DC Isolator Switches for PV and Battery Strings
Product Specifications
Product Overview
Direct current does not have a zero crossing, so an arc drawn between separating contacts does not go out by itself. That single fact is why a DC isolator is not an AC switch with a different label. A DC rated device uses a permanent magnet or a blowout coil to push the arc sideways into a splitter, lengthening it until the voltage can no longer sustain it, and it opens fast enough that the arc is short.
In a photovoltaic system the isolator appears in three places: at the string, in the combiner box, and at the inverter input. Each has a different requirement. A string switch is a small two pole body that a service engineer operates once a year. A combiner switch carries the summed current of several strings and has to break a fault current fed by the array. The inverter input switch is often a large frame with a motor operator or a side handle.
The voltage rating of a DC switch is a property of the pole arrangement, not of the frame. Connecting poles in series divides the arc voltage across several gaps, which is why the same small body is rated 600 V DC with two poles and 1000 V DC with four. Reading the current rating alone and ignoring the pole count is the most common way a DC isolator ends up under-rated for the array voltage.
Key Specifications
| Family | Poles | Voltage | Current | Utilisation | Mounting | Note |
|---|---|---|---|---|---|---|
| ABB OTDC16UT2 | 2 | 600 V DC UL, 660 V DC IEC | 16 A | DC-PV2 | base or DIN | single circuit |
| ABB OTDC16UT4 | 4 | 1000 V DC | 10 A at 1000 V, 16 A at 660 V | DC-PV2 | base or DIN | poles in series |
| ABB OTDC32UT4 | 4 | 1000 V DC | 20 A at 1000 V, 32 A at 660 V | DC-PV2 | base or DIN | poles in series |
| ABB OTDC100U11 | 2 | 1000 V DC, UL98B | 100 A | DC-PV2 | base | 5 kA at 1000 V DC |
| ABB OTDC200U11 | 2 | 1000 V DC, UL98B | 200 A | DC-PV2 | base | 5 kA at 1000 V DC |
| ABB OTDC100E | 2 to 4 | 1000 V DC, IEC | 100 A | DC-21B and DC-22B | base | visible contacts |
| ABB OTDC250E | 2 to 4 | 1000 V DC, IEC | 250 A | DC-21B and DC-22B | base | 1500 V versions in the same family |
Included Models and Order Codes
The type code reads current, frame generation and purpose. On ABB OTDC the number is the rated current, the letter after it is the frame size, and the last two characters give the pole count: 11 is two poles, 22 four poles, 03 three poles. The U and E suffixes are the UL and IEC versions, and the S in OTDCP marks the enclosed body rather than a base mounted switch.
| Part number | Poles | Rated voltage | Rated current | Short circuit | Weight | Note |
|---|---|---|---|---|---|---|
| OTDC16UT2 | 2 | 600 V DC, 660 V DC | 16 A | on request | 0.15 kg | single circuit |
| OTDC25UT2 | 2 | 600 V DC, 660 V DC | 25 A | on request | 0.15 kg | single circuit |
| OTDC32UT2 | 2 | 600 V DC, 660 V DC | 32 A | on request | 0.15 kg | single circuit |
| OTDC16UT4 | 4 | 1000 V DC | 16 A at 660 V, 10 A at 1000 V | on request | 0.15 kg | double circuit |
| OTDC25UT4 | 4 | 1000 V DC | 25 A at 660 V, 16 A at 1000 V | on request | 0.15 kg | double circuit |
| OTDC32UT4 | 4 | 1000 V DC | 32 A at 660 V, 20 A at 1000 V | on request | 0.15 kg | double circuit |
| OTDC100U11 | 2 | 1000 V DC | 100 A | 5 kA | 1.2 kg | UL98B, 2000 cycles |
| OTDC200U11 | 2 | 1000 V DC | 200 A | 5 kA | 1.2 kg | UL98B, 2000 cycles |
| OTDC100E | 2 to 4 | 1000 V DC | 100 A | on request | on request | IEC 60947-3 |
| OTDC250E | 2 to 4 | 1000 V DC | 250 A | on request | on request | IEC 60947-3 |
Poles in Series and the Voltage They Buy
On a DC switch the rated voltage is bought with poles, not with frame size. The table shows how the small OTDC bodies are rated as the poles are connected in series, which is the calculation behind a 1000 V string switch built on a 16 A body.
