Photovoltaic Fuse Links for PV Strings and Battery Racks
Product Specifications
Product Overview
A photovoltaic string cannot be switched off. The modules produce current whenever there is light, and a faulted string is fed by every other string in parallel with it. That reverse current is the fault a string fuse is there to clear, and it is a DC fault with no current zero, at a voltage that stays up all day. A gPV link is built for that duty: a DC rated body, a DC rated element and a breaking capacity that holds the arc at the string voltage.
The sizing rule is short and often applied loosely. The fuse rating must be at least 1.25 times the short circuit current of the string at standard test conditions, and it must not exceed the maximum series fuse rating that the module maker allows. Between those two numbers there is usually one or two standard ratings, so an 8.9 A string takes a 12 A link and a 13.9 A string takes a 20 A link. A larger fuse does not protect the module, a smaller one opens on a hot day.
The second half of the job is thermal. A fuse in a combiner box sits in the sun, in a sealed enclosure, next to other fuses, and its rating is quoted at a reference ambient. Above that ambient the link has to be derated, and the watts loss figure decides how much heat the box has to shed. This is the reason two 15 A links with the same voltage rating are not interchangeable when one has half the watts loss of the other.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Class | gPV to IEC 60269-6, type A | full range protection for a string, not a general purpose link |
| Rated voltage DC | 1000 V DC on the 10 x 38 mm body, 1500 V DC on the 10 x 112 mm body | the DC rating is the working voltage of the string |
| Rated current | 1 A to 30 A on 10 x 38 mm, 10 A to 25 A on 10 x 112 mm | standard steps, not every value in between |
| Breaking capacity | 20 kA from 1 A to 20 A, 50 kA at 25 A and 30 A | 50 kA on the 1500 V body as well |
| Body size | 10 x 38 mm and 10 x 112 mm | the holder and the box depth follow from the body |
| Pre-arcing I2t | 22 A2s at 15 A on the 10 x 38 mm part | the number a module withstand is compared against |
| Total I2t at 1000 V DC | 220 A2s at 15 A | measured with a 1 to 3 ms time constant |
| Watts loss | 1.7 W at 70 percent of rating, 2.9 W at 100 percent, on the 15 A part | 1.24 to 3.10 W across the 1500 V sizes |
| Time constant | 1 to 3 ms | DC test condition, stated with the breaking capacity |
| Terminals | ferrule, PCB tabs, crimp cap for 10 to 12 AWG and for 8 AWG | the crimp cap version is used where the holder is bolted |
| Standards | UL 248-19, IEC 60269-6, CSA | UL listed and CSA certified on the 10 x 38 mm range |
| Sizing rule | rating at least 1.25 times string Isc, and not above the module maximum series fuse rating | the second limit is the one that is usually missed |
| Ambient derating | per the maker curve above 40 C | a sealed combiner in the sun runs well above 40 C |
Included Models and Order Codes
The rows are grouped by body size, because the body decides the holder and the holder decides the box. The Littelfuse SPF range is quoted as SPF plus three digits for the ampere rating, and the packing suffix is part of the order number: T for a 10 piece pack, H for a 100 piece pack, and R for the PCB tab version. The Eaton Bussmann 10 x 38 mm range uses PV-amp-A10 plus a suffix, where F is the ferrule version and 1P or 2P points to the holder configuration. The Mersen 1500 V body is quoted as HP15M plus the ampere rating, with CC for the 10 to 12 AWG crimp cap and CC8 for the 8 AWG cap.
| Part number | Family | Voltage | Rated current | Breaking capacity | Note |
|---|---|---|---|---|---|
| SPF001 (0SPF001.T) | Littelfuse SPF | 1000 V DC | 1 A | 20 kA | 10 x 38 mm, 10 piece pack, H suffix for 100 |
| SPF005 (0SPF005.T) | Littelfuse SPF | 1000 V DC | 5 A | 20 kA | 10 x 38 mm ferrule |
| SPF010 (0SPF010.T) | Littelfuse SPF | 1000 V DC | 10 A | 20 kA | 10 x 38 mm ferrule |
| SPF015 (0SPF015.T) | Littelfuse SPF | 1000 V DC | 15 A | 20 kA | 10 x 38 mm ferrule |
| SPF020 (0SPF020.T) | Littelfuse SPF | 1000 V DC | 20 A | 20 kA | 10 x 38 mm ferrule |
| SPF025 (0SPF025.T) | Littelfuse SPF | 1000 V DC | 25 A | 50 kA | 10 x 38 mm ferrule |
| SPF030 (0SPF030.T) | Littelfuse SPF | 1000 V DC | 30 A | 50 kA | 10 x 38 mm ferrule |
| SPF015R | Littelfuse SPF | 1000 V DC | 15 A | 20 kA | PCB tab version for board mounted combiners |
| PV-15A10F | Eaton Bussmann | 1000 V DC | 15 A | 50 kA | 10 x 38 mm, 22 A2s pre-arcing, 220 A2s total |
| PV-15A10-1P | Eaton Bussmann | 1000 V DC | 15 A | 50 kA | 1P holder configuration |
| PV-15A10-2P | Eaton Bussmann | 1000 V DC | 15 A | 50 kA | 2P holder configuration |
| HP15M10R | Mersen Helios | 1500 V DC | 10 A | 50 kA | 10 x 112 mm ferrule, 1.24 W at 70 percent |
| HP15M15R | Mersen Helios | 1500 V DC | 15 A | 50 kA | 10 x 112 mm ferrule |
| HP15M20R | Mersen Helios | 1500 V DC | 20 A | 50 kA | 10 x 112 mm ferrule, 1.77 W at 70 percent |
| HP15M25R | Mersen Helios | 1500 V DC | 25 A | 50 kA | 10 x 112 mm ferrule, 2.21 W at 70 percent |
| HP15M20RCC | Mersen Helios | 1500 V DC | 20 A | 50 kA | crimp cap for 10 to 12 AWG, for bolted holders |
| HP15M25RCC8 | Mersen Helios | 1500 V DC | 25 A | 50 kA | crimp cap for 8 AWG |
String Sizing in One Table
The two limits are a lower bound from the string current and an upper bound from the module, and the fuse has to sit between them. The arithmetic below is the version that shows up on most utility and commercial roofs.
