DC Axial Fans for Enclosure Cooling
Product Specifications
Product Overview
A fan does not cool an enclosure, it moves air through it. The heat has to leave through the wall, through a vent or through the air the fan pushes, and the fan only decides how much air passes in a given time. That is why the first number in a fan selection is the wattage inside the box and the second is the rise the contents will accept, with the airflow following from those two rather than from the size of the hole that is already punched.
The rule of thumb for a sealed enclosure with a fan and a filtered inlet is airflow in CFM equal to 3.16 times the watts divided by the allowed rise in degrees F. A 100 W box that may rise 10 F therefore needs about 32 CFM, and that is the figure the fan has to deliver at the pressure the filter and the louvre impose rather than in free air. A 40 CFM fan on a bench is a 25 CFM fan behind a dirty filter, which is the gap that catches most first builds.
The working point is where the fan curve crosses the system impedance curve, and a filter and a louvre move that crossing to the left. A fan with a high static pressure at low flow is the one for a dense filter or a long duct, and a fan with a high free air figure is the one for an open panel. The 40 mm parts on this page show the spread: 7 CFM at 0.12 in H2O on the thin frame, 19.6 CFM at 1.38 in H2O on the 28 mm frame, and 31.3 CFM at 3.12 in H2O on the high speed part. Putting the thin frame where the high pressure part belongs gives a fan that spins fast and moves almost nothing.
Size and noise trade against each other, and the trade is steep. A 120 mm frame at 1900 rpm moves 70 CFM at 29 dBA, while a 40 mm frame has to run at 14600 rpm to move 20 CFM and does it loudly. Where there is room, the larger slower fan is quieter and lasts longer, and where there is no room, the high speed small fan is the only option and the noise has to be planned around with a rubber mount and a duct.
Voltage follows the rail that is already in the cabinet. 12 V and 24 V are the usual industrial rails, 48 V is the telecom rail and is the one that keeps the current down on a long loom, and 5 V parts exist for a small instrument. Current matters twice: the steady draw has to sit inside the supply budget, and the inrush at start has to sit inside the fuse. A fan that draws 0.95 A at 12 V is a fan that needs a 2 A rail with margin, and four of them on one rail is a different supply.
Bearing choice sets the life and the mounting. A dual ball bearing part is listed at 70,000 hours L10 at 40 C and can be mounted in any orientation, which is what a cabinet door fan needs. A sleeve bearing part is cheaper and quieter when it is new, but it has to be mounted shaft horizontal and it wears faster in a hot box. A vapo or a sealed sleeve part sits between the two, and the sealed sleeve is the one for a dusty workshop where a plain sleeve fills up and seizes.
The options on the lead wires decide how the fan reports itself. Two wires are power only. Three wires add a tachometer output that the controller can read to tell a stopped fan from a slow one. Four wires add a PWM input for speed control, and a separate alarm output is available on the parts that carry it. In a cabinet that is monitored, the tachometer is the difference between an alarm that means something and a temperature trip that arrives after the damage.
Environment is the last filter. The standard parts run from minus 20 C to plus 65 C, which covers an outdoor cabinet in most climates. A washdown or an outdoor coastal cabinet needs an IP rated version, and the IP68 and IP69K parts on this page are the ones for a hose and a salt fog. A fan is also a hole in the enclosure: the finger guard keeps a hand out, the filter keeps the dust out, and both raise the impedance the fan has to work against.
Key Specifications
| Parameter | Value | Notes |
|---|---|---|
| Frame sizes | 40, 60, 80, 92 and 120 mm | 10, 20, 25 and 28 mm thick |
| Rated voltage | 5, 12, 24 and 48 V DC | 48 V for telecom rails |
| Bearing types | Sleeve, vapo, sealed sleeve, dual ball | Dual ball for any mounting angle |
| Airflow | 7.0 CFM to 120 CFM | Free air, at the rated speed |
| Static pressure | 0.12 in H2O to 3.12 in H2O | The figure that decides a filtered inlet |
| Noise | 20 dBA to 43 dBA | At one metre, per part number |
| Speed | 1850 rpm to 14600 rpm | Rated speed at the rated voltage |
| Life | 70,000 hours L10 at 40 C on ball bearings | 50,000 hours on sealed sleeve |
| Operating temperature | Minus 20 C to plus 65 C | Storage to plus 75 C |
| Current | 0.040 A to 0.95 A | Read against the rail budget and the fuse |
| Leads and options | 2, 3 or 4 wire, 24 to 26 AWG | Tachometer, alarm and PWM input |
| Ingress options | IP55, IP68 and IP69K versions | For washdown and coastal cabinets |
| Motor protection | Auto cutoff, auto restart, polarity protected | Locked rotor does not burn the winding |
Included Models and Order Codes
The fans are listed by frame size and voltage first, then by airflow, because the size is fixed by the cutout and the voltage by the rail. Static pressure and noise follow on the same line, so a part can be compared against a filter before it is ordered.
