Braking Resistors for Variable Speed Drives
Product Specifications
Product Overview
When a drive decelerates a load faster than the load would stop by itself, the motor becomes a generator and pushes energy back into the DC bus. A small amount goes into the bus capacitors and the rest lifts the bus voltage until the drive trips on overvoltage. A braking resistor is the path that lets that energy out as heat, switched by a braking transistor inside the drive.
The resistor is not chosen by the motor power. It is chosen by the braking cycle, which is written as a torque level and a time inside a period. Three cycles cover most machines: a light cycle for a conveyor with low inertia, a medium cycle for high inertia and frequent stops, and a severe cycle for a hoist or a machine with vertical movement, where the load has to be held while it comes down.
That is why the same drive can take a 100 ohm 1.7 kW part or a 100 ohm 0.1 kW part. The ohmic value sets the peak braking current and is fixed by the drive, while the average power sets the mass of the resistor and is fixed by the cycle. Buying a resistor on ohms alone gives a part that either trips the drive on overcurrent or burns out after a month.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Ohmic value | 5 to 100 ohm at 20 C | sets the peak braking current, fixed by the drive |
| Average power | 0.1 kW to 32 kW at 50 C | set by the braking cycle, not by the motor |
| Degree of protection | IP20 for the small bodies, IP23 for the large ones | resistor sits outside the enclosure but under a cover |
| Thermal protection | thermal switch at 120 C or drive monitoring | the contact is wired back to the drive or to a relay |
| Braking cycles | light, medium and severe | 1.5 Tn for 0.8 s per 40 s, 1.35 Tn for 4 s per 40 s, 1.65 Tn for 6 s per 120 s |
| Ambient temperature | 0 C to +50 C in operation | the average power figure is quoted at 50 C |
| Storage temperature | -25 C to +70 C | before first energisation |
| Electrical connection | terminal up to 10 mm2 on the resistor | 2.5 mm2 to the thermal switch |
| Supply voltage of the DC bus | 380 to 480 V class on the medium range | 500 to 690 V class parts exist separately |
| Mounting | vertical, air inlet at the bottom | do not obstruct the inlet or the outlet |
| Standards | IEC 60322, EN 60322 | power resistors for drive applications |
Included Models and Order Codes
The part number carries the cycle and the drive frame. The 773x family is the light cycle, 774x the medium cycle and 775x the severe cycle, and the last digit rises with the drive frame. The same number can be used for a light cycle on a large frame or a severe cycle on a small one, so the cycle has to be quoted with the order.
| Part number | Ohmic value | Average power at 50 C | Cycle | Enclosure | Weight |
|---|---|---|---|---|---|
| VW3A7730 | 100 ohm | 0.1 kW | light, 1.5 Tn for 0.8 s per 40 s | IP20 | 1.5 kg |
| VW3A7731 | 60 ohm | 0.16 kW | light | IP20 | 2.0 kg |
| VW3A7732 | 28 ohm | 0.3 kW | light | IP20 | 3.0 kg |
| VW3A7733 | 16 ohm | 1.1 kW | light | IP20 | 4.0 kg |
| VW3A7734 | 10 ohm | 1.1 kW | light | IP20 | 5.5 kg |
| VW3A7735 | 8 ohm | 1.1 kW | light | IP20 | 5.5 kg |
| VW3A7736 | 5 ohm | 1.9 kW | light | IP23 | 18.0 kg |
| VW3A7740 | 100 ohm | 0.26 kW | medium, 1.35 Tn for 4 s per 40 s | IP20 | 2.5 kg |
| VW3A7741 | 60 ohm | 0.5 kW | medium | IP20 | 4.5 kg |
| VW3A7742 | 28 ohm | 1.1 kW | medium | IP20 | 4.0 kg |
| VW3A7743 | 16 ohm | 2.2 kW | medium | IP20 | 7.0 kg |
| VW3A7744 | 10 ohm | 3.4 kW | medium | IP20 | 11.5 kg |
| VW3A7745 | 8 ohm | 3.8 kW | medium | IP23 | 23.0 kg |
| VW3A7746 | 5 ohm | 6.9 kW | medium | IP23 | 27.0 kg |
| VW3A7750 | 100 ohm | 1.7 kW | severe, 1.65 Tn for 6 s, Tn for 54 s per 120 s | IP20 | 5.5 kg |
| VW3A7751 | 60 ohm | 2.9 kW | severe | IP20 | 8.3 kg |
| VW3A7752 | 28 ohm | 5.1 kW | severe | IP23 | 25.0 kg |
| VW3A7753 | 16 ohm | 14 kW | severe | IP23 | 47.0 kg |
| VW3A7754 | 10 ohm | 19 kW | severe | IP23 | 67.0 kg |
| VW3A7755 | 8 ohm | 25 kW | severe | IP23 | 86.0 kg |
| VW3A7756 | 5 ohm | 32 kW | severe | IP23 | 120.0 kg |
Reading a Braking Cycle Before Selecting a Resistor
A cycle is written as a torque, a braking time and a period, and two cycles with the same average power can need different resistors because the peak is different. The table below is the three cycles used in this range, in the wording of the drive documentation.
