PV and DC Surge Protective Devices for String Combiners

DC surge arresters for the string side of a photovoltaic plant, rated 1000 V or 1500 V continuously. Type 2 modules carry 25 kA to 40 kA at 8/20, and the type 1 version adds 6.25 kA at 10/350 per pole. Short circuit current rating and the open circuit failure mode are stated, because a PV array cannot be switched off. Enclosure versions and DIN rail versions are listed with their protection level and response time.
quote now

Product Specifications

Product Overview

A photovoltaic array is a current source that cannot be switched off, and that single fact changes how a surge arrester is chosen. On an AC board the arrester is asked to discharge a surge and then return to a high impedance state, with the system behind a breaker that can be opened. On a string the array keeps feeding the arrester after the surge, so the device has to be rated for the short circuit current of the array and has to fail in a way that does not leave a conductive path across the string.

That is why the DC side has its own standard and its own parameters. The maximum continuous operating voltage Ucpv is the string voltage at the coldest expected temperature, not the nominal system voltage, because a module produces more voltage when it is cold. The short circuit current rating Iscpv is the array current the arrester can interrupt or withstand, and the end of life mode has to be an open circuit rather than a short, which is what the OCFM notation means on the DIN rail part.

The second decision is the class. A type 2 arrester inside a combiner box handles the induced surge on the DC cables. A type 1 arrester is used where a lightning current can reach the DC side directly, for example on a rooftop array with a short cable run to the inverter, and it is rated for a 10/350 impulse as well as the 8/20 wave. Fitting a type 2 part where the risk assessment asks for a type 1 is the usual reason a combiner is replaced after the first storm.

Key Specifications

ParameterValueNote
Typetype 2 / class II to EN 61643-31, or type 1 and 2 combinedthe DC standard, not the AC one
Maximum continuous operating voltage1000 V DC or 1500 V DCthe cold string voltage, not the nominal system figure
Short circuit current rating1000 A on the 1000 V enclosure version, 2000 A on the 1500 V rail versionthe array current the device can withstand
Nominal discharge current, 8/2012.5 kA on the enclosure version, 20 kA on the rail versionper pole to protective earth
Maximum discharge current, 8/2025 kA on the enclosure version, 40 kA on the rail version
Lightning impulse current, 10/3506.25 kA peak, 3.125 As charge on the type 1 part12.5 kA total per pole set
Total discharge current40 kA at 8/20 on both families12.5 kA at 10/350 on the type 1 part
Voltage protection levelup to 4 kV, 4.5 kV on the 1500 V part3.5 kV at 5 kA and 3.3 kV at 3 kA on the respective parts
Response time25 ns or lessboth families
Rated load current50 A on the rail versionthe arrester sits in parallel, this is the through current
End of life modeopen circuit failure mode, OCFMa shorted arrester on a string is a fire risk
EnclosureIP65, 94 x 94 x 81 mm, 426 g, three cable entries of 3 to 7 mmprewired enclosure for one MPP input
Mountingenclosure with cable entries, or DIN rail modulethe enclosure version needs no space in a separate box
Operating temperature-35 to +80 Coutdoor rated on the enclosure version
ApprovalsKEMA on the enclosure version, UL and IEC 61643-31 on the rail version

Included Models and Order Codes

The two families answer two different installation styles. The DEHNcube is a prewired enclosure with cable entries and IP65 protection, so it goes on the frame next to the combiner and needs no cabinet space; the part number carries the number of MPP inputs, 1M for one and 2M for two. The Phoenix VAL-MB part is a DIN rail module for a 1500 V system, rated as a combined type 1 and type 2, with an optional remote indication contact on the FM version. Values below are the ones on the maker data sheet; where a figure is not published for a variant, the cell says so.

Part numberFamilyUcpvIscpvDischarge currentNote
900 910 (DCU YPV SCI 1000 1M)DEHNcube1000 V DC1000 A12.5 kA nominal, 25 kA maximum at 8/20one MPP input, IP65, Up 4 kV, 426 g
900 920 (DCU YPV SCI 1000 2M)DEHNcube1000 V DC1000 Asame protective circuit per inputtwo MPP inputs in one enclosure
2905641 (VAL-MB-T1/T2 1500DC-PV/2+V)Phoenix Contact VAL-MB1500 V DC2000 A20 kA nominal, 40 kA maximum at 8/20, 6.25 kA at 10/350type 1 and 2, DIN rail, Up 4.5 kV, 50 A load current
VAL-MB-T1/T2 1500DC-PV/2+V-FMPhoenix Contact VAL-MB1500 V DC2000 Asame as the base partwith a remote indication contact for the monitoring system

Enclosure or DIN Rail

The same electrical function exists in two mechanical forms, and the form is decided by where the DC cables already run. The table below is the short version of that decision.

