Non-Fused Switch Disconnectors for Panel and Machine Isolation

A non-fused disconnector gives a visible break without a fuse, which is what a maintenance lock out or a local isolator needs. Eight bodies cover 16 to 100 A with AC-23A ratings from 7.5 to 37 kW at 400 V. Insulation voltage is 750 V and impulse withstand is 8 kV, with a conditional short circuit rating of 50 kA behind a fuse. The handle and shaft are ordered separately, so the operating position can be chosen on the panel.
quote now

Product Specifications

Product Overview

A switch disconnector is a switch that can be locked in the open position and that shows a visible gap between the contacts. That combination is what makes it a disconnector rather than a switch: a maintenance team can see the break, apply a padlock and work on the downstream circuit. The non-fused version carries no fuse, so it isolates a feeder that is already protected upstream by a breaker or a set of NH links.

The rating that matters is AC-23A, the utilisation category for motor loads and mixed resistive and inductive loads. It is lower than the thermal current of the body, and much lower than the UL general purpose rating on the same part. A 40 A body in this range is rated 23 A in AC-23A at 415 V, and a buyer who reads the general purpose figure and connects a motor will run the contacts above their switching rating.

Two versions of the same current exist for different duties. The OT16 to OT80 range is a UL 508 general purpose switch, and the OT30, OT60 and OT100 are UL 98 rated, which is what a service entrance or a feeder disconnect requires in a North American panel. The difference is in the approval and in the short circuit behaviour, not in the outline, and it is the reason two parts with the same current carry different prices.

Key Specifications

ParameterValueNote
Poles3front operated, base mounted
Rated operational current, AC-23A16 A at OT16F3, 20 A at OT25F3, 23 A at OT40F3, 63 A at OT63F3at 380 to 415 V
Rated operational power, AC-23A7.5 kW to 37 kW at 400 to 415 Vwritten per part in the table below
Rated insulation voltage750 VIEC 60664-1
Rated impulse withstand voltage8 kVpollution degree 3
Rated short time withstand0.5 kA for 1 s on the small bodies, 1 kA on OT63F3Icw, rms
Conditional short circuit current50 kA behind a 40 A fuse at 415 Vthe fuse is the protection, the switch is the isolator
Degree of protectionIP20 at the frontfinger safe terminals
Mechanical durability20,000 operationsoperating cycles without load
Cable range0.75 to 10 mm2 on OT16 to OT40, 1.5 to 35 mm2 on OT63screw clamp terminals
Tightening torque0.8 N.m to 2 N.mper body, on the terminal screw
Mountingbase mounting, DIN rail or plate35 mm rail on the small bodies
Handleordered separately, knob or selectorshaft length sets the mounting depth
StandardsIEC 60947-3, UL 508 or UL 98 depending on the rangeUL 98 on OT30, OT60 and OT100

Included Models and Order Codes

The part number is a body size, and the digits are the UL general purpose current, not the AC-23A current. The F3 suffix marks three poles and a front operated mechanism, and a 6 in place of the 3 marks six poles for a three phase circuit with a switched neutral. The handle and the shaft are a separate order, and the shaft length is chosen by how deep the switch sits behind the door.

Part numberUL general purpose ratingAC-23A power at 400 VWidthCable rangeNote
OT16F320 A7.5 kW35 mm0.75 to 10 mm2smallest body, DIN rail, local isolator
OT25F330 A9 kW35 mm0.75 to 10 mm220 A in AC-23A at 415 V
OT30F330 A15 kW35 mm0.75 to 10 mm2UL 98 rated, service disconnect
OT40F340 A11 kW35 mm0.75 to 10 mm223 A in AC-23A at 415 V
OT60F360 A18.5 kW52.5 mm1.5 to 35 mm2UL 98 rated, feeder disconnect
OT63F360 A22 kW52.5 mm1.5 to 35 mm263 A in AC-23A at 415 V, 45 A at 500 V
OT80F380 A37 kW52.5 mm1.5 to 35 mm2largest body on 35 mm rail
OT100F3100 A37 kW70 mmon requestUL 98 rated, main disconnect

Where a Non-Fused Disconnector Belongs

The same body can be a local isolator, a feeder disconnect or a maintenance break, and the requirement changes with the position. The table below is the job and what it asks of the device.

