Contact Us

Industrial Plugs and Sockets for Machine Power

Plugs, connectors and wall sockets to IEC 60309 for machines that are moved, serviced or swapped. Ratings run from 16 A to 63 A in 3, 4 and 5 pole versions, at 110, 230, 400 and 500 V. The clock position and the colour code the voltage, so a 400 V plug cannot enter a 230 V socket. IP44 covers indoor panels and IP67 covers washdown bays, with the cable range stated per part.
quote now

Product Specifications

Product Overview

An industrial plug and socket is a connector with a mechanical rule built in. The earth pin sits at a clock position that belongs to a voltage, and the housing colour repeats it: yellow for 110 V, blue for 230 V, red for 400 V. A 400 V plug will physically not enter a 230 V socket, and that single feature is why the format survives on machines that are moved between sites by people who did not wire them.

The other half of the format is current and poles. 16 A and 32 A share a body size within a family, 63 A steps up to a larger shell with frame terminals and a pilot contact, and the pole count decides whether the machine gets a neutral. A 3 pole plug gives phase, neutral and earth on single phase, a 4 pole gives three phases and earth without a neutral, and a 5 pole gives three phases, neutral and earth, which is what most modern machines with a 230 V control circuit need.

Sealing is the third decision, and it is not a detail. IP44 is splash resistant and belongs inside a building, on a panel front or a bench. IP67 is dust tight and survives a hose, which is what a washdown bay, a food line or an outdoor skid needs. The two look similar on a data sheet and differ in the cap, the seal and the cable gland, so the same 16 A 5 pole body is a different part number at IP44 and at IP67.

Key Specifications

Parameter16 A32 A63 A
StandardIEC 60309-2IEC 60309-2IEC 60309-2
Poles3, 4 or 54 or 54 or 5, plus 7 pole specials at 16 A
Nominal voltage110, 230, 400 or 500 V230, 400 or 500 V400 V, 500 V on request
Frequency50 to 60 Hz50 to 60 Hz50 to 60 Hz
Clock position4 h yellow, 6 h blue and red6 h red, 7 h black6 h red, 7 h black
SealingIP44 or IP67IP44 or IP67IP67
Connectionscrew terminalsscrew terminalsframe terminals, PZ2 or slot
Cable range1 to 2.5 mm22.5 to 6 mm26 to 16 mm2
Pilot contactnonenoneone pilot contact, used for interlock
Housing materialPA6PA6PA6
Ambient temperature-25 to +40 C, +55 C on some types-25 to +40 C-25 to +40 C

Included Models and Order Codes

Mennekes type numbers group by family and by shell size, and the family name on the part tells you which one you are holding: AM-TOP covers 16 and 32 A with a single part body, POWERTOP Plus and POWERTOP Xtra cover 63 A with frame terminals, and the DUO wall sockets add a mechanical interlock that will not let a plug be removed under load. The 247 and 509 pair is the 110 V 3 pole set, plug and connector, and they only mate with each other.

Part numberTypeCurrentPolesVoltage and clockSealingCable rangeWeight
247AM-TOP plug16 A3 p110 V, 4 h, yellowIP441 to 2.5 mm2132 g
509AM-TOP connector16 A3 p110 V, 4 h, yellowIP441 to 2.5 mm2on request
21362AM-TOP plug16 A5 p400 V, 6 h, redIP671 to 2.5 mm2210 g
24670AM-TOP plug with cap16 A5 p400 V, 6 h, redIP671 to 2.5 mm2261 g
742AM-TOP plug16 A7 p400 V, 6 h, redIP441 to 2.5 mm2195 g
20709AM-TOP plug32 A4 p400 V, 6 h, redIP672.5 to 6 mm2316 g
24770AM-TOP plug with cap32 A5 p400 V, 6 h, redIP672.5 to 6 mm2415 g
3308POWERTOP Plus plug63 A4 p400 V, 6 h, redIP676 to 16 mm2800 g
3325POWERTOP Plus plug63 A5 p400 V, 6 h, redIP676 to 16 mm2848 g
24870POWERTOP Xtra R plug with cap63 A5 p400 V, 6 h, redIP676 to 16 mm2880 g
7130wall mounted socket16 A5 p400 V, 6 h, redIP672.5 mm2 terminals988 g
7150wall mounted socket with RCD16 A5 p400 V, 6 h, redIP672.5 mm2 terminals1388 g
7292DUO wall socket, switched and interlocked16 A5 p400 V, 6 h, redIP672.5 mm2 terminals2055 g
7626DUO wall socket, horizontal, interlocked16 A5 p400 V, 6 h, redIP670.5 to 4 mm21360 g

Colour and Clock Position Are the Same Rule

The colour of the housing and the hour position of the earth pin carry the same information, and both come from the standard rather than from the maker. Reading either one tells you what the part will mate with, which is the fastest check on a site where the label has worn off.

