Cam Switches and Changeover Switches for Panel Control
Product Specifications
Product Overview
A cam switch is a mechanical sequencer. Contact stages sit side by side on a common shaft, each stage carries a cam that opens or closes its contact at a set angle, and turning the handle walks all the stages through the sequence printed on the switch drawing. There is no coil, no supply and no program, which is why a cam switch still selects between two supplies, reverses a motor or steps a tap on panels that have no controller at all.
The part that has to be specified is not the current, it is the function. A cam switch is ordered as a type plus a function code, and the function code is the drawing: which contacts close in position 1, which stay closed through the transition, and which are open in the off position. Two switches with the same 20 A frame and the same handle can be a star delta selector and a two speed motor selector, and the only difference is the code. That is why a replacement order needs the code from the old switch or a photograph of its stage drawing, not just the frame size.
The ratings separate into a thermal current and a utilization category. Thermal current is what the switch carries continuously, 10, 20 or 25 A depending on the frame. The utilization category is what it can break: AC-23A covers frequent switching of a motor or another highly inductive load, AC-3 covers direct on line starting, and AC-15 covers contactor coils and other control circuits. A switch rated 20 A thermal is 7.5 kW at AC-23A but only 5.5 kW at AC-3, and the UL rating in the same frame is often lower than the IEC one, 16 A at 150 V on a part that carries 20 A in a European panel.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Standard | IEC 60947-3, EN 60947-3, VDE 0660 part 107 | UL 508 and CSA on the same family |
| Rated thermal current | 10 A on S00, 20 A on S0, 25 A on S1 | CG4, CH6 and CH10, CH10B, CH16 and CH16B |
| Rated insulation voltage | 440 V on CG4, 690 V on CH and CHR | 600 V AC on the UL rating |
| Rated impulse withstand voltage | 4 kV on CG4, 6 kV on CH and CHR | overvoltage category III, pollution degree 3 |
| Switching angle | 30, 45, 60 and 90 degrees | 45, 60 and 90 degrees on the CG4 frame |
| Maximum number of stages | 9 on S00, 12 on S0 and S1 | stage count sets the depth behind the panel |
| Panel size | S00 30 x 30 mm, S0 48 x 48 mm, S1 64 x 64 mm | escutcheon plate and handle follow the size |
| Motor rating AC-23A at 380 to 440 V | 3 kW on CG4, 7.5 kW on CH10, 11 kW on CH16 | frequent switching of a motor load |
| Motor rating AC-3 at 380 to 440 V | 2.2 kW on CG4, 5.5 kW on CH10, 7.5 kW on CH16 | direct on line starting |
| Control circuit rating AC-15 at 220 to 240 V | 2.5 A on CG4, 6 A on CH10, 8 A on CH16 | contactor coils and small solenoids |
| AC-22A at 500 V and at 660 to 690 V | 20 A and 16 A on CH10 | mixed resistive and inductive load |
| Short circuit protection, gG fuse | 10 A on CG4, 25 A on CH10, 35 A on CH16 | maximum fuse that protects the switch |
| Rated short time withstand current, 1 s | 90 A on CG4, 200 A on CH10, 250 A on CH16 | withstand before the fuse clears |
| Terminal | screw up to 4 mm2, ring type, or quick connect | 1 Nm tightening torque on the CH10 screw terminal |
| UL pilot duty | A300 on CG4 and CH6, A600 on CH10 and CH16 | matters when the panel is built to UL |
| Changeover switch rating | 20 A, 60 or 90 degrees, 1-0-2 or 1-2 | Eaton T0, with or without a centre off position |
Included Models and Order Codes
Kraus and Naimer type codes carry the frame and the terminal style, and the function is added as a suffix at order time. CH10 is the 20 A screw terminal frame in size S0, CHR10 is the same electrical part with ring type terminals, CH10B moves to the larger S1 panel with four hole mounting, and CH16 and CHR16 step up to 25 A. A complete order reads as type, function code, mounting and optional extras, for example CHR10 D-1234 FT2 S0 V750D/3G, where the D-1234 block is the contact sequence. The Eaton T0 rows are changeover switches rather than cam switches in the K and N sense: they are ordered by catalogue number and the suffix describes mounting and handle.