PositionWhat it providesRequirementNote
Machine local isolatora visible break beside the motorlockable in the open positionAC-23A rating for the motor current
Feeder disconnectisolation of a sub boardUL 98 where the panel is North Americanprotection is upstream
Main disconnectisolation of the whole panellockable, marked, accessiblehandle through the door
Maintenance breaka gap for work on a drivevisible gap, padlockdo not rely on a contactor
Changeover dutysupply from mains or from a generatortwo devices with a mechanical interlocknever parallel the two sources

Key Features

AC-23A rating per part – the motor load rating is written on every row and is lower than the general purpose figure, which is the number that decides a motor feeder.

750 V insulation voltage – the body is rated above the 400 V and 500 V supplies it usually sits on, which leaves margin for a 690 V panel.

50 kA conditional short circuit – with a 40 A fuse in front, the assembly holds a 50 kA fault, so the switch can sit downstream of a protection device rather than beside the intake.

Finger safe IP20 front – the terminals are protected at the front, which is what an open panel door exposes to a maintenance hand.

Separate handle and shaft – the operating position is chosen on the panel, so the same body works with a direct knob or a door mounted selector.

20,000 operating cycles – the mechanical life is quoted for the range, which covers a machine isolator used several times a day.

Applications

These switches are bought by the isolation point on the drawing, and three cases cover most of the requests.

Local isolator beside a motor – a machine that is serviced with the panel live needs a break at the motor, and a 25 or 40 A body on the machine frame gives a visible gap that can be padlocked.

Feeder isolation inside a cabinet – a sub board or a drive group is isolated by a 63 or 80 A body on the rail, while the fault protection stays with the breaker upstream.

Mains and generator changeover – two disconnectors with a mechanical interlock give a changeover that cannot parallel the two sources, which is what a standby supply in a plant requires.

The isolation point is quoted with the board it feeds, so the SUPERB PCBA and the SUPERB PCB are checked on the same feeder list and the switch is sized from the cable protection upstream.

Sourcing and Cross-Reference

Read the AC-23A column, not the body size. A 63 A body is rated 63 A in AC-23A at 415 V but only 45 A at 500 V and 20 A at 690 V, so a 690 V motor feeder on a 63 A body is running the contacts well above their switching rating. The voltage of the supply has to be quoted with the current.

Order the handle and the shaft with the body. The switch arrives without either, and a panel that is assembled before the handle arrives cannot be closed. The shaft length is set by the depth from the switch to the door, and the handle type is set by whether the door is opened or the switch is operated through it.

Bodies are a stock item up to 80 A and a lead time item at 100 A. Where a size is short, see lead time and availability, and shortage recovery when a panel is waiting on one body and one handle.

The SUPERB Assembly team fits the handle at the height the door allows and records the shaft length, because a handle that fouls the door is found only at commissioning.

Q: Can you supply the disconnector with the matching handle and shaft, and confirm the AC-23A rating for the supply voltage of the panel?

A: Yes. Send the supply voltage, the load current, the fault level and whether the panel is North American, and the SUPERB Tech team returns the body, the handle and the shaft.

Why Panel Builders Buy Disconnectors From SUPERB

  1. AC-23A current stated: the motor rating sits beside the general purpose rating, so a feeder is not sized from the wrong column.
  2. Voltage dependence explained: the fall in AC-23A current from 415 V to 690 V is written down, which is where a 690 V panel usually goes wrong.
  3. UL 98 and UL 508 separated: the two approvals are marked per part, so a North American feeder disconnect is not ordered as a general purpose switch.
  4. Handle and shaft noted: the page says what is not in the box, which avoids a panel that cannot be commissioned.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Fuse Switch Disconnectors for Panel Isolation, NH Fuse Links and DIN Rail Fuse Bases, Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads, DC Isolator Switches for PV and Battery Strings.