| Poles in series | Breaking voltage | Current at that voltage | Typical use | Note |
|---|---|---|---|---|
| 2 poles | 600 V DC | 16 to 32 A | single string, 600 V array | one circuit per body |
| 4 poles | 1000 V DC | 10 to 20 A | 1000 V string or two 600 V strings | two circuits in one body |
| 2 poles on a 100 A frame | 1000 V DC | 100 A | combiner output | magnetic blowout in the frame |
| 2 poles on a 200 A frame | 1000 V DC | 200 A | inverter input | side handle available |
| 4 poles on a 250 A frame | 1500 V DC | 250 A | 1500 V central inverter | wider frame, higher arc voltage |
Key Features
Magnetic arc blowout – a permanent magnet drives the DC arc into a splitter stack, which is what allows the contacts to break a direct current without a zero crossing.
Visible contacts – the contact position can be seen through the cover, so isolation is confirmed by inspection and not by the handle alone.
Quick make and quick break – the mechanism is spring driven and independent of how fast the handle is moved, so a slow operator does not hold an arc.
Poles in series for higher voltage – the same body reaches 1000 V DC with four poles in series, which keeps a string switch small and cheap.
Rated for photovoltaic duty – the DC-PV2 utilisation category covers the array fault current, which is only slightly above the operating current and therefore easy to underestimate.
Base, DIN and door mounting – the small frames mount on a DIN rail or a base plate, and the large frames take a shaft and a door handle, so the same family covers a combiner and an inverter.
Applications
The isolator is chosen from where it sits in the array, and the fault current at that point decides the frame.
String disconnect at the roof – a two or four pole body at each string, rated for the array open circuit voltage with a margin, operated only for service.
Combiner box output – a 100 to 250 A frame carrying the summed string current, with the short circuit rating checked against the array fault current and the fuse class.
Battery rack isolation – a DC switch on a battery rack where the fault level is much higher than a PV array, which is why the ESS rated versions exist in the same family.
The isolator is quoted with the monitoring board that reads the array, so the SUPERB PCBA and the SUPERB PCB are checked against the same drawing and the auxiliary contact agrees with the input.
Sourcing and Cross-Reference
Never substitute an AC switch disconnector on a DC circuit. The contacts may look identical and the thermal current may match, but the arc extinction is made for a current that crosses zero twice per cycle, and a DC arc will hold until the switch is destroyed. The DC rating is the first line to read on the label.
Work out the pole count from the array voltage, not from the current. A 1000 V string on a two pole body is outside its rating even if the current is 8 A, and the four pole version of the same frame is the correct part. The same logic applies at 1500 V, where the wider frames with four poles are needed.
Check the fault level for a battery rack. A PV array delivers only a little more than its short circuit current, while a battery can deliver several kiloamps, and the ESS rated versions are the ones quoted with that figure. Related pages cover AC fuse switch disconnectors for the grid side, insulation monitors for an unearthed battery system, and lead time and availability for the current position.
The SUPERB Assembly team torques the DC terminals to the maker figure and keeps the positive and negative runs separated to the switch, because a shared terminal block on a 1000 V string is a tracking path waiting to happen.
Q: Can you supply the DC isolator with the fuses and the combiner enclosure sized for our string voltage?
A: Yes. Send the string voltage, the string current, the number of strings per combiner and whether the load is a PV array or a battery, and the SUPERB Tech team returns the frame, the pole count and the handle.
Why Solar and Battery Builders Buy DC Isolators From SUPERB
- Pole count and voltage together: each row states the poles and the voltage those poles buy, which is the calculation a string switch depends on.
- DC rating separated from AC: the utilisation category is written per family, so an AC body is never quoted into a DC circuit.
- Current at the rated voltage: the current is given at 1000 V and at 660 V separately, because the same body carries less at the higher voltage.
- Frame and mounting stated: base, DIN and door mounting are listed with the weight, so the enclosure and the handle are planned with the switch.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Fuse Switch Disconnectors for Panel Isolation, Insulation Monitoring Devices for Unearthed Systems, Surge Protective Devices for AC Distribution Boards, DC Axial Fans for Enclosure Cooling, Busbars and Earth Bars for Panel Power Distribution.