Anti Condensation Heaters for Electrical Enclosures
Product Specifications
Product Overview
Condensation does not need rain. A cabinet that is warm and humid inside, and cold on its steel skin, will form water on the inside of the door and on the coldest terminals in the box. The usual sequence is a warm day, a cool night, and a control panel that trips at four in the morning on a fault that cannot be found at noon. The water is not a leak, it is the dew point crossing, and no gasket stops it.
The remedy is to keep the inside surface above the dew point, and that takes far less power than most people expect. Ten to thirty watts in a small enclosure, or fifteen to one hundred and fifty watts in a medium one, is normally enough to lift the internal air a few degrees and to keep the steel above the condensation point. A PTC element is the right source for this job because its resistance rises as it heats, so the output falls back instead of running away, and the heater can be left on continuously without a thermostat.
Sizing is a heat balance, not a guess. The cabinet loses heat through its surface at roughly 5.5 W per square metre per kelvin for painted steel, so a one square metre cabinet in a room 15 K colder than the target loses about 80 W. The heater only has to replace enough of that loss to hold the surface above the dew point, which is why a 30 W heater is often correct in a 600 x 400 mm box and an 800 W fan heater belongs in a large floor standing cabinet that is opened often.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Heating capacity | 10 W to 800 W across the three families | 15 to 150 W on the PTC convection body |
| Supply | 120 to 240 V AC or DC on the convection heater, 230 V AC on the radiant heater | other voltages on request, output drops about 10 percent below 140 V |
| Element | PTC resistor, self regulating | the output falls as the surface warms, so no thermostat is needed for frost protection |
| Protection type | IP20 on the convection heater, IP54 on the radiant heater | the heater is inside the cabinet, the IP figure is about dust and touch |
| Maximum surface temperature | 95 C at 10 W, 115 C at 20 W, 140 C at 30 W | radiant heater, keep cables 50 mm clear |
| Inrush current | 1.5 A at 15 W, 3 A at 30 W, 9 A at 150 W | decides the MCB curve, a C curve is the usual choice |
| Operating temperature | -45 to +70 C | storage -45 to +70 C |
| Mounting | clip for 35 mm DIN rail, screw fixing as an accessory | installation with the airflow vertical and the connection at the bottom |
| Connection | 3 pressure clamps for 0.5 to 2.5 mm2 | 300 mm cable on the radiant heater |
| Airflow | 30 CFM, about 50 m3/h, on the fan heater | the fan is what makes 800 W usable in a large box |
| Pre-fuse | 6 A at 200 W, 10 A from 400 W to 800 W | the maker table gives a pre-fuse per rating |
| Duty cycle | 100 percent, continuous operation | PTC bodies are built to stay energised |
| Width | 70 mm on the convection heater, 29.5 mm on the 10 W radiant heater | narrow bodies fit beside terminals on the same rail |
Included Models and Order Codes
The list runs from the smallest radiant heater to the largest fan heater, because a panel line usually needs two sizes rather than one. STEGO part numbers in the 1400x series carry the wattage in the last two digits: 14000 is 15 W, 14001 is 30 W, and the body length grows from 110 mm to 265 mm as the rating rises. The Pfannenberg PRH mini series is quoted with a seven digit article number and a 300 mm cable, and the PFH fan heaters use one article number per voltage, so the 230 V and 115 V versions of the same rating are two different numbers.
| Part number | Type | Heating capacity | Supply | Inrush current | Note |
|---|---|---|---|---|---|
| 14000.0-00 | STEGO HG 140 convection | 15 W | 120 to 240 V AC / DC | 1.5 A | 110 x 70 x 60 mm, 300 g, 35 mm rail clip |
| 14001.0-00 | STEGO HG 140 convection | 30 W | 120 to 240 V AC / DC | 3 A | same body as the 15 W part |
| 14003.0-00 | STEGO HG 140 convection | 45 W | 120 to 240 V AC / DC | 3.5 A | same body, higher element rating |
| 14005.0-00 | STEGO HG 140 convection | 60 W | 120 to 240 V AC / DC | 2.5 A | 185 x 70 x 60 mm, 400 g |
| 14006.0-00 | STEGO HG 140 convection | 75 W | 120 to 240 V AC / DC | 4 A | 185 mm body, 500 g |
| 14007.0-00 | STEGO HG 140 convection | 100 W | 120 to 240 V AC / DC | 4.5 A | 185 mm body, 500 g |
| 14008.0-00 | STEGO HG 140 convection | 150 W | 120 to 240 V AC / DC | 9 A | 265 mm body, 700 g |
| 17000105317 | Pfannenberg PRH 010-M radiant | 10 W | 230 V AC 50/60 Hz | 1.0 A | 29.5 x 50 mm, 95 C surface, IP54, 300 mm cable |
| 17000205317 | Pfannenberg PRH 020-M radiant | 20 W | 230 V AC 50/60 Hz | 1.1 A | 115 C surface, 120 g |
| 17000305317 | Pfannenberg PRH 030-M radiant | 30 W | 230 V AC 50/60 Hz | 1.2 A | 140 C surface, 120 g |
| 17020610030 | Pfannenberg PFH 200 fan heater | 200 W | 230 V AC | 9 A | 30 CFM, pre-fuse 6 A |
| 17040610030 | Pfannenberg PFH 400 fan heater | 400 W | 230 V AC | 15 A | 30 CFM, pre-fuse 10 A |
| 17065610030 | Pfannenberg PFH 650 fan heater | 650 W | 230 V AC | 20 A | 30 CFM, pre-fuse 10 A |
| 17080610030 | Pfannenberg PFH 800 fan heater | 800 W | 230 V AC | 31 A | 30 CFM, pre-fuse 10 A |
| 17020615030 | Pfannenberg PFH 200 fan heater | 200 W | 115 V AC | 9 A | the 115 V version of the same body |
| 17080615030 | Pfannenberg PFH 800 fan heater | 800 W | 115 V AC | 31 A | 115 V version, pre-fuse 10 A |
How Much Heat a Cabinet Actually Needs
The heater does not have to warm the cabinet to room temperature, it has to keep the coldest internal surface above the dew point. That is a much smaller number, and it is the reason a 30 W part is often right where a 200 W part looks safer.