| String Isc at STC | Lower bound, 1.25 x Isc | Rating to order | Check against |
|---|---|---|---|
| 8.9 A | 11.1 A | 12 A | module maximum series fuse rating, usually 15 or 20 A |
| 9.8 A | 12.3 A | 15 A | holder rating and box temperature |
| 11.5 A | 14.4 A | 15 A | watts loss in a sealed combiner |
| 13.9 A | 17.4 A | 20 A | the 10 x 38 mm body carries 20 A at 20 kA |
| 18.5 A | 23.1 A | 25 A | 50 kA breaking capacity at this rating |
Key Features
DC rated body and element – the link is built for a DC arc at the string voltage, which is a different part from an AC fuse of the same current.
Two body sizes – 10 x 38 mm for string boxes and 10 x 112 mm for larger strings, with the terminals named so the holder matches.
Breaking capacity per rating – 20 kA up to 20 A and 50 kA at 25 and 30 A, because a larger string has more parallel current behind the fault.
I2t and watts loss published – pre-arcing and total I2t plus the watts loss, which are the two numbers that decide module protection and box temperature.
Packing suffix understood – T and H are the pack sizes and R is the PCB tab version, so a reorder does not arrive as a different mounting.
Crimp cap option – the 1500 V body is available with a 10 to 12 AWG or an 8 AWG crimp cap for bolted holders, where a ferrule clip is not used.
Applications
String fuses are fitted in three places, and the body and holder follow from where the link sits.
String combiner boxes – each string gets one link in a holder on a DIN rail, and the 10 x 38 mm body with a ferrule is the part that fits the standard holder.
Inverter DC input with integrated combiners – the links sit on a board or in a fused disconnect, and the PCB tab version keeps the assembly height down.
Battery racks and DC collection – a 1500 V body with a crimp cap protects a rack string where the holder is bolted to a busbar rather than clipped to a rail.
The combiner monitoring board is quoted with the link, so the SUPERB PCBA and the SUPERB PCB are checked against the same fuse rating and the same box temperature.
Sourcing and Cross-Reference
A string fuse order is usually a reorder, and the two things that change without notice are the packing suffix and the terminal. SPF015 and 0SPF015.H are the same link in different packs, and SPF015R is the same link with PCB tabs, so a purchase order that quotes the family without the suffix can arrive as something that does not fit the holder.
The second point is the derating. A combiner box in direct sun runs at 60 C or more inside, and a link rated at 25 A in a 25 C test is not a 25 A link at 60 C. The maker curve applies, and the usual outcome is that the next rating up is used together with a check that the module maximum series fuse rating still allows it. Where the two limits cross, the answer is a different module or a different string length, not a bigger fuse.
For a plant that is being repaired rather than built, the question is which link is in the holder and whether the same body is available. See lead time and availability for a specific rating and BOM shortage recovery where a combiner is waiting on one link.
The SUPERB Assembly team checks the crimp cap with a pull test rather than by eye, because a loose cap on a 1500 V string is a hot joint that appears a season later.
Q: Can you confirm the string current, the module maximum series fuse rating and the box temperature before we fix the fuse rating?
A: Yes. Send the string Isc, the module maximum series fuse rating, the string voltage and the box temperature, and the SUPERB Tech team returns the rating and the body that fit.
Why Solar Builders Source gPV Fuses From SUPERB
- Rating and I2t on the same row: the string current, the pre-arcing energy and the watts loss sit together, which is how a link is chosen against a module rather than against a price.
- Body and terminal named: 10 x 38 mm ferrule, PCB tab and 10 x 112 mm crimp cap are separated, so the link matches the holder that is already on the rail.
- Breaking capacity per rating: the 20 kA and 50 kA figures are attached to the ratings they belong to, which matters when strings are paralleled.
- Derating and sizing stated: the 1.25 times rule and its upper limit are written out, so the arithmetic is on the page and not in a handover note.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DC Isolator Switches for PV and Battery Strings, NH Fuse Links and DIN Rail Fuse Bases, Semiconductor and DC Fuses for Drive and Battery Protection, PV and DC Surge Protective Devices for String Combiners, Fuse Holders and Clips for Board Level Protection.