Contact Us
  • Home
  • COMPONENTS
  • DIN Rail End Stops and Terminal Partition Plates

DIN Rail End Stops and Terminal Partition Plates

End stops for NS 35/7,5 and NS 35/15 rail in 9.5 mm and 5.15 mm widths. End covers and partition plates in 1.8 mm and 2.2 mm thickness. PA bodies rated UL 94 V-0, operating range -60 to 105 C. Parts matched to UT, UK and CLIPFIX terminal series by part number.
quote now

Product Specifications

Product Overview

A terminal strip is held in place by two small parts that never appear on the drawing: the end stop at each end, and the partition plate between groups that must not touch. The stop carries the side load of the strip and the pull of the wires; the plate carries the creepage distance between two circuits that share a rail.

The stop is chosen by rail and by strip. E/NS 35 N fits NS 35/7,5 and NS 35/15 rail and is 9.5 mm wide. E/UK fits NS 32 as well as NS 35, which matters on older panels where the rail was never changed. CLIPFIX 35 is the quick version: it clips on without a screw, and the 5.15 mm CLIPFIX 35-5 leaves room to park a bridge.

The plate is chosen by terminal series, not by rail. A UT 2,5 strip takes D-UT 2,5/10 end covers and ATP-UT partition plates; a UK 5 N strip takes D-UK 4/10 covers, which are 1.8 mm thick against the 2.2 mm of the UT family. Mixing the two leaves a gap that shows up as a creepage failure, not as a loose part.

Key Specifications

PropertyValue
Rail standardNS 35/7,5 and NS 35/15 to EN 60715; NS 32 on E/UK
Body materialPolyamide (PA), grey RAL 7042
FlammabilityUL 94 V-0
Operating temperature-60 to 105 C
End stop widths5.15 mm, 9.5 mm and 10 mm
Plate thickness1.8 mm for UK series, 2.2 mm for UT series
MountingScrew fixing or tool-free clip, depending on the clamp
Packing50 pcs for most stops and covers, 10 pcs for E/UK 1

Included Models and Order Codes

The part number fixes the width, and the width fixes how many plates fit between two strips on a given rail length. The list below covers the stops and plates used with the UT and UK screw terminal families.

Part numberTypeWidthLength or heightFits
0800886E/NS 35 N end stop9.5 mm48.6 mmNS 35/7,5 and NS 35/15
1201442E/UK end stop9.5 mm50.5 mmNS 32 and NS 35/7,5
1201413E/UK 1 end stop10 mm-Double and three-level strips
3022218CLIPFIX 35 quick clamp9.5 mm55.6 mmNS 35/7,5 and NS 35/15
3022276CLIPFIX 35-5 quick clamp5.15 mm48.5 mmNS 35, with bridge parking
3047028D-UT 2,5/10 end cover2.2 mm47 mmUT 2,5 to UT 10
3047141D-UT 2,5/4-TWIN end cover2.2 mm57.8 mmUT 2,5-TWIN
3047109D-UT 2,5/4-QUATTRO end cover2.2 mm65.4 mmUT 2,5-QUATTRO
3047167ATP-UT partition plate2.2 mm50 mmUT 2,5 to UT 10
3003020D-UK 4/10 end cover1.8 mm42.5 mmUK 5 N and UK 6 N

Key Features

Stop carries the side load – the clamp is screwed or clipped to the rail and takes the pull of the wire bundle, so the strip does not creep along the rail.

Two widths for tight strips – 5.15 mm CLIPFIX and 9.5 mm E/NS cover the same rail with different space claims.

Plate thickness follows the series – 1.8 mm for UK, 2.2 mm for UT, so the creepage gap is the one the terminal was tested with.

PA body rated V-0 – the same material class as the terminal body, with a -60 to 105 C range.

Marking surface on the clamp – the 9.5 mm face takes a Zack strip, so the strip end can be identified without a separate holder.

Old rail covered – E/UK fits NS 32 as well as NS 35, which keeps older panels serviceable.

Applications

These parts are bought by the strip, not by the piece. Three patterns repeat.

Control and automation panels – UT 2,5 and UT 4 strips with D-UT covers and ATP-UT plates between the 24 V and the 230 V groups.

Machine wiring – UK 5 N strips on older NS 32 rail, where the E/UK stop is the only one that fits without changing the rail.

Retrofit and repair – single stops and covers for a panel that is being extended, where the strip is already wired and only one end is open.

Terminal strips are quoted with their end stops and plates in one line, and the SUPERB PCBA and the SUPERB PCB are checked against the same rail drawing so the strip length is fixed before the rail is cut.

Sourcing and Cross-Reference

Order the plate with the terminal, not after: a UT 2,5 strip needs D-UT 2,5/10 covers at both ends and ATP-UT plates at every group boundary, and the plate count is one less than the number of groups.

Check the rail, not the panel drawing. NS 32 and NS 35 look similar on a photo and only the E/UK family covers both; a 35 mm stop on 32 mm rail will fit loosely and fail a pull test.

Pack sizes are 50 for most stops and covers, so a one-off repair still buys a box. Split packs are available on request through lead time and availability.

The SUPERB Assembly team fits the end stops first and then slides the strip against them, which keeps the pitch and leaves room for the marker at the end.

Q: Can you supply the stops and plates together with the terminal strip?

A: Yes. Send the terminal series and the number of poles, and the SUPERB Tech team quotes the matching end stops, end covers and partition plates for that strip.

Why Panel Builders Buy Rail Accessories From SUPERB

  1. Matched by terminal series: the cover and plate part numbers are checked against the strip, not picked by width alone.
  2. Old and new rail in one quote: NS 32 and NS 35 stops ship together for panels that mix generations.
  3. Small parts in the same box: stops, covers and plates arrive with the terminals, so the strip is not held up for a 2.2 mm part.
  4. Traceable batch: the packing carries the part number and batch, which keeps the material record complete for audit builds.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DIN Rail Terminal Blocks, Mounting Brackets and DIN Rail Clips, Screw Terminal Blocks and Pluggable Connectors, Wire Ferrules and Crimp Sleeves.