InstallationForm that fitsWhy
Combiner on the mounting frame, no cabinet spaceprewired IP65 enclosurecable entries and a transparent cover, no separate box to buy or seal
Combiner inside a cabinet with DIN railDIN rail moduleone module per MPP input, remote indication available on the FM version
Two MPP inputs at one point2M enclosure versionone enclosure, two protective circuits, one earth connection
Retrofit on an existing 1500 V inverterDIN rail type 1 and 2 modulethe type 1 rating covers the direct strike case without a second stage
Plant with a monitoring systemFM versionthe remote contact reports a spent module to the SCADA rather than to a lamp

Key Features

Ucpv quoted at the cold string voltage – 1000 V and 1500 V continuous ratings, because a cold module produces more voltage than its nominal figure.

Short circuit current rating stated – 1000 A and 2000 A, which is the parameter that separates a DC arrester from an AC one.

Open circuit failure mode – a spent module opens rather than shorts, which is the only safe failure on an array that cannot be switched off.

Type 1 and type 2 in one part – 6.25 kA at 10/350 plus 40 kA at 8/20 covers the direct and the induced case on a rooftop run.

Protection level and response time – 4 to 4.5 kV and 25 ns, the two figures an inverter DC input is compared against.

Two mechanical forms – prewired IP65 enclosure or DIN rail module, so the arrester follows the installation rather than the other way round.

Applications

PV surge arresters are fitted at three points on a plant, and the class follows from the point.

String combiner boxes on the array – the DC cables leave the box and run along the frame, so a type 2 arrester in a prewired enclosure handles the induced surge without taking cabinet space.

Inverter DC input on a rooftop plant – a short cable run from the array means a direct strike is credible, so a combined type 1 and 2 module on the DC side carries the 10/350 wave as well.

Battery racks and DC collection on storage plants – the same DC rules apply, and the short circuit current rating is checked against the rack rather than against the inverter.

The combiner monitoring board shares the enclosure with the arrester, so the SUPERB PCBA and the SUPERB PCB are checked against the same earth point and the same 1500 V clearance.

Sourcing and Cross-Reference

A PV arrester is bought with its enclosure or its rail space, and the second is the part that is discovered too late. The enclosure version arrives prewired with cable entries and a transparent cover, so it needs a frame position and an earth connection, while the rail version needs 4 modules of DIN rail and a short conductor to the earth bar. Quoting the part without the mounting is the usual reason a combiner is rebuilt on site.

The second point is the type. A type 2 module is the right part for the induced surge inside a combiner, and a type 1 module is the right part where a lightning current can reach the DC side. On a plant with an external lightning protection system the risk assessment normally asks for type 1 at the entry, and the two types are not interchangeable even when the discharge current figures look similar, because the 10/350 wave is a different test.

Where a specific module is on a long lead time, the alternatives are the other mounting form of the same electrical part, the FM version of the same module if remote signalling is not essential, or a second enclosure for two inputs. See lead time and availability for a specific number and BOM shortage recovery where a combiner is held up.

The SUPERB Assembly team keeps the arrester earth conductor as short as the enclosure allows, because a long earth lead adds inductance that the protection level does not account for.

Q: Can you confirm Ucpv at the lowest expected temperature and the short circuit current rating of the array before we fix the arrester type?

A: Yes. Send the string voltage at the lowest temperature, the array short circuit current, the mounting position and the required type, and the SUPERB Tech team returns the part.

Why Solar Builders Source DC Arresters From SUPERB

  1. DC parameters, not AC ones: Ucpv, Iscpv and the open circuit failure mode are on the page, which is what separates a DC arrester from a lookalike.
  2. Type stated per part: type 2 and combined type 1 and 2 are separate rows with their 10/350 ratings, so the risk assessment and the order agree.
  3. Both mounting forms: the prewired enclosure and the DIN rail module are listed together, so the form follows the installation.
  4. Protection level and response time: the two figures the inverter input is compared against are quoted per part rather than per family.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Surge Protective Devices for AC Distribution Boards, Surge Protective Devices for Signal and Data Lines, DC Isolator Switches for PV and Battery Strings, Photovoltaic Fuse Links for PV Strings and Battery Racks, Surge Counters and SPD Monitoring Units.