Enclosure Air Conditioners for Sealed Cabinet Cooling
Product Specifications
Product Overview
A sealed cabinet cannot be cooled with filtered air. Once the enclosure has to hold an IP rating, the heat has to leave through a refrigeration circuit, and the cooling unit becomes the largest single item on the panel after the drive.
The Blue e+ wall mounted range covers 1.6, 2.0, 2.6, 4.0 and 5.5 kW at L35 L35, which is 35 C inside and 35 C outside. The same unit at L35 L50, a 50 C ambient, gives less: the 1.6 kW model drops to 1.2 kW and the 2.6 kW model to 1.7 kW. Sizing on the headline figure for a site that sees 45 C is how a cabinet ends up hot in July.
Every unit in the range takes either 110 to 240 V single phase or 380 to 480 V three phase from the same model number, which removes the voltage variant from the spare parts list. The internal circuit is IP55, the refrigerant is R-513A, and condensate is evaporated inside the unit so no drain line leaves the cabinet.
Key Specifications
| Model | Cooling L35 L35 | Cooling L35 L50 | Supply | Power input | Airflow internal / external | W x H x D | Protection |
|---|---|---|---|---|---|---|---|
| SK 3185.830 | 1.6 kW | 1.2 kW | 110 - 240 V 1~, 380 - 480 V 3~ | 0.54 - 0.61 kW | 700 / 895 m3/h | 400 x 950 x 310 mm | IP55 internal |
| SK 3185.530 | 1.6 kW | 1.2 kW | 110 - 240 V 1~, 380 - 480 V 3~ | 0.54 - 0.61 kW | 700 / 895 m3/h | 400 x 950 x 310 mm | IP55 internal, stainless |
| SK 3186.930 | 2.0 kW | 1.29 kW | 110 - 240 V 1~, 380 - 480 V 3~ | 0.73 kW | 1250 / 1250 m3/h | 450 x 1600 x 294 mm | IP55 internal |
| SK 3187.930 | 2.6 kW | 1.7 kW | 110 - 240 V 1~, 380 - 480 V 3~ | 1.05 kW | 1250 / 1250 m3/h | 450 x 1600 x 294 mm | IP55 internal |
| SK 3188.940 | 4.0 kW | - | 380 - 480 V 3~ | 1.45 kW | 2300 / 2300 m3/h | 450 x 1600 x 393 mm | IP55 internal |
| SK 3189.940 | 5.5 kW | - | 380 - 480 V 3~ | 2.35 kW | 2300 / 2300 m3/h | 450 x 1600 x 393 mm | IP55 internal |
Included Models and Order Codes
Model numbers below carry the material and the output. The 3185 frame is a 400 x 950 mm wall unit with a 383 x 929 mm cut-out; the larger frames use a taller cut-out and need two people to lift.
| Part number | Cooling output | Material | Cut-out | Notes |
|---|---|---|---|---|
| 3185.830 | 1.6 kW | Sheet steel, RAL 7035 | 383 x 929 mm | Standard wall unit |
| 3185.530 | 1.6 kW | Stainless steel 1.4301 | 383 x 929 mm | Wash down and food areas |
| 3186.930 | 2.0 kW | Sheet steel, RAL 7035 | Tall frame | 1250 m3/h internal fan |
| 3187.930 | 2.6 kW | Sheet steel, RAL 7035 | Tall frame | 1250 m3/h internal fan |
| 3188.940 | 4.0 kW | Sheet steel, RAL 7035 | Tall frame | Three phase only |
| 3189.940 | 5.5 kW | Sheet steel, RAL 7035 | Tall frame | Three phase only |
Accessories and Service Parts
The IoT interface turns the unit into a monitored asset; the filter mats and the metal filter are consumables and belong in the first order, not in a later one.
| Part number | Part | Fits | Notes |
|---|---|---|---|
| 3124.300 | IoT interface | Blue e+ cooling units | Remote monitoring and alarms |
| 3124.400 | Temperature sensor | Blue e+ cooling units | For the IoT interface |
| 3285.800 | Filter mat set | 3185 frame | 3 pcs per pack |
| 3285.810 | Metal filter | 3185 frame | Washable |
| 3355.200 | Connection box cover | Blue e+ units | Optional since 2024 |
| 3355.210 | Connection box cover, stainless | Blue e+ units | Optional since 2024 |
Key Features
Cooling output at two ambients – the L35 L35 and L35 L50 figures are both quoted, because a 50 C site does not get the catalogue headline.
One model, two voltages – 110 to 240 V single phase and 380 to 480 V three phase on the same part number, so a spare fits either supply.
Speed controlled fans and heat pipe – the unit modulates instead of switching on and off, which is where the energy saving comes from.
Condensate evaporated inside – no drain line through the cabinet wall, which keeps the IP rating and removes a maintenance point.
RiNano condenser coating – hydrophobic coating on the condenser, so dust and water run off rather than matting the fins.
Touch display and IoT option – set points and alarms are readable at the unit, and the 3124.300 interface puts them on the network.
Applications
Cooling units are chosen by heat load and ambient. Three patterns repeat.
Machine and drive cabinets – 1.6 to 2.6 kW units on inverter and servo cabinets where the heat load is steady and the ambient is inside the hall.
Outdoor and semi-outdoor enclosures – units rated for the ambient range, mounted on the shaded side and protected by the recommended surge device.
Food and pharmaceutical panels – stainless 3185.530 units where the cabinet is washed down and a painted finish would not last.
Cooling units are quoted with the enclosure, and the SUPERB PCBA and the SUPERB PCB are checked against the same heat load calculation before the cut-out is punched.
Sourcing and Cross-Reference
Calculate the heat load first, then add the solar gain for an outdoor cabinet. A unit sized on the internal losses alone will run at full speed all afternoon and still lose the set point.
Use the L35 L50 figure for any site that sees more than 40 C. The difference between 2.6 kW and 1.7 kW is the difference between a 45 C cabinet and a 55 C one.
Plan the cut-out and the lifting. The 1.6 kW frame needs a 383 x 929 mm opening and weighs enough to need two people; the larger frames are taller and heavier again.
Protect the supply. Rittal specifies a surge device for these units: Uc 275 V, In 20 kA, Imax 40 kA, Up 1.5 kV below 460 V. The matching devices are on surge protective devices for AC distribution boards.
The SUPERB Assembly team mounts the unit on the cut-out before the internal components go in, because the fixing bolts are reached from inside the cabinet.
Q: Will the unit hold 35 C inside when the outside air reaches 50 C?
A: Yes. Send the heat load in watts, the ambient temperature and the cut-out size; the SUPERB Tech team quotes the unit that holds the internal temperature at that ambient.
Why Builders Buy Enclosure Cooling From SUPERB
- Sized on the real ambient: the quote states the output at L35 L50 as well as L35 L35, so the hot day is not a surprise.
- Spare parts per unit: one model covers two supply voltages, so the spare fits either line.
- Consumables in the first order: filter mats and the metal filter are quoted with the unit.
- Monitoring ready: the IoT interface and sensor are quoted with the cooling unit where the panel is on a network.