| Cabinet | Heat loss at 15 K difference | Heater that usually fits |
|---|---|---|
| 600 x 400 x 250 mm, painted steel | about 33 W | 30 W convection heater, or a 20 W radiant part on a small box |
| 800 x 600 x 300 mm, painted steel | about 65 W | 60 W or 75 W convection heater |
| 1200 x 800 x 400 mm, painted steel | about 125 W | 150 W convection heater, or a 200 W fan heater if the door is opened often |
| 2000 x 800 x 600 mm, floor standing | about 210 W | 400 W fan heater, because the air has to move to reach the top of the cabinet |
| Cabinet in a washdown area, opened daily | loss plus a full air exchange each opening | fan heater with a thermostat, the opening is the load, not the steel |
Key Features
PTC element, no thermostat needed – the resistance rises with temperature, so the heater settles at its output instead of cycling, which is what makes continuous operation safe.
Surface temperature on the row – 95, 115 and 140 C are listed per radiant part, because cable routing next to the heater is decided by that figure.
Inrush current published – 1.5 A to 31 A across the range, which is the number that decides the breaker curve and stops a nuisance trip on a shared circuit.
Three forms for three jobs – radiant for a cold spot, convection for a whole small cabinet, fan for a large one, with the airflow figure given for the fan version.
Rail mounting as standard – a 35 mm clip is the default and screw fixing is an accessory, so the heater lands on the rail with the terminals it protects.
Voltage bands stated – 120 to 240 V AC or DC on the convection body covers most panels with one part number, and 115 V versions are listed separately.
Applications
Anti condensation heaters are fitted for three situations, and the choice of form follows from which one applies.
Outdoor cabinets and roadside enclosures – the steel skin drops below the dew point every night, so a convection heater on a rail holds the internal surface warm enough that the water never forms on the terminals.
Washdown and food processing areas – daily cleaning puts moisture into the air around the cabinet, and a fan heater with a thermostat dries the box after each shift instead of letting the water settle in the bottom.
Cold stores and unheated warehouses – the cabinet is colder than the air that enters when the door opens, so a radiant heater aimed at the terminal block keeps the one surface that matters above the condensation point.
The cabinet heater sits on the same rail as the control board, so the SUPERB PCBA and the SUPERB PCB are checked against the same 24 V and 230 V separation in the panel.
Sourcing and Cross-Reference
A heater order is usually a rating and a voltage, and the two are easy to separate by accident. The STEGO 1400x body covers 120 to 240 V AC or DC in one part, but the Pfannenberg PFH family has one article number per voltage, so the 115 V and 230 V versions of the same wattage are different numbers. Reading the article number rather than the description is the safe habit here.
The second point is the circuit. A 150 W PTC heater draws 9 A at switch on, and an 800 W fan heater draws 31 A for a fraction of a second, which is enough to trip a B curve breaker shared with other small loads. The pre-fuse and inrush figures on this page come from the maker tables and are there to be used before the panel is wired, not after the first nuisance trip.
Where a rating is short, the alternative is usually the next size up with a thermostat, a second smaller heater on the other side of the cabinet, or a fan heater instead of a convection body when the cabinet is tall. See lead time and availability for a specific part and BOM shortage recovery when a panel is waiting on one heater to ship.
The SUPERB Assembly team keeps the heater circuit on its own breaker rather than sharing the control supply, because an inrush of 9 A on a shared rail is a nuisance trip waiting to happen.
Q: Can you confirm the heater rating and the inrush current for a cabinet of this size, and whether a thermostat is needed?
A: Yes. Send the cabinet dimensions, the lowest ambient, the supply voltage and whether the door is opened daily, and the SUPERB Tech team returns the rating and the form that fit.
Why Panel Builders Buy Enclosure Heaters From SUPERB
- Rating, voltage and inrush together: the three numbers that decide the circuit are on one