PV and DC Surge Protective Devices for String Combiners
Product Specifications
Product Overview
A photovoltaic array is a current source that cannot be switched off, and that single fact changes how a surge arrester is chosen. On an AC board the arrester is asked to discharge a surge and then return to a high impedance state, with the system behind a breaker that can be opened. On a string the array keeps feeding the arrester after the surge, so the device has to be rated for the short circuit current of the array and has to fail in a way that does not leave a conductive path across the string.
That is why the DC side has its own standard and its own parameters. The maximum continuous operating voltage Ucpv is the string voltage at the coldest expected temperature, not the nominal system voltage, because a module produces more voltage when it is cold. The short circuit current rating Iscpv is the array current the arrester can interrupt or withstand, and the end of life mode has to be an open circuit rather than a short, which is what the OCFM notation means on the DIN rail part.
The second decision is the class. A type 2 arrester inside a combiner box handles the induced surge on the DC cables. A type 1 arrester is used where a lightning current can reach the DC side directly, for example on a rooftop array with a short cable run to the inverter, and it is rated for a 10/350 impulse as well as the 8/20 wave. Fitting a type 2 part where the risk assessment asks for a type 1 is the usual reason a combiner is replaced after the first storm.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Type | type 2 / class II to EN 61643-31, or type 1 and 2 combined | the DC standard, not the AC one |
| Maximum continuous operating voltage | 1000 V DC or 1500 V DC | the cold string voltage, not the nominal system figure |
| Short circuit current rating | 1000 A on the 1000 V enclosure version, 2000 A on the 1500 V rail version | the array current the device can withstand |
| Nominal discharge current, 8/20 | 12.5 kA on the enclosure version, 20 kA on the rail version | per pole to protective earth |
| Maximum discharge current, 8/20 | 25 kA on the enclosure version, 40 kA on the rail version | |
| Lightning impulse current, 10/350 | 6.25 kA peak, 3.125 As charge on the type 1 part | 12.5 kA total per pole set |
| Total discharge current | 40 kA at 8/20 on both families | 12.5 kA at 10/350 on the type 1 part |
| Voltage protection level | up to 4 kV, 4.5 kV on the 1500 V part | 3.5 kV at 5 kA and 3.3 kV at 3 kA on the respective parts |
| Response time | 25 ns or less | both families |
| Rated load current | 50 A on the rail version | the arrester sits in parallel, this is the through current |
| End of life mode | open circuit failure mode, OCFM | a shorted arrester on a string is a fire risk |
| Enclosure | IP65, 94 x 94 x 81 mm, 426 g, three cable entries of 3 to 7 mm | prewired enclosure for one MPP input |
| Mounting | enclosure with cable entries, or DIN rail module | the enclosure version needs no space in a separate box |
| Operating temperature | -35 to +80 C | outdoor rated on the enclosure version |
| Approvals | KEMA on the enclosure version, UL and IEC 61643-31 on the rail version |
Included Models and Order Codes
The two families answer two different installation styles. The DEHNcube is a prewired enclosure with cable entries and IP65 protection, so it goes on the frame next to the combiner and needs no cabinet space; the part number carries the number of MPP inputs, 1M for one and 2M for two. The Phoenix VAL-MB part is a DIN rail module for a 1500 V system, rated as a combined type 1 and type 2, with an optional remote indication contact on the FM version. Values below are the ones on the maker data sheet; where a figure is not published for a variant, the cell says so.
| Part number | Family | Ucpv | Iscpv | Discharge current | Note |
|---|---|---|---|---|---|
| 900 910 (DCU YPV SCI 1000 1M) | DEHNcube | 1000 V DC | 1000 A | 12.5 kA nominal, 25 kA maximum at 8/20 | one MPP input, IP65, Up 4 kV, 426 g |
| 900 920 (DCU YPV SCI 1000 2M) | DEHNcube | 1000 V DC | 1000 A | same protective circuit per input | two MPP inputs in one enclosure |
| 2905641 (VAL-MB-T1/T2 1500DC-PV/2+V) | Phoenix Contact VAL-MB | 1500 V DC | 2000 A | 20 kA nominal, 40 kA maximum at 8/20, 6.25 kA at 10/350 | type 1 and 2, DIN rail, Up 4.5 kV, 50 A load current |
| VAL-MB-T1/T2 1500DC-PV/2+V-FM | Phoenix Contact VAL-MB | 1500 V DC | 2000 A | same as the base part | with a remote indication contact for the monitoring system |
Enclosure or DIN Rail
The same electrical function exists in two mechanical forms, and the form is decided by where the DC cables already run. The table below is the short version of that decision.
