Control Transformers for Panel Control Voltage
Product Specifications
Product Overview
A control transformer exists to make the control circuit independent of the mains. Contactors, relays, pilot lamps and safety relays run on 24 V or 110 V while the machine runs on 400 V, and the transformer also stops a fault in the control circuit from reaching the mains side as a direct connection.
The primary is tapped, not switched. A 230 V and a 400 V terminal pair sit on the same winding, so one part number covers a panel built for either supply, and the tap is chosen at wiring time. That is why the input section of the table lists both voltages against one rating rather than two separate parts.
Sizing is done on inrush, not on the sealed load. A contactor coil that holds at a few volt amperes draws several times that while its armature is closing, and the transformer has to supply that pulse without dropping the voltage so far that the contactor chatters. Adding the sealed figures and buying the next size up is how a panel ends up with a transformer that browns out on a multi contactor start.
Key Specifications
| Family | Rating | Primary | Secondary | Frequency | Ambient |
|---|---|---|---|---|---|
| ABL6TS, 25 to 100 VA | 25, 63, 100 VA | 230 V and 400 V taps | 24 V, 115 V, 230 V | 47 to 63 Hz | -20 to +50 C |
| ABL6TS, 160 to 400 VA | 160, 250, 400 VA | 230 V and 400 V taps | 12 V, 24 V, 115 V, 230 V | 47 to 63 Hz | -20 to +50 C |
| ABL6TS, 630 to 1000 VA | 630, 1000 VA | 230 V and 400 V taps | 24 V, 115 V, 230 V | 47 to 63 Hz | -20 to +50 C |
| ABL6TS, 1600 to 2500 VA | 1600, 2500 VA | 230 V and 400 V taps | 115 V, 230 V | 47 to 63 Hz | -20 to +50 C |
Included Models and Order Codes
The code carries the rating and the secondary voltage: ABL6TS16B is 160 VA with a 24 V secondary, and ABL6TS16U is the same rating at 230 V. The primary is tapped for 230 V and 400 V on every rating, with an input tolerance that covers a supply between 207 V and 253 V on the 230 V tap and between 360 V and 440 V on the 400 V tap. Efficiency rises with the rating, from the small single phase parts to the 2500 VA frame, and the dissipation figure is what the enclosure heat calculation needs.
| Part number | Rating | Primary | Secondary | Efficiency | Note |
|---|---|---|---|---|---|
| ABL6TS02B | 25 VA | 230 V or 400 V | 24 V | on request | smallest frame, single circuit |
| ABL6TS16B | 160 VA | 230 V or 400 V | 24 V | on request | typical for a 24 V control circuit |
| ABL6TS16G | 160 VA | 230 V or 400 V | 115 V | on request | for 110 to 115 V coils |
| ABL6TS16U | 160 VA | 230 V or 400 V | 230 V | on request | for 230 V coils and lamps |
| ABL6TS25B | 250 VA | 230 V or 400 V | 24 V | on request | several contactors on one circuit |
| ABL6TS25U | 250 VA | 230 V or 400 V | 230 V | on request | 230 V control circuit |
| ABL6TS40B | 400 VA | 230 V or 400 V | 24 V | on request | larger 24 V loads |
| ABL6TS40U | 400 VA | 230 V or 400 V | 230 V | 92 percent | 34.8 W dissipation |
| ABL6TS63B | 630 VA | 230 V or 400 V | 24 V | on request | multi contactor panels |
| ABL6TS250U | 2500 VA | 230 V or 400 V | 230 V | on request | largest frame in the range |
What to Count When Sizing the Rating
The rating is not the sum of the nameplate volt amperes. Each load type contributes a different figure, and the inrush of a contactor coil is the one that decides the frame. The table below is the counting rule we apply when a customer sends a panel schedule instead of a transformer rating, and it is also the reason a panel with four contactors is quoted on a 250 VA part rather than a 100 VA one.
