Fuse Switch Disconnectors for Panel Isolation
Product Specifications
Product Overview
A fuse switch disconnector does two jobs in one body: it isolates a feeder with a visible break, and it holds the fuse that clears a short circuit. That combination is why it appears at the incoming of a sub-panel, in front of a group of drives, and on any feeder where a maintenance engineer needs to lock the supply off and see that it is off.
The rating that decides the order is the utilisation category, not the thermal current on the label. AC-21 covers resistive loads, AC-22 a light inductive load, and AC-23 a motor load with its inrush. A 160 A device can carry 160 A in AC-23 at 400 V and only 25 A in AC-23 at 690 V, because the arc energy rises with the voltage. Reading only the current is how a switch ends up undersized on a 690 V drive feeder.
The fuse does the short circuit protection and nothing else. Overload protection of a motor still belongs to a thermal relay, and cable overload protection belongs to the fuse rating being chosen for the cable. On a feeder where the fuse is sized for the cable, a downstream motor needs its own protection, which is why the switch is usually followed by a motor protection device rather than replacing it.
Key Specifications
| Family | Fuse size | Rated current | Voltage | AC-23 rating | Poles | Note |
|---|---|---|---|---|---|---|
| ABB OS100GJ03 | NH000 / NH00 | 100 A | 690 V AC | 100 A up to 690 V | 3 | Ui 1000 V, base mounting |
| ABB OS125GD03 | NH000 / NH00 | 125 A | 690 V AC | 125 A at 690 V, 55 kW at 400 V | 3 | handle and shaft not included |
| ABB OS160GD03 | NH000 / NH00 | 160 A | 690 V AC | 160 A at 690 V, 75 kW at 400 V | 3 | Inc 80 kA at 690 V |
| ABB OS125GDS30K | NH000 / NH00 | 125 A | 690 V AC | 125 A at 690 V | 3 | side operated, terminal bolts included |
| ABB OS160GDS30K | NH000 / NH00 | 160 A | 690 V AC | 160 A at 690 V | 3 | side operated, terminal bolts included |
| ABB OS125GB03 | BS 125 A | 125 A | 690 V AC | 125 A at 690 V | 3 | BS fuse system, not NH |
| Siemens 3NP1123-1CA20 | NH000 | 160 A frame, 125 A rated | 690 V AC | 160 A at 400 V, 25 A at 690 V | 3 | IP40 with cover, IP20 open |
Included Models and Order Codes
The type code carries the current, the generation and the mounting. On ABB OS125GD03 the 125 is the rated current, G is the gamma generation, D is the DIN NH fuse system and 03 is three poles; the S in OS125GDS30K marks the side operated version. On Siemens 3NP1 the last groups set the pole count, the fuse size and the terminal style, so 3NP1123-1CA20 is three pole NH000 with box terminals, and a different suffix changes the terminals rather than the rating.
| Part number | Fuse size | Rated current | Power at 400 V AC-23 | Power at 690 V AC-23 | Terminals | Note |
|---|---|---|---|---|---|---|
| OS100GJ03 | NH000 / NH00 | 100 A | on request | on request | bolt | base mounting |
| OS125GD03 | NH000 / NH00 | 125 A | 55 kW | 110 kW | bolt M8 | front operated |
| OS160GD03 | NH000 / NH00 | 160 A | 75 kW | 132 kW | bolt M8 | front operated |
| OS125GDS30K | NH000 / NH00 | 125 A | 55 kW | 110 kW | bolt kit included | side operated |
| OS160GDS30K | NH000 / NH00 | 160 A | 75 kW | 132 kW | bolt kit included | side operated |
| OS125GB03 | BS 125 A | 125 A | 55 kW | 110 kW | bolt | BS fuse, 3 pole |
| 3NP1123-1CA20 | NH000 | 125 A rated, 160 A at 35 C | 160 A AC-23B | 25 A AC-23B | box terminal | DC-21B 100 A at 440 V |
What the Fuse Size Allows
The switch body and the fuse inside it have separate limits, and the lower of the two is the real rating of the feeder. The table lists the usual NH sizes with the current they can carry and the body width that follows from them.