| Installation | Form that fits | Why |
|---|---|---|
| Combiner on the mounting frame, no cabinet space | prewired IP65 enclosure | cable entries and a transparent cover, no separate box to buy or seal |
| Combiner inside a cabinet with DIN rail | DIN rail module | one module per MPP input, remote indication available on the FM version |
| Two MPP inputs at one point | 2M enclosure version | one enclosure, two protective circuits, one earth connection |
| Retrofit on an existing 1500 V inverter | DIN rail type 1 and 2 module | the type 1 rating covers the direct strike case without a second stage |
| Plant with a monitoring system | FM version | the remote contact reports a spent module to the SCADA rather than to a lamp |
Key Features
Ucpv quoted at the cold string voltage – 1000 V and 1500 V continuous ratings, because a cold module produces more voltage than its nominal figure.
Short circuit current rating stated – 1000 A and 2000 A, which is the parameter that separates a DC arrester from an AC one.
Open circuit failure mode – a spent module opens rather than shorts, which is the only safe failure on an array that cannot be switched off.
Type 1 and type 2 in one part – 6.25 kA at 10/350 plus 40 kA at 8/20 covers the direct and the induced case on a rooftop run.
Protection level and response time – 4 to 4.5 kV and 25 ns, the two figures an inverter DC input is compared against.
Two mechanical forms – prewired IP65 enclosure or DIN rail module, so the arrester follows the installation rather than the other way round.
Applications
PV surge arresters are fitted at three points on a plant, and the class follows from the point.
String combiner boxes on the array – the DC cables leave the box and run along the frame, so a type 2 arrester in a prewired enclosure handles the induced surge without taking cabinet space.
Inverter DC input on a rooftop plant – a short cable run from the array means a direct strike is credible, so a combined type 1 and 2 module on the DC side carries the 10/350 wave as well.
Battery racks and DC collection on storage plants – the same DC rules apply, and the short circuit current rating is checked against the rack rather than against the inverter.
The combiner monitoring board shares the enclosure with the arrester, so the SUPERB PCBA and the SUPERB PCB are checked against the same earth point and the same 1500 V clearance.
Sourcing and Cross-Reference
A PV arrester is bought with its enclosure or its rail space, and the second is the part that is discovered too late. The enclosure version arrives prewired with cable entries and a transparent cover, so it needs a frame position and an earth connection, while the rail version needs 4 modules of DIN rail and a short conductor to the earth bar. Quoting the part without the mounting is the usual reason a combiner is rebuilt on site.
The second point is the type. A type 2 module is the right part for the induced surge inside a combiner, and a type 1 module is the right part where a lightning current can reach the DC side. On a plant with an external lightning protection system the risk assessment normally asks for type 1 at the entry, and the two types are not interchangeable even when the discharge current figures look similar, because the 10/350 wave is a different test.
Where a specific module is on a long lead time, the alternatives are the other mounting form of the same electrical part, the FM version of the same module if remote signalling is not essential, or a second enclosure for two inputs. See lead time and availability for a specific number and BOM shortage recovery where a combiner is held up.
The SUPERB Assembly team keeps the arrester earth conductor as short as the enclosure allows, because a long earth lead adds inductance that the protection level does not account for.
Q: Can you confirm Ucpv at the lowest expected temperature and the short circuit current rating of the array before we fix the arrester type?
A: Yes. Send the string voltage at the lowest temperature, the array short circuit current, the mounting position and the required type, and the SUPERB Tech team returns the part.
Why Solar Builders Source DC Arresters From SUPERB
- DC parameters, not AC ones: Ucpv, Iscpv and the open circuit failure mode are on the page, which is what separates a DC arrester from a lookalike.
- Type stated per part: type 2 and combined type 1 and 2 are separate rows with their 10/350 ratings, so the risk assessment and the order agree.
- Both mounting forms: the prewired enclosure and the DIN rail module are listed together, so the form follows the installation.
- Protection level and response time: the two figures the inverter input is compared against are quoted per part rather than per family.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Surge Protective Devices for AC Distribution Boards, Surge Protective Devices for Signal and Data Lines, DC Isolator Switches for PV and Battery Strings, Photovoltaic Fuse Links for PV Strings and Battery Racks, Surge Counters and SPD Monitoring Units.