NH Fuse Links and DIN Rail Fuse Bases
Product Specifications
Product Overview
An NH fuse link, also called an HRC fuse in the UK and a knife fuse in some catalogues, is a ceramic body with a blade contact at each end and a silver or copper element inside. The blade contacts let the link carry a high current with a low voltage drop and still break a short circuit inside a small volume. That is why a panel with a 500 kVA transformer at the intake uses NH links where a miniature fuse would not survive.
The class that matters most in a panel is gG, the general purpose class that protects cable and switchgear against overload and short circuit. A gG link follows a time current curve, so a 63 A link carries 63 A indefinitely, trips on a modest overload after minutes and clears a short circuit in a few milliseconds. For a motor branch the gG link is usually the back up behind a motor protection circuit breaker, and the coordination table of the breaker states which link size is required.
Two things in this family catch buyers out. The first is the size code. NH000 is 21 mm wide at the mounting and NH00 is 30 mm, and a 100 A link exists in both, so a 100 A order can arrive in the wrong body. The second is the voltage suffix. The plain 3NA38 part is rated 500 V AC and 250 V DC, while the -6 suffix is the 690 V version, and a 690 V panel fed with the plain part runs the link above its rating.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Fuse standard | IEC 60269-1 and EN 60269 | NH blade fuse system |
| Operational class | gG | cable and line protection, overload and short circuit |
| Rated voltage, NH000 and NH00 | 500 V AC, 250 V DC | -6 suffix raises the AC rating to 690 V |
| Rated voltage, NH1 and NH2 | 500 V AC, 440 V DC | DC rating follows the larger body |
| Breaking capacity | 120 kA at 500 V AC | let through current below 17 kA on the standard range |
| Current range in this range | 6 A to 250 A | size decides the base, not the current |
| Mounting width | 21 mm NH000, 30 mm NH00 and NH1, 47.5 mm NH2 | NH000 and NH00 are not interchangeable |
| Base rated voltage | 690 V AC, 440 V DC | 3NH3 series bases |
| Base breaking capacity | 120 kA AC, 25 kA DC | with a link of the matching size fitted |
| Base terminal | flat terminal 95 mm2, M8 stud | tightening torque 14 N.m on the main terminal |
| Indicator options | front indicator or combination alarm | combination alarm gives a signalling contact |
| Operating temperature | -5 C to +40 C average, 35 C daily mean | derating above 40 C follows the maker curve |
Included Models and Order Codes
The part number carries the size and the current. On the 3NA3 range the digits after the series are the current code, and the -7 suffix marks size 00 where the same current exists in two bodies. The -8 suffix on the two largest NH000 currents marks a 400 V only link, and the -6 suffix marks the 690 V AC version. When a drawing lists only a current, the body size on the existing base is the reference that has to be read before ordering.
| Part number | Size | Rated current | Rated voltage AC / DC | Class | Note |
|---|---|---|---|---|---|
| 3NA3801 | NH000 | 6 A | 500 V / 250 V | gG | control circuits and small transformers |
| 3NA3803 | NH000 | 10 A | 500 V / 250 V | gG | instrument and signal supplies |
| 3NA3805 | NH000 | 16 A | 500 V / 250 V | gG | back up for a small motor starter |
| 3NA3810 | NH000 | 25 A | 500 V / 250 V | gG | sub distribution in a cabinet |
| 3NA3814 | NH000 | 35 A | 500 V / 250 V | gG | common size on 5.5 kW drives |
| 3NA3817 | NH000 | 40 A | 500 V / 250 V | gG | feeder to a contactor group |
| 3NA3820 | NH000 | 50 A | 500 V / 250 V | gG | feeder to a 7.5 kW motor starter |
| 3NA3822 | NH000 | 63 A | 500 V / 250 V | gG | most used current in a machine panel |
| 3NA3824 | NH000 | 80 A | 500 V / 250 V | gG | largest practical NH000 on a DIN rail |
| 3NA3830 | NH000 | 100 A | 500 V / 250 V | gG | top of the 500 V NH000 range |
| 3NA3832-8 | NH000 | 125 A | 400 V | gG | 400 V only, check the panel voltage |
| 3NA3836-8 | NH000 | 160 A | 400 V | gG | 400 V only, 160 A in a 21 mm body |
| 3NA3820-7 | NH00 | 50 A | 500 V / 250 V | gG | size 00 body, 30 mm mounting |
| 3NA3830-7 | NH00 | 100 A | 500 V / 250 V | gG | size 00 body, 30 mm mounting |
| 3NA3136 | NH1 | 160 A | 500 V / 440 V | gG | main feeder in a large cabinet |
| 3NA3144 | NH1 | 250 A | 500 V / 440 V | gG | intake protection at 250 A |
Bases and Matching Accessories
A base is chosen by size and by pole count, and the current rating of the base is a thermal limit that sits above the largest link that fits. The 3NH3 range below covers the single pole and three pole bodies in the three sizes used in a panel, and the flat terminal takes a 95 mm2 cable with an M8 stud at 14 N.m.