| Fuse size | gG current range | Body width | Typical switch | Note |
|---|---|---|---|---|
| NH000 | 2 to 100 A | 21 x 76 mm blade | OS100G, 3NP1123 | the common panel size |
| NH00 | 2 to 160 A | 21 x 78 mm blade | OS125G, OS160G, 3NP1123 | same blade, higher current |
| NH1 | 16 to 250 A | 30 x 100 mm blade | OS200 and above | needs a larger switch body |
| NH2 | 35 to 400 A | 40 x 120 mm blade | OS400 class | not covered by this page |
Key Features
Visible break under the cover – the fuse carrier is pulled out of the circuit, so isolation can be confirmed by inspection and not only by a handle position.
Padlockable in the off position – the handle takes a padlock, which is what a lock-out procedure needs before maintenance starts on a feeder.
AC-23 rating for motor feeders – the motor switching figure is listed next to the thermal current, because a 690 V drive feeder is limited by the arc energy and not by the copper.
80 kA conditional short circuit current – the switch and a matching fuse clear a fault without the body being replaced, which is the reason the fuse size and the switch are chosen together.
Three and four pole versions – a four pole body is used where the neutral is switched or where a three phase load is isolated completely, and the mounting footprint stays the same.
Front or side operation – a front handle suits a door mounted switch and a side handle suits a base mounted row, and the shaft length is chosen from the enclosure depth.
Applications
The switch is bought for three situations, and each one puts a different requirement on the fuse and the handle.
Sub-panel incoming isolation – one switch at the head of a group of drives, padlocked for maintenance, with the fuse sized for the busbar and the downstream protection doing the rest.
Drive and motor feeder – an AC-23 rated switch in front of a single large drive or a soft starter, where the motor inrush is the load the contacts have to break.
PV and DC auxiliary circuits – the AC switch is used on the inverter output side, with the DC side handled by a dedicated DC isolator rather than an AC body.
The switch is quoted with the panel wiring schedule, so the SUPERB PCBA and the SUPERB PCB are checked against the same drawing and the fuse rating agrees with the cable it protects.
Sourcing and Cross-Reference
Order the handle with the switch. Most front operated NH switches are supplied as a body only, and the handle, the shaft and sometimes the terminal bolts are separate lines. A switch that arrives without a handle cannot be operated, and the shaft length depends on the enclosure depth, which is known at the panel stage and forgotten at the order stage.
Check the utilisation category against the load. A switch rated 160 A in AC-21 is not a 160 A motor switch, and the difference is largest at 690 V. For a drive feeder the AC-23 figure is the one to compare, and for a resistive load the AC-21 figure is enough with a smaller body.
Match the fuse to the cable and to the short circuit level. The conditional short circuit current of the combination is quoted with a specific fuse, so a cheaper fuse of the same size can lower the rating of the whole feeder. See fuses and PTC protection for the board level parts, kWh meters for metering on the same feeder, and lead time and availability for the current position.
The SUPERB Assembly team torques the terminal bolts to the maker figure and leaves the handle in the off position with the padlock hole free, because a switch shipped closed is a switch that gets energised during transport.
Q: Can you quote the switch with the handle, the shaft and the fuses as one set, sized for our feeder?
A: Yes. Send the feeder current, the load type and the enclosure depth, and the SUPERB Tech team returns the switch, the fuse size, the handle and the shaft length that fit.
Why Panel Builders Buy Fuse Switch Disconnectors From SUPERB
- Both ratings in one row: thermal current and AC-23 current are listed together, so a motor feeder is not sized on the wrong figure.
- Fuse size named: NH000, NH00 and BS types are stated per model, because the fuse system decides what the switch can hold.
- Accessories called out: the rows say where the handle, the shaft or the terminal bolts are separate, which is the line most often missing from a first order.
- Short circuit rating given: the conditional rating is written with the fuse it assumes, so the combination is checked rather than assumed.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail kWh Meters for Panel Energy Monitoring, Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads, DC Isolator Switches for PV and Battery Strings, Surge Protective Devices for AC Distribution Boards.