| Part number | Thermal current | Panel size | AC-23A at 380 to 440 V | AC-3 at 380 to 440 V | Terminal | Note |
|---|---|---|---|---|---|---|
| CG4 | 10 A | S00, 30 x 30 mm | 3 kW | 2.2 kW | screw | smallest frame, 45, 60 and 90 degree angles |
| CG4-1 | 10 A | S00, 30 x 30 mm | 3 kW | 2.2 kW | screw | gold plated contacts for low level signals |
| CH6 | 20 A | S0, 48 x 48 mm | 7.5 kW | 5.5 kW | screw | 20 A frame with a shorter stage stack |
| CH10 | 20 A | S0, 48 x 48 mm | 7.5 kW | 5.5 kW | screw, 4 mm2 | the general purpose 20 A control switch |
| CHR10 | 20 A | S0, 48 x 48 mm | 7.5 kW | 5.5 kW | ring type | same ratings, ring terminals for a fixed loom |
| CH10B | 20 A | S1, 64 x 64 mm | 7.5 kW | 5.5 kW | screw, 4 mm2 | four hole panel mounting, larger escutcheon |
| CHR10B | 20 A | S1, 64 x 64 mm | 7.5 kW | 5.5 kW | ring type | S1 panel with ring terminals |
| CH16 | 25 A | S0, 48 x 48 mm | 11 kW | 7.5 kW | screw | 25 A frame, 35 A gG back up fuse |
| CHR16 | 25 A | S0, 48 x 48 mm | 11 kW | 7.5 kW | ring type | 25 A frame with ring terminals |
| CH16B | 25 A | S1, 64 x 64 mm | 11 kW | 7.5 kW | screw | 25 A on the larger panel |
| CHR16B | 25 A | S1, 64 x 64 mm | 11 kW | 7.5 kW | ring type | 25 A, S1 panel, ring terminals |
| T0-3-8212/E | 20 A | flush, 3 contact units | not rated as a motor switch | not rated as a motor switch | screw | changeover, 6 contacts, 60 degrees, 1-0-2 with off |
| T0-2-15907/I1/SVC | 20 A | surface, 2 contact units | not rated as a motor switch | not rated as a motor switch | screw | changeover, AUTO-0-HAND, padlocking feature |
| 222652 | 20 A | surface, 3 contact units | not rated as a motor switch | not rated as a motor switch | screw | changeover, 6 contacts, 90 degrees, 1-2 without off |
How a Function Code Is Read
A cam switch drawing is a matrix: positions across the top, stages down the side, and a filled block wherever a contact is closed. The code in the part number is that matrix written in a short form. Reading it the wrong way round is the usual reason a replacement switch turns the wrong way or leaves a contact closed in the off position.
| Code element | What it controls | What to check on the old switch |
|---|---|---|
| Switch type, CH10 or CHR16 | frame, current and terminal style | terminal screws or ring lugs, and the panel cut out |
| Function block, D-1234 | which contacts close in each position | the stage drawing on the side of the body, or a photo of it |
| Mounting suffix, FT2 | base or four hole panel mounting and handle | the hole pattern, not the handle shape |
| Angle, 30 to 90 degrees | how far the handle turns between positions | the number of positions marked on the escutcheon |
| Optional extra, V750D | a special handle, lock or marking | whether the old switch can be locked in the off position |
Key Features
Contact sequence fixed by the cam, not by a program – the switch repeats the same sequence for its whole life, which is what a mains changeover or a motor reversal needs in a panel with no controller.
Up to 12 stages on one shaft – a single switch can carry a main circuit, a control contact and an indicator contact that all move together, which removes the timing error between separate devices.