| Cycle | Braking torque | Braking time | Period | Typical machine |
|---|---|---|---|---|
| Light | 1.5 Tn | 0.8 s | 40 s | conveyor, fan, horizontal axis with low inertia |
| Medium | 1.35 Tn | 4 s | 40 s | high inertia load, frequent starts and stops |
| Severe | 1.65 Tn for 6 s and 1 Tn for 54 s | 60 s total | 120 s | hoist, lift, vertical axis |
| Custom | as measured | as measured | as measured | a cycle that does not fit the three above |
Key Features
Cycle stated per part – the table says which of the three cycles the part is rated for, so a severe duty hoist is not fitted with a light cycle body of the same ohmic value.
Average power at 50 C – the power figure is quoted at the ambient the resistor actually sees, which is the number the enclosure airflow has to remove.
Ohmic value at 20 C – resistance is quoted cold, so the tolerance and the temperature rise of the element are not hidden in the figure.
IP20 and IP23 bodies – the small parts are IP20 for mounting beside a drive and the large ones are IP23, which keeps a finger out of a 32 kW element.
Thermal switch at 120 C – a normally closed contact opens when the element overheats and is wired back to the drive or to a relay, so a stalled cycle does not end in a fire.
Terminal and cable range – 10 mm2 on the element and 2.5 mm2 on the switch, which is what a panel wire and a drive terminal actually take.
Applications
Resistors are bought by the machine motion, and these three cover most of the requests we see.
Hoists and vertical axes – a load that is lowered has to be held and braked continuously, which is a severe cycle, and the resistor has to absorb 1.65 times rated torque for six seconds inside a two minute period.
High inertia conveyors – a loaded conveyor keeps moving after the drive stops, and the medium cycle resistor takes the four second braking event without the bus reaching its trip level.
Fast machine cycles – a machine that stops and starts every few seconds produces short braking events with little time to cool, and the light cycle part is sized on the average power of that pattern.
The braking circuit is quoted with the control board that monitors it, so the SUPERB PCBA and the SUPERB PCB share one terminal list and the thermal contact lands on an input that is actually wired.
Sourcing and Cross-Reference
Quote the cycle with the order. Two parts can share an ohmic value and differ by a factor of twenty in average power, and a light cycle body fitted to a hoist will fail within weeks. Where the machine cycle is not measured yet, the drive documentation gives a starting point and the measured cycle can replace it later.
The ohmic value is a limit, not a preference. A value below the minimum for the drive raises the braking current above what the braking transistor can switch, and the drive trips or the transistor fails. A value far above the minimum gives a weak braking torque and a long stop, which is why the drive manual gives a window rather than a single number.
Large resistors are a production item and the lead time follows the element. Where a size is not on the shelf, see lead time and availability, and shortage recovery when a machine is waiting on one resistor to be commissioned.
The SUPERB Assembly team wires the thermal switch to a separate pair of terminals rather than in series with the element, because a resistor that opens the element circuit still leaves the drive able to run.
Q: Can you match a braking resistor to the drive and the machine cycle, and supply the thermal switch wiring on the same list?
A: Yes. Send the drive reference, the ohmic value from the manual and the machine cycle, and the SUPERB Tech team returns the resistor, its enclosure and the switch wiring.
Why Machine Builders Buy Braking Resistors From SUPERB
- Cycle on the row: light, medium and severe are separate rows, so the resistor is bought by the motion of the machine rather than by the drive frame alone.
- Power at the real ambient: the figure is quoted at 50 C, which is what a cabinet interior reaches and what the cooling has to remove.
- Enclosure and weight given: IP rating and mass are listed, so a 120 kg element is not ordered for a wall mounted panel.
- Switch wiring included: the thermal contact and its cable size are part of the part, which is the piece usually missing from a resistor quote.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Line Reactors and Motor Chokes for Variable Speed Drives, Brake Rectifiers and Motor Brake Modules, Soft Starters for Motor Starting, Motor Protection Circuit Breakers for Panel Feeders, Contactors and Reversing Contactors for Motor Loads.