| Load | Figure to use | Why |
|---|---|---|
| Contactor coil, AC | inrush VA at the closing instant | the coil draws several times its sealed VA while the armature closes |
| Relay coil, AC | sealed VA | the armature is light, so the inrush is short and small |
| Pilot lamp or LED stack light | steady wattage divided by the power factor | a lamp is a resistive load and runs continuously |
| Safety relay and electronic modules | steady VA plus any inrush stated by the maker | electronics carry a capacitor that charges at switch on |
| Reserve | at least 20 percent above the total | a transformer run at its limit has a short life at 50 C |
Key Features
Tapped primary on one part – 230 V and 400 V terminals on the same winding, so a panel built for either supply uses one spare.
Secondary separated from the mains – the control circuit is isolated, which allows one side to be earthed and the fault path to be defined.
Ratings from 25 VA to 2500 VA – a single circuit and a full contactor row come from the same family, with the same terminal arrangement.
Efficiency stated per frame – the dissipation figure is what the enclosure heat calculation needs on a sealed cabinet.
50 C ambient rating – the frame runs at its rating at 50 C, which is the temperature inside a closed cabinet in summer.
Terminal cover available – the primary terminals are covered, which matters on a part where 400 V is exposed at the top of the stack.
Applications
The transformer sits between the supply and the control circuit. Three panel types use it.
Contactor and relay control on a 400 V machine – a 400 V primary tap with a 24 V secondary, so every coil and lamp in the panel runs on one voltage.
Safety circuit supply – a separate 24 V secondary feeding the safety relay and its contactors, kept apart from the PLC rail so a control fault cannot drop the guard circuit.
Panel built for export – a 230 V tap on the same part, so the same panel is wired for a 230 V supply without a different transformer.
The control voltage is quoted with the board that uses it, so the SUPERB PCBA and the SUPERB PCB are checked for the same 24 V rail and the relay coils that load it.
Sourcing and Cross-Reference
Add the inrush, then add the reserve. Four contactor coils that hold at a few volt amperes each can pull several times that while closing, and a transformer sized on the sealed total will drop the secondary voltage during a simultaneous start. The contactor then chatters, the auxiliary contact bounces, and the fault looks like a coil problem rather than a supply problem.
Check the secondary voltage against the coil, not against the drawing note. A 24 V secondary with a long cable and a heavy load can arrive at the coil below its pull in voltage. Where the run is long, the 115 V or 230 V secondary carries the same power at a lower current and loses less in the cable.
Keep the transformer dissipation in the enclosure calculation. A 400 VA part dissipates about 35 W at full load, which is heat inside a sealed cabinet and has to be added to the contactor and drive losses. A cabinet with a cooling unit is fine, and a sealed cabinet without one is where the ambient rating of the transformer becomes the limiting item.
Lead time on the large frames follows the rating rather than the secondary voltage. See lead time and availability for the position today, and the power management cross reference when the frame on the drawing has been withdrawn.
The SUPERB Assembly team keeps the primary and secondary wiring in separate ducts, because a 400 V primary core run beside a 24 V signal is the shortest path to an intermittent input.
Q: Can you supply the control transformer sized on our coil schedule, tapped for the supply voltage of the site?
A: Yes. Send the coil schedule with the sealed and inrush volt amperes, the supply voltage at the site and the enclosure temperature, and the SUPERB Tech team returns the rating and the tap.
Why Panel Builders Buy Control Transformers From SUPERB
- Sized on inrush: the coil schedule is added with the inrush figures and a reserve, so a simultaneous start does not brown out the control circuit.
- One part, two supplies: the 230 V and 400 V taps are in the table, which keeps one spare for panels built for either site.
- Dissipation stated: the watts lost in the transformer are quoted, because they are heat inside the enclosure.
- Secondary matched to the coil: 24 V, 115 V and 230 V versions are separated, so the coil voltage and the transformer are ordered together.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, DIN Rail Power Supplies for Control Cabinets, Thermal Overload Relays for Motor Protection, Power Distribution Blocks for Panel Feeds, Surge Protective Devices for AC Distribution Boards.