| Part Number | Frame | Voltage | Airflow | Static Pressure | Noise | Current | Bearing |
|---|---|---|---|---|---|---|---|
| MF40101V2-1000U-A99 | 40 x 40 x 10 mm | 12 V | 7.0 CFM | 0.120 in H2O | Not listed | 0.040 A | Vapo |
| MF40201VX-1000U-A99 | 40 x 40 x 20 mm | 12 V | 10.8 CFM | 0.290 in H2O | Not listed | 0.080 A | Vapo |
| GF40282B1-1000U-ADP | 40 x 40 x 28 mm | 12 V | 19.6 CFM | 1.380 in H2O | Not listed | 0.230 A | Dual ball |
| PF40281BX-1000U-S9H | 40 x 40 x 28 mm | 12 V | 31.3 CFM | 3.120 in H2O | Not listed | 0.950 A | Dual ball |
| OD6025-12HB | 60 x 60 x 25 mm | 12 V | 25 CFM | 0.22 in H2O | 30 dBA | Not listed | Dual ball |
| OD6025-12HHB | 60 x 60 x 25 mm | 12 V | 32 CFM | 0.24 in H2O | 32 dBA | Not listed | Dual ball |
| OD6025-24HB | 60 x 60 x 25 mm | 24 V | 25 CFM | 0.22 in H2O | 30 dBA | Not listed | Dual ball |
| OD6025-48HB | 60 x 60 x 25 mm | 48 V | 25 CFM | 0.23 in H2O | 30 dBA | Not listed | Dual ball |
| OD8025-12HB | 80 x 80 x 25 mm | 12 V | 40 CFM | 0.23 in H2O | Not listed | 1.8 W draw | Dual ball |
| OD9225-12HB | 92 x 92 x 25 mm | 12 V | 60.2 CFM | 0.25 in H2O | 38 dBA | 0.29 A | Dual ball |
| OD9225-12LLB | 92 x 92 x 25 mm | 12 V | 25.1 CFM | 0.12 in H2O | 23 dBA | 0.12 A | Dual ball |
| OD9225-24HB | 92 x 92 x 25 mm | 24 V | 60.2 CFM | 0.25 in H2O | 38 dBA | 0.18 A | Dual ball |
| OD1225-12HB | 120 x 120 x 25 mm | 12 V | 120 CFM | 0.24 in H2O | 42 dBA | Not listed | Dual ball |
| OD1225-24HB | 120 x 120 x 25 mm | 24 V | 120 CFM | 0.24 in H2O | 42 dBA | Not listed | Dual ball |
| OD1225-12LSS | 120 x 120 x 25 mm | 12 V | 70 CFM | 0.12 in H2O | 29.2 dBA | 0.20 A | Sealed sleeve |
| OD1225-12HBIP68 | 120 x 120 x 25 mm | 12 V | 120 CFM | 0.24 in H2O | 42 dBA | Not listed | Dual ball, IP68 |
| OD1225-12MB | 120 x 120 x 25 mm | 12 V | 90 CFM | 0.19 in H2O | 35 dBA | Not listed | Dual ball |
Key Features
Working point, not free air – Static pressure is listed with every part, because a fan behind a filter delivers a fraction of its free air figure.
40 mm to 120 mm in one range – From 7 CFM on a thin 40 mm frame to 120 CFM on a 120 mm frame, so a cutout decides the part rather than a guess.
Four voltage rails – 5, 12, 24 and 48 V parts, with the 48 V line for telecom cabinets where a long loom would lose too much at 12 V.
Current per part number – 0.040 A to 0.95 A, so the rail budget and the fuse are checked before the fan is fitted rather than after it trips.
