Contact Us
  • Home
  • COMPONENTS
  • Semiconductor and DC Fuses for Drive and Battery Protection

Semiconductor and DC Fuses for Drive and Battery Protection

aR fuse links that clear a fault before the module sees the let through energy, sized from 40 A to 2250 A. Square body and NH bodies carry the same 690 V AC rating, in four mounting styles for busbar and rail builds. DC ratings are quoted separately: 150 kA at 1000 V DC on the PSR range, 50 kA at 500 V DC on the stud fuse. Pre-arcing and clearing I2t sit on the same row, so a replacement is checked on energy rather than on amps.
quote now

Product Specifications

Product Overview

A drive or a rectifier fails at the module, not at the breaker. The thyristor or IGBT has a surge current limit measured in a few milliseconds, and an ordinary gG fuse is built to carry starting current and to clear in tens of milliseconds. By the time a gG link opens, the junction is already past its limit. The aR class exists for exactly this reason: it does not hold an overload, it opens fast and it limits the current that reaches the module.

The number that decides whether a fuse protects a module is I2t, not the ampere rating. A 400 A aR link with 15 kA2s pre-arcing and 90 kA2s clearing lets through a fraction of the energy of a 400 A gG link, and that fraction is what the module data sheet compares against its own withstand. This is also why two fuses with the same current rating cannot be swapped without checking the two I2t values, and why an oversized link is as wrong as an undersized one: the module is then protected by nothing.

Direct current changes the calculation. A DC arc has no natural current zero, so the fuse has to build up an arc voltage higher than the system voltage and hold it until the current falls. That is why a DC rating is quoted with a time constant and a separate breaking capacity, and why an AC rated link is not a DC rated link even when the voltage figure looks low enough. On a battery rack the same rule applies in reverse: a 500 V DC stud fuse with 50 kA breaking capacity is a different part from a 690 V AC link, and the part number has to be read for the DC figure.

Key Specifications

ParameterValueNote
Rated voltage AC450 to 1300 V690 V AC IEC and 700 V AC UL on the square body and NH aR ranges
Rated voltage DC450 to 1000 V on the PSR range, 500 V DC on the FWH stud fuseDC figures are separate ratings, not a derating of the AC value
Rated current40 to 2250 A16 to 1000 A on the NH aR sizes
Breaking capacity AC80 to 200 kA200 kA on square body size 32 and size 33
Breaking capacity DC50 kA at 500 V DC, 150 kA at up to 1000 V DCtime constant 10 ms on the PSR DC tests
Operating classaR to IEC 60269-4gG, gPV and aM are different jobs and different curves
Pre-arcing I2t5.2 kA2s at 315 A, 465 kA2s at 1400 Asize 32 and size 33 tables
Clearing I2t at rated voltage31.8 kA2s at 315 A, 2700 kA2s at 1400 Acompare against the module withstand, not against the fuse current
Power dissipation at rated current71 W at 315 A, 200 W at 1400 Apanel cooling has to carry this figure
Trip indicationlow voltage trip indicator, microswitch as an optionProtistor and PSR both offer a field mountable microswitch
Bodyceramic, sand filled, silver plated contactssand controls the arc and keeps I2t low
TerminalsM10 and M12 threaded, DIN 80 and DIN 110 blades, flush end studsone rating appears in several mountings
Operating temperature-55 to +125 CPSR range
StandardsIEC 60269-4, UL 248-13, CCC GB 13539.4UL and CSA recognition per range, check the status column on the maker table

Included Models and Order Codes

The rows below are grouped by maker, because the order code carries the rating differently in each family. On the Mersen Protistor the catalog number holds the size and the voltage: PC32 is size 32, UD is the aR element, 69 is 690 V AC, and the last digits are the ampere rating, so PC32UD69V400TF is a 400 A size 32 link. On the Mersen NH range the size prefix comes first, NH000 or NH00, followed by the same voltage block. The Eaton Bussmann 170M family is quoted by size and ampere, and the Littelfuse PSR range is quoted by series and terminal style, with the DC voltage in the part description. Where a maker publishes the I2t pair, both numbers are in the row. Where the value is only given per family, the row says so instead of carrying a figure across from another size.

Part numberFamilyRated voltageRated currentI2t pre-arcing / clearingNote
PC32UD69V400TFMersen Protistor size 32690 V AC, 700 V UL400 A15 / 90 kA2sM10 threaded terminals, 200 kA, 72 W
PC32UD69V500TFMersen Protistor size 32690 V AC, 700 V UL500 A28 / 160 kA2s200 kA, 85 W
PC32UD69V630TFMersen Protistor size 32690 V AC, 700 V UL630 A54 / 310 kA2s200 kA, 95 W
PC32UD69V800TFMersen Protistor size 32690 V AC, 700 V UL800 A115 / 660 kA2s200 kA, 110 W
PC33UD69V1000TFMersen Protistor size 33690 V AC, 700 V UL1000 A170 / 990 kA2sM12 threaded terminals, 200 kA, 135 W
PC33UD69V1250TFMersen Protistor size 33690 V AC, 700 V UL1250 A355 / 2053 kA2s200 kA, 150 W
NH000UD69V100PVMersen Protistor NH 000690 V AC, 700 V UL100 A722 A2s / 4.3 kA2s80 kA, 19.4 W, 0.13 kg
NH00UD69V160PVMersen Protistor NH 00690 V AC, 700 V UL160 A2070 A2s / 12.2 kA2s170 kA, 30.5 W
170M size 1 to 3Eaton Bussmann 170M690 V AC, 700 V UL40 to 2000 Aper rating in the maker tableaR, DIN 43653 blades, 200 kA
FWH-400AEaton Bussmann FWH500 V AC and 500 V DC400 Aper rating in the maker tablestud mount, 200 kA AC and 50 kA DC, 35 to 1600 A in the family
PSR, flush endLittelfuse PSR450 to 1300 V AC, 450 to 1000 V DC40 to 2250 Aper rating in the maker table100 to 200 kA AC, 150 kA DC, 10 ms, blown fuse indicator
PSR, DIN 43653 bladeLittelfuse PSR450 to 1300 V AC, 450 to 1000 V DC40 to 2250 Aper rating on the maker tablebolted blade and DIN blade styles on the same ratings