| Part number | Size | Poles | Rated current | Rated voltage | Note |
|---|---|---|---|---|---|
| 3NH3030 | NH00 | 1 | 160 A | 690 V AC / 440 V DC | flat terminal 95 mm2, 122 x 34 x 60 mm |
| 3NH4030 | NH00 | 3 | 160 A | 690 V AC / 440 V DC | three pole base for a feeder in one block |
| 3NH3230 | NH1 | 1 | 250 A | 690 V AC / 440 V DC | size 1 body, 250 A link |
| 3NH3330 | NH2 | 1 | 400 A | 690 V AC / 440 V DC | size 2 body, intake or main distribution |
| 3NX1016 | NH000 to NH3 | - | - | - | fuse puller with leather sleeve |
| 3NX3114 | NH0 | - | - | - | insulated cover for the base of that size |
Key Features
120 kA breaking capacity – a short circuit at the intake of a 500 kVA transformer is cleared without the link rupturing the base, which is the reason NH is used rather than a miniature fuse above 63 A.
Size code stated on every line – NH000 at 21 mm and NH00 at 30 mm appear as separate rows, so a 100 A order cannot arrive in the wrong body.
Voltage suffix kept separate – the plain part is 500 V AC and the -6 suffix is the 690 V version, with a -8 suffix on the two 400 V only currents.
DC ratings to 440 V – the NH1 and NH2 bodies are rated 440 V DC, which covers a battery string or a DC bus in a drive cabinet.
Front indicator or combination alarm – the plain link shows a striker, and the combination alarm version adds a signalling contact for a panel lamp or a PLC input.
Bases rated above the link – 690 V AC and 440 V DC on the base with a 120 kA AC breaking capacity, so the base is not the weak point of the feeder.
Applications
NH links are bought by the feeder they protect, and these three cover most of the panels we quote.
Main and sub distribution feeders – a gG link at the intake protects the busbar and the cable to the first sub board, and the same size continues down the cabinet so a fault trips only the affected feeder.
Back up for motor protection circuit breakers – the coordination table of a motor protection breaker states the largest gG link that may sit in front of it, and above that current the breaker alone cannot clear the fault.
DC battery and drive buses – the 440 V DC rating on the NH1 and NH2 bodies covers a battery string or a DC bus in a drive cabinet where an AC rated link would be outside its rating.
A feeder is quoted with the board that monitors it, so the SUPERB PCBA and the SUPERB PCB are checked against the same current list and the link is sized from the cable rather than from the label.
Sourcing and Cross-Reference
Order by body size first and current second. A 100 A gG link exists as NH000 at 21 mm and as NH00 at 30 mm, and the base in the panel decides which one fits. When a drawing lists a current only, the mounting width of the base that is already there is the reference, and a photo of the old link beside a rule is enough to confirm it.
Check the voltage suffix before the current. The plain 3NA38 part is rated 500 V AC and 250 V DC, the -6 suffix raises the AC rating to 690 V, and the -8 suffix on 125 A and 160 A marks a 400 V only link. A 690 V panel that receives the plain part runs the element above its rated voltage, and the failure shows up as a link that opens without a fault.
Lead time on NH links is usually a stock question rather than a production question, because the range is made in large volume. Where a specific size or a 690 V version is short, see lead time and availability for the alternatives, and shortage recovery when a panel is held up by one size.
The SUPERB Assembly team labels each link with its body size as well as its current, because a 100 A NH000 and a 100 A NH00 look alike in a bin and only one of them fits the base.
Q: Can you supply the NH link, the base and the fuse puller on one list for a panel, with the body size confirmed against the base already fitted?
A: Yes. Send the base size, the current, the voltage and the class, and the SUPERB Tech team returns the link, the base and the puller as one line with the body size confirmed.
Why Panel Builders Buy NH Fuses From SUPERB
- Body size on every row: the mounting width is a column, not a footnote, so the base in the panel can be matched before the order is placed.
- Voltage suffix explained: the 500 V, 690 V and 400 V only versions are separated, which removes the most common wrong part on this family.
- Base and link on one page: the three pole base, the single pole base and the puller sit beside the links, so a feeder is quoted as one line.
- DC rating stated: the 440 V DC figure on the larger bodies is written per part, which decides whether a battery string can be protected by the same link.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Fuse Switch Disconnectors for Panel Isolation, Fuse Holders and Clips for Board Level Protection, Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads, DIN Rail Terminal Blocks for Control Panel Wiring.