Ball, sleeve and sealed sleeve – Dual ball for any mounting angle at 70,000 hours L10, sealed sleeve for a dusty shop where a plain sleeve seizes.
Tachometer, alarm and PWM – Three and four wire versions report speed and accept a speed command, which is what a monitored cabinet needs.
IP55, IP68 and IP69K versions – Rated parts for a washdown bay and a coastal cabinet, on the 92 mm and 120 mm frames.
Auto restart and polarity protection – A locked rotor cuts the drive and restarts, and a reversed lead does not destroy the board.
Applications
These fans move air through instrument cabinets, telecom racks, charger and inverter enclosures, machine control panels and outdoor roadside cabinets.
Telecom and roadside cabinets – A 48 V 120 mm part on a sealed cabinet with a filtered inlet, where the rail is already 48 V and the fan is monitored by a tachometer.
Instrument and analyser cases – A 60 mm or 92 mm low noise part on a bench instrument, where the cabinet is close to an operator and 23 dBA matters more than airflow.
Charger and inverter enclosures – A 120 mm part at 120 CFM behind a louvre, with the working point read against 0.24 in H2O rather than free air.
Small and portable equipment – A 40 mm part on a hand held unit, with the 28 mm high pressure version where the airflow path is short and restricted.
A fan is the last part chosen on a sealed enclosure and the first one to be blamed, and the SUPERB PCB thermal plan fixes the wattage and the allowed rise before the frame size is picked. On the SUPERB PCBA route the fan is fitted after the board is tested, because a fan that runs during an in circuit test pulls dust through a filter that is not there yet.
Sourcing and Cross-Reference
A fan is ordered with four numbers: frame size, voltage, airflow at the working pressure and the lead configuration. The frame is fixed by the cutout, the voltage by the rail, and the airflow by the wattage and the allowed rise. The lead configuration is the one that is decided last and forgotten first, and a two wire fan dropped into a monitored cabinet leaves the controller unable to tell a stopped fan from a cool one.
Where a fan replaces another make, the frame, the thickness, the voltage and the airflow are the cross reference. A 92 mm fan at 60 CFM can be replaced by another 92 mm fan at 60 CFM, but not by a 92 mm fan at 35 CFM with a higher static pressure, because the cabinet was balanced on the airflow and the filter was chosen around it. Where the mounting holes differ, the adapter plate is a separate part and not a reason to change the cabinet.
The life figure is the part that decides a service interval. A ball bearing part at 70,000 hours L10 is a fan that runs eight years continuously before a tenth of a batch has failed, while a sleeve part in a 60 C box is a fan that is changed every two years. Where a cabinet is in a difficult place to service, the ball bearing part is cheaper over the life of the unit than the sleeve part that has to be replaced.
SUPERB Assembly runs a fan for an hour on the first unit of a build and reads the current against the data sheet, because a fan that is wired backwards still turns and a fan with a blocked filter still turns at the same speed while moving a third of the air.
Q: Can you supply a 120 mm 24 V fan with a tachometer output, an IP68 version for a washdown cabinet and the finger guard that goes with it?
A: Send the watts inside the enclosure, the ambient, the rise you can accept, the voltage rail you have and the cutout size. The SUPERB Tech desk works the airflow from the wattage and quotes a fan with its working point at your static pressure, not its free air figure.
Why Buy Cooling Fans Through SUPERB
- Working point quoted, not free air: Static pressure and airflow sit on the same line, so a filtered inlet can be checked before the order.
- Sizes from 40 mm to 120 mm: One range covers a hand held unit and a telecom cabinet, with the voltage rails that go with each.
- Current and fuse checked: The steady draw is listed per part, which is what the rail budget and the fuse are sized from.
- Sealed and IP rated options: Washdown and coastal cabinets get an IP68 or IP69K part without a second supplier and a second lead time.
- Spares matched to the fitted part: A replacement fan is quoted with the same frame, voltage and lead count, so a service call does not need a rework.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Fan Guards and Filter Screens for Enclosure Cooling, Breather Vents and Pressure Equalization Plugs for Sealed Cases, EMI Shielding Cans and Contact Gaskets for RF Boards, Cable Clamps and Harness Ties for Internal Wiring, Standoffs, Spacers and Mounting Hardware for Board Stacks, Obsolete Part Cross Reference Hub.