Contactor Coil Suppression Modules and RC Networks
Product Specifications
Product Overview
A contactor coil is an inductor, and interrupting an inductor produces a voltage spike that travels down the control wiring. The spike does not damage the coil, it damages what the coil is connected to: a PLC output, a relay contact, a sensor input sharing the same duct, or a drive analogue card in the same panel. Fitting a suppressor across the coil is the cheapest way to stop the spike at its source instead of filtering it at the victim.
Three technologies cover the job and each one trades peak voltage against release time. An RC network limits the peak to about three times the coil voltage and adds a release delay of 1.2 to 2 times normal. A varistor limits the peak to about twice the coil voltage with a shorter delay, 1.1 to 1.5 times. A diode assembly on a DC coil removes the peak almost completely but makes the release the slowest of the three. There is no best type in general, only a best type for the machine: a press that must stop fast takes the varistor, a panel with a sensitive analogue card takes the RC, and a DC holding coil on a battery system takes the diode.
The second decision is mechanical. Some suppressors clip into a cavity on top of the contactor, some screw onto the coil terminals, and some are built into a cabling accessory that also carries the coil leads. The same electrical function exists in all three forms, and the form is decided by the contactor size and by whether the panel has room above the device. Getting this wrong is the usual reason a suppressor is ordered twice.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Suppressor technologies | RC network, varistor, diode assembly | each has a different peak limit and release delay |
| Peak voltage, RC | up to 3 x Uc | Schneider LA4D RC data |
| Peak voltage, varistor | up to 2 x Uc | varistor clamps harder than an RC network |
| Release delay, RC | 1.2 to 2 times the normal drop out time | this is the price of the lower transient |
| Release delay, varistor | 1.1 to 1.5 times the normal drop out time | faster release than RC at a higher peak |
| Oscillation frequency limit, RC | 400 Hz | above this an RC network is the wrong choice |
| AC voltage bands | 24 to 48 V, 50 to 127 V, 110 to 240 V, 380 to 415 V | one module covers a band, not a single voltage |
| DC voltage bands | 12 to 250 V on diode assemblies, 150 to 250 V DC on the RC element | DC coils need the DC rated module |
| Mounting | clip into the contactor cavity, screw to the coil terminals, or built into a cabling accessory | form is decided by contactor size |
| Ambient temperature in operation | -25 to +55 C, -25 to +60 C on the Siemens parts | storage -40 to +80 C |
| Weight | 18 g on LA4DA2E, 7 g on 3RT2916 | the module does not change the device footprint |
| Coil frequency | 50 and 60 Hz | DC coils use the diode or the DC rated RC |
| Standards | IEC 60947-4-1, UL, CSA | module carries the same approvals as the contactor family |
Included Models and Order Codes
The rows are grouped by contactor family because a suppressor is only useful if it fits the device it is ordered for. The Schneider LA4D range screws to the coil terminals of the larger TeSys D bodies, LC1D80 to LC1D150, and the LAD4 range clips into the cavity on the smaller bodies, LC1D09 to LC1D38. The Siemens 3RT2916 range is the same idea for the S00 and S0 SIRIUS bodies, and its part number carries the technology in the middle: 1B is a varistor, 1C is an RC element, 1J is a varistor with an LED, and 1E is a diode assembly. Voltages below are the ones printed on the maker data sheet.
| Part number | Technology | Coil voltage | Fits | Peak limit | Note |
|---|---|---|---|---|---|
| LA4DA2E | RC | 24 to 48 V AC 50/60 Hz | LC1D80 to D150 | 3 x Uc | screw mounting on the coil terminals, 18 g |
| LA4DA2G | RC | 50 to 127 V AC 50/60 Hz | LC1D80 to D150 | 3 x Uc | same body, middle voltage band |
| LA4DA2U | RC | 110 to 240 V AC 50/60 Hz | LC1D80 to D150 | 3 x Uc | the band used on most 230 V control panels |
| LA4DA2N | RC | 380 to 415 V AC 50/60 Hz | LC1D80 to D150 | 3 x Uc | for panels without a control transformer |
| LAD4RC3U | RC | 110 to 240 V AC 50/60 Hz | LC1D09 to D38 | 3 x Uc | screw connection to the coil terminals |
| LAD4RC3N | RC | 380 to 415 V AC 50/60 Hz | LC1D09 to D38 | 3 x Uc | same cavity, higher band |
| LAD4BBVE | varistor in a cabling accessory | 24 to 48 V AC | LC1D09 to D38 | 2 x Uc | replaces the plain coil lead adapter LAD4BB |
| LAD4BBVG | varistor in a cabling accessory | 50 to 127 V AC | LC1D09 to D38 | 2 x Uc | keeps the coil leads and the suppressor in one part |
| 3RT2916-1BB00 | varistor | 24 to 48 V AC, 24 to 70 V DC | 3RT2.1 and 3RH2, size S00 | 2 x Uc | clip on, 7 g |
| 3RT2916-1JK00 | varistor with LED | 48 to 127 V AC, 24 to 70 V DC | 3RT2.1 and 3RH2, size S00 | 2 x Uc | the LED shows the coil is energised |
| 3RT2916-1CC00 | varistor | 48 to 127 V AC | 3RT2.1 and 3RH2, size S00 | 2 x Uc | standard varistor for the middle band |
| 3RT2916-1CD00 | RC element | 127 to 240 V AC, 150 to 250 V DC | 3RT2.1 and 3RH2, size S00 | 3 x Uc | RC on a DIN rail contactor body, 28 x 46 x 9 mm |
| 3RT2916-1EH00 | diode assembly | 12 to 250 V DC | 3RT2.1 and 3RH2, size S00 | near zero peak on DC | diode and Zener pair, for DC operated coils |
Choosing Between the Three Technologies
The choice is made on three questions, in this order: is the coil AC or DC, how fast must the contactor release, and what else shares the control wiring. The table below is the short version of that conversation.
