100 Hz on the configurable part | 3 dB |
| Supply | 19.2 to 30 V DC, nominal 24 V | through the rail connector or a terminal pair |
| Power consumption | 0.6 W to 1.8 W per channel | counts in the panel heat load |
| Load impedance | 250 to 550 ohm on the current output | check against the receiving input |
| Width | 6.2 mm or 12.5 mm | 6.2 mm on the mini range, 12.5 mm on the ACT20P range |
| Mounting | 35 mm DIN rail to EN 60715 | screw or spring cage terminals |
| Operating temperature | -20 C to +60 C | class A product, EMC declaration applies |
| HART | pass through, 0.5 to 2.5 kHz | the digital signal is not converted |
Included Models and Order Codes
The part number carries the function: UI means a universal input, I is a current output, 2I is two current outputs, and the NC or SP suffix is the terminal style, screw or spring cage. The 2864 and 2865 groups are the 6.2 mm mini range, and the 77600541 group is the 12.5 mm wide range with a higher isolation voltage.
| Part number | Type | Input to output | Isolation | Width | Note |
|---|---|---|---|---|---|
| 2864150 MINI MCR-SL-UI-UI-NC | configurable isolator | universal to universal | 3-way, 1.5 kV | 6.2 mm | 36 combinations by DIP switch, screw terminals |
| 2864163 MINI MCR-SL-UI-UI-SP-NC | configurable isolator | universal to universal | 3-way, 1.5 kV | 6.2 mm | same part with spring cage terminals |
| 2864176 MINI MCR-SL-UI-2I-NC | signal duplicator | universal to 2 current outputs | 4-way | 6.2 mm | one input to two isolated loops, 250 ohm load |
| 7760054114 ACT20P-CI-CO-S | current isolator | 0 or 4 to 20 mA to 0 or 4 to 20 mA | 3-way, 2 kV | 12.5 mm | 0.5 ms step response, 550 ohm load, HART |
| 7760054115 ACT20P-CI-2CO-S | current duplicator | 0 or 4 to 20 mA to 2 current outputs | 4-way, 2 kV | 12.5 mm | two isolated loops, 300 ohm load each |
Two Wire, Three Wire and Four Wire Sensors
The number of wires on the sensor decides whether the isolator has to supply the loop, and getting this wrong is the usual reason a new isolator reads zero. The table below is the wiring in the terms used on the data sheets.
| Sensor | Wires | Who powers the loop | Isolator setting |
|---|---|---|---|
| Two wire transmitter | 2 | the isolator, through the loop | input as active source, sensor supply on |
| Three wire transmitter | 3 | the isolator, separate supply and signal | input as three wire, common return |
| Four wire transmitter | 4 | the sensor has its own supply | input as passive, no sensor supply |
| Loop powered indicator | 2 | the control system | passive input, isolator does not feed |
| Valve positioner | 2 | the control system | passive input, HART must pass through |
Key Features
Supply isolated as well – the 3-way barrier separates the 24 V rail from the field loop, which is the path that a ground difference actually uses in a panel.
Two isolated outputs – the duplicator parts feed a PLC and a recorder from one sensor without joining their commons, which removes a loop that reads differently on two devices.
Configurable by DIP switch – one stock item covers 36 combinations of voltage and current, so a service van does not need six part numbers.
0.5 ms step response – the fixed current parts follow a fast pressure or torque signal, which matters on a closed loop rather than on a temperature loop.
HART pass through – the digital signal on top of the 4-20 mA is not filtered out, so a HART configurator still reaches the transmitter through the barrier.
6.2 mm width – six channels fit in 37 mm of rail, which is what makes an isolator per channel practical in a small cabinet.
Applications
Isolators are bought by the signal path they break, and these three cover most of the requests we see.
Sensors on a machine frame – a pressure or vibration sensor bolted to a frame sits at a different earth potential from the cabinet, and the barrier removes the current that would otherwise flow through the loop.
Signals into two systems – a line that has to reach a PLC and a recorder uses a duplicator, so both inputs see the same source and neither one can pull the other off zero.
Retrofit into an old cabinet – a configurable part replaces an unknown old isolator in a panel where the drawings are missing, because the input and output range can be set on site.
The analogue path ends on a board, so the SUPERB PCBA and the SUPERB PCB are checked against the same 4-20 mA list and the barrier is matched to the input that actually receives it.
Sourcing and Cross-Reference
Match the barrier to the sensor wiring, not to the signal range. A two wire transmitter expects the isolator to feed the loop, and a four wire transmitter does not, and the same 4-20 mA appears on both. A barrier set for the wrong one reads zero or reads full scale, and the sensor is usually replaced before the setting is checked.
Check the load the output can drive. A 550 ohm output into a 250 ohm input is fine, but two devices in series on one output can pass the limit, and the loop then reads low at the top of the range. The figure is on the row, so the sum of the receiving impedances is the check.
Signal isolators are a stock item in the common configurations and a lead time item in the special ones. Where a part is short, see lead time and availability, and cross reference when the old isolator is no longer made.
The SUPERB Assembly team sets the DIP switches on the bench and records the setting on the drawing, because a configurable barrier left at its default reads a different range on site.
Q: Can you supply the isolator with the sensor wiring already set, so the panel does not have to configure it on site?
A: Yes. Send the sensor type, its wiring, the supply and the range the control system expects, and the SUPERB Tech team returns the part with the switch setting written down.
Why Panel Builders Buy Signal Isolators From SUPERB
- Wiring explained with the part: two, three and four wire sensors are separated, which is the setting that most often goes wrong on a retrofit.
- Isolation voltage stated: 1.5 kV and 2 kV parts are listed separately, so a barrier is not chosen on price and then found to be below the isolation the panel needs.
- Load impedance given: the output load limit is on the row, which is what decides whether two devices can share one output.
- Width and heat load: 6.2 mm and 0.6 W are quoted with the part, so a cabinet full of barriers can be checked for rail space and for temperature rise.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail Terminal Blocks for Control Panel Wiring, Digital Panel Meters and Counters for Control Panels, DIN Rail Power Supplies for Control Cabinets, Control Transformers for Panel Control Voltage, Surge Protective Devices for AC Distribution Boards.