Nominal voltageClock positionHousing colourTypical use
110 V4 hyellowsite tools and temporary lighting from a 110 V site transformer
230 V6 hbluesingle phase machines and bench equipment with a neutral
400 V6 hredthree phase machines, 4 pole without neutral and 5 pole with neutral
500 V7 hblackthree phase machines on a 500 V supply, mostly marine and heavy plant

Key Features

Clock position prevents a wrong voltage – the earth pin sits at 4 h for 110 V, 6 h for 230 V and 400 V and 7 h for 500 V, so a plug will not enter a socket of another voltage even when the shells look the same size.

IP67 on the 16 and 32 A bodies – dust tight and protected against a hose, with the seal carried by the cap and the gland rather than by the joint between the two halves of the shell.

Frame terminals on the 63 A parts – 6 to 16 mm2 conductors land in a frame terminal tightened to 2 Nm with a PZ2 or a slot driver, which takes the cable sizes a 63 A feed actually uses.

Pilot contact on 63 A – one pilot contact is used by the interlock circuit so a plug cannot be pulled under load where the socket is switched and interlocked.

Single part body on AM-TOP – the shell, the gland and the strain relief are one moulding, so there is no separate cable gland to order and no joint to leave loose.

Switched and interlocked wall sockets – the DUO bodies combine a switch, a mechanical interlock and a padlockable cover, which is what a maintenance bay needs where the plug is the only isolation point.

Applications

The format is chosen by how the machine is powered and moved. These three cover most of the orders behind this family.

Machine tools and test benches – a 16 A 5 pole IP67 plug and a wall socket give a machine a single isolation point that a service engineer can pull without tools, and the 400 V keyway keeps it away from a 230 V outlet.

Washdown and food lines – IP67 bodies with caps on both the plug and the socket are the normal choice where a hose is used at the end of a shift, and the cable gland range decides the cable that can be used.

Site power and temporary distribution – 110 V yellow 4 h parts from a site transformer, with the 3 pole set used on hand tools and the 5 pole set used where a neutral is needed for control.

The power entry is quoted with the machine harness, so the SUPERB PCBA and the SUPERB PCB are checked against the same current budget and the plug rating agrees with the breaker feeding it.

Sourcing and Cross-Reference

Match the pair, not the plug alone. A plug and a socket of the same current and pole count from different families can share a shell size and still not mate, and the interlocked DUO sockets only accept the matching shell. Where a machine arrives with a plug already fitted, the socket has to be ordered to the same family and clock position, and the family name is on the body rather than in the drawing.

Check the cable before the current. A 32 A plug takes 2.5 to 6 mm2 and a 63 A part takes 6 to 16 mm2, so a 63 A socket fed with a 4 mm2 cable is limited by the cable and not by the connector. On a long run the volt drop decides the conductor, and the connector follows from it.

Sealing and interlock are the two options that change the part number most often. An IP44 body and an IP67 body of the same rating are not interchangeable on a washdown line, and a switched interlocked socket costs more but removes the need for a separate isolator at the machine. See lead time and availability when a specific shell is short, and shortage recovery when a panel or a machine is waiting on the connector alone.

The SUPERB Assembly team lands the phase conductors on the frame terminal in the order marked inside the shell, because a swapped pair on a 400 V plug is a rotating machine running backwards.

Q: Can you supply the plug, the matching socket and the cable gland as one matched set, so the machine does not arrive with a plug that has no socket?

A: Yes. Send the supply voltage, the current, the pole count and whether the bay is washed down, and the SUPERB Tech team returns the plug, the socket and the gland that mate.

Why Machine Builders Buy Industrial Plugs and Sockets From SUPERB

  1. Voltage, clock position and colour on one line: each part is listed with the voltage, the hour position and the housing colour, so a wrong-voltage pair is caught before the order.
  2. Cable range stated: the conductor range per shell is written beside the part, which is what decides whether the gland will close on the cable in hand.
  3. IP44 and IP67 side by side: both sealing levels are quoted in the same list, so a washdown bay and an indoor panel do not end up with the same body by accident.
  4. Matching socket for every plug: plugs, connectors and wall sockets are quoted together, including the switched interlocked bodies, so a machine leaves with a complete power entry.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN and Circular Connectors for Panel Wiring, Cable Glands and Strain Relief Bushings for Enclosure Entries, DC Isolator Switches for PV and Battery Strings, Control Transformers for Panel Control Voltage, Enclosure Air Conditioners for Sealed Cabinet Cooling.