| Situation | Type that fits | Why |
|---|---|---|
| AC coil, PLC output driving the coil directly | RC network or varistor | either one keeps the spike below the output rating, RC is quieter on long leads |
| AC coil, machine must stop without extra delay | varistor | release delay 1.1 to 1.5 times, against 1.2 to 2 times for RC |
| AC coil, analogue signal in the same duct | RC network | the RC damps the oscillation instead of clipping it, which suits audio and instrument wiring |
| DC coil on a battery or a DC link | diode assembly | removes the reverse spike almost completely, the slower release is acceptable on a holding coil |
| Coil driven at 400 Hz or above | varistor or diode | an RC network is limited to 400 Hz oscillation |
Key Features
Three technologies on one page – RC, varistor and diode assemblies are listed together, with the peak limit and release delay of each, so the trade is visible before the part is ordered.
Voltage bands, not single voltages – a module covers 24 to 48 V or 110 to 240 V, which means one part number serves a panel with several coil voltages.
Form matched to the contactor – clip in, screw on and cabling accessory versions are separated, because the same function in the wrong form will not fit above the device.
Peak limit stated – 3 x Uc for RC and 2 x Uc for varistor, which is the number an output card is compared against.
Release delay stated – the added drop out time is on the row, because a safety circuit that relies on fast opening notices it.
Fits the range already on the rail – Schneider LA4D and LAD4 and Siemens 3RT2916 are listed separately, so a panel keeps one contactor family and one suppressor family.
Applications
These modules are small, and they are usually fitted for one of the three reasons below.
PLC and safety relay outputs – a transistor output that switches a contactor coil sees the full reverse spike, and a suppressor keeps the output inside its rating without adding an interposing relay.
Long coil leads and shared ducts – a coil at the far end of a panel couples its transient into every conductor in the same duct, so the suppressor goes at the coil rather than at the card.
DC coils on battery and DC link systems – a DC holding coil with a diode assembly releases slowly and quietly, which is what a battery system with a shared negative rail needs.
The coil circuit shares a panel with the control board, so the SUPERB PCBA and the SUPERB PCB are reviewed against the same suppressor list and the same 24 V rail.
Sourcing and Cross-Reference
The practical risk with suppressors is a mismatch of form rather than of function. A 110 to 240 V RC module exists for both the small and the large TeSys D bodies, but the small one clips into a cavity and the large one screws to the terminals, so the part number has to be read with the contactor size in hand. The same is true on the Siemens side, where the S00 module does not fit the S0 body.
The second risk is voltage banding. A 24 to 48 V module on a 110 V coil is a short circuit waiting to be energised, and a 380 to 415 V module on a 230 V coil clamps too late to be useful. Because the bands overlap at the edges, the coil voltage is best quoted together with the part number rather than read off the contactor label afterwards.
For panels in build, the module is often the last item on the list and the first to hold up a test. Where a band is short, the alternative is another technology in the same band, a cabling accessory with the suppressor built in, or the same function from the other contactor family if the panel has not been wired yet. See lead time and availability for a specific band and obsolete part cross reference where an older suppressor number has been withdrawn.
The SUPERB Assembly team fits the module before the coil leads are dressed, because a suppressor added after the wiring is combed is often left off the drawing.
Q: Can you supply the suppressor module in the same voltage band as the coil we already have, in the form that fits the contactor body?
A: Yes. Send the contactor part number, the coil voltage, AC or DC, and the release requirement, and the SUPERB Tech team returns the module that fits that body.
Why Panel Builders Buy Coil Suppressors From SUPERB
- Band and form on the same row: the coil voltage and the contactor size sit together with the part number, which is the pair that has to match for the module to be usable.
- Peak limit and delay written out: the two numbers that decide whether the module suits a fast stop or a sensitive input are on the page rather than in a footnote.
- Contactor families kept separate: Schneider and Siemens parts are listed in their own groups, so a panel does not end up with a mixed set that only one electrician can service.
- Three technologies, one order: RC, varistor and diode can be quoted together for a panel with AC and DC coils, which keeps the suppressor list on one line of the BOM.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, DIN Rail Terminal Blocks for Control Panel Wiring, Ferrite Beads and EMI Suppression Filters for Board Noise.