What the Class Letter Decides

Four letters cover most of the panel work, and mixing them up is the most common reason a fuse is replaced twice. The class is not a quality grade, it is a statement about which fault the link is meant to clear and how much energy it lets through before it does.

ClassWhat it protectsWhere it belongs
aRsemiconductor modules: diodes, thyristors, IGBT, MOSFETdrive DC bus, rectifier output, inverter leg, UPS, soft starter
gPVphotovoltaic strings against reverse currentstring combiner and inverter DC input, rated for the string voltage
gGcables and general loads against overload and short circuitpanel feeders and distribution, not a module
aMmotor circuits, short circuit only, overload left to the relaymotor feeder where a thermal relay sits downstream

Key Features

I2t quoted as a pair – pre-arcing and clearing energy sit on the same row, so a substitute is compared on the number the module data sheet asks for instead of on the ampere rating alone.

DC rating written out – 150 kA at up to 1000 V DC on the PSR range and 50 kA at 500 V DC on the FWH stud fuse, with the 10 ms time constant, because a DC arc has no current zero to help it.

Trip indicator with microswitch option – a blown link shows on the body, and the microswitch brings the signal to the door or to the controller, which turns a two hour fault find into a lamp.

One rating, four mountings – threaded studs, DIN 80 blades, DIN 110 blades and flush end studs let the same electrical part fit a busbar stack or a rail holder without changing the protection.

NH body for rail builds – NH 000 and NH 00 links sit in a standard fuse base, so a panel that already uses NH gear keeps its bases and its arc barriers.

Sand filled ceramic body – the filler quenches the arc and keeps the let through energy low, which is what makes the fast clearing possible at 200 kA.

Applications

The three cases below cover most of the orders we quote for this family, and each one sets a different limit on the fuse.

Variable speed drives and servo amplifiers – the DC bus capacitor bank delivers a fault current that rises faster than any breaker can follow, and the aR link in series with the module is the only part fast enough to keep the junction inside its surge rating.

Rectifiers, UPS and battery chargers – the thyristor bridge and the battery share a DC node, so the fuse has to clear a reverse fault from the battery as well as a forward fault from the bridge, which is why the DC breaking capacity and the time constant are checked before the ampere rating.

Battery racks and DC distribution – a rack fuse protects the cable and the cells against a short in one string, and the 500 V DC stud fuse with 50 kA breaking capacity is the part that holds the arc on a 400 V rack where an AC link would restrike.

The drive is quoted with its control board, so the SUPERB PCBA and the SUPERB PCB are checked against the same fuse list and the DC bus clearance is verified once for both.

Sourcing and Cross-Reference

Most of these links are ordered as a line item on a drive BOM, so the practical question is which body the panel was built around. A square body size 32 sits on a busbar with M10 studs, an NH 00 sits in a base on a rail, and a 170M sits on DIN 43653 blades. The electrical protection can be matched across all three, the mounting cannot, so the first check on a replacement is the terminal style and the second is the I2t pair.

The second question is the DC figure. Panels that started on an AC drive often grow a battery or a DC link later, and the same 690 V AC link is then asked to break DC. Where the maker publishes a DC rating, it is in the row above. Where it does not, the honest answer is that the link is an AC part and a DC rated family is needed, and we would rather say that than let a 690 V AC number stand in for a DC rating it never had.

For panels waiting on one rating, the options are usually a different mounting of the same rating, the next size up in the same family when the I2t still fits the module, or an equivalent family from another maker with the same class and voltage. See lead time and availability for the position on a specific rating, and BOM shortage recovery where a drive build is held up by one fuse.

The SUPERB Assembly team fits the link on the stud with the maker torque figure, because an under torqued stud adds resistance that shows up later as a warm terminal.

Q: Can you confirm the pre-arcing I2t and the DC voltage rating of a proposed substitute before we release the drive build?

A: Yes. Send the module part number, the DC bus voltage, the expected fault current and the mounting, and the SUPERB Tech team returns the class, the I2t pair and the mounting style that fit.

Why Drive and Battery Builders Source Fuses Through SUPERB

  1. Both I2t numbers on the row: the pre-arcing and clearing values are listed together with the voltage, so a substitute is checked on energy rather than on the ampere figure printed on the barrel.
  2. AC and DC ratings kept apart: a DC rating is shown as its own value with its time constant, which stops an AC link from being used on a battery rack because the voltage looked close enough.
  3. Mounting style named: stud, DIN 80, DIN 110 and flush end are called out per row, so the part that arrives fits the busbar that is already in the panel.
  4. Trip indication available: the microswitch option is listed with the link, which keeps the fault signal on the drawing instead of being added after the first failure.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: NH Fuse Links and DIN Rail Fuse Bases, Fuse Holders and Clips for Board Level Protection, DC Isolator Switches for PV and Battery Strings, Line Reactors and Motor Chokes for Variable Speed Drives, Fuse Switch Disconnectors for Panel Isolation.