Four switching angles – 30, 45, 60 and 90 degree steps let one frame be a fine tap selector or a two position changeover, with the escutcheon marking the positions.
Three panel sizes – S00 at 30 x 30 mm, S0 at 48 x 48 mm and S1 at 64 x 64 mm, so the same electrical family fits a small instrument box and a large cabinet door.
Screw, ring or quick connect terminals – the terminal style follows the wiring method in the panel, and the ring type versions are used where a fixed loom is bolted rather than screwed.
Changeover switches with a centre off – the Eaton T0 range covers 1-0-2 and 1-2 sequences at 20 A, which is the part that transfers a panel between mains and a generator without a contactor interlock.
Applications
Cam switches are specified by the sequence they perform, so the three cases below are the ones that come up most often in panel work.
Mains and generator changeover – a 20 A changeover switch with a centre off position transfers a small panel between two supplies with a mechanical gap between the positions, so the two sources cannot be paralleled by a mistake.
Motor direction and star delta selection – a 20 or 25 A cam switch with a reversing or star delta function replaces two contactors and the interlock wiring on a machine that is switched by hand rather than by a controller.
Instrument and tap selection – a small S00 frame with gold contacts switches thermocouple, RTD or signal pairs on a test bench, where the contact resistance and the low level signal matter more than the current rating.
The switch is quoted with the board that carries the control circuit, so the SUPERB PCBA and the SUPERB PCB are checked against the same terminal list and the switch stages are named on the drawing.
Sourcing and Cross-Reference
Ordering a cam switch from a description is where most mistakes happen. The frame and the current are easy, and the function is the part that has to be read from the old unit. A CH10 with a two position reversing function and a CH10 with a three position star delta function share the same body, the same panel cut out and the same price band, and only the stage drawing tells them apart. When the old switch is still in place, the stage drawing is moulded or printed on the side, and a photograph of it is enough to rebuild the code.
The second trap is the rating table. A 20 A switch is 20 A thermal, 7.5 kW at AC-23A and 5.5 kW at AC-3, and the UL rating at 300 V can be lower than the IEC rating at 690 V. A switch selected on the thermal current alone can be undersized for a motor that is started and plugged, which is the duty AC-23A is there to describe. Where the panel is built to UL, the pilot duty rating A300 or A600 is the figure the inspector looks for.
Where a switch has been obsolete for years, the mechanical interface is the constraint rather than the electrical rating: the shaft length, the panel hole pattern and the handle fixing have to match, or the door has to be reworked. See obsolete part cross reference for the comparison route and lead time and availability when a panel is waiting on one switch.
The SUPERB Assembly team labels each stage of a multi stage switch before the loom goes in, because a stage that is one position out is invisible once the escutcheon is fitted.
Q: Can you supply a cam switch built to the same contact sequence as the one on the machine, including the panel mounting and handle?
A: Yes. Send a photo of the stage drawing on the old switch, the panel cut out and the load it switches, and the SUPERB Tech team returns the type, the function code and the mounting suffix.
Why Panel Builders Buy Cam Switches From SUPERB
- Frame and function separated: the type gives the current and the panel size, the function code gives the sequence, and both are written on the same row so a replacement is not guessed.
- Ratings per utilization category: AC-23A, AC-3 and AC-15 figures are listed separately, which is what decides whether a 20 A frame is enough for a motor.
- Panel size and terminal style stated: S00, S0 and S1 and the screw or ring terminal are part of the row, so a spare fits the hole that is already in the door.
- Changeover options in the same list: the Eaton T0 parts sit beside the cam switches, which covers the mains transfer case without a second search.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Non Fused Switch Disconnectors for Panel and Machine Isolation, Contactors and Reversing Contactors for Motor Loads, Industrial Pushbuttons and Selector Switches for Panel Fronts, Emergency Stop Devices and Enabling Switches, DIN Rail Terminal Blocks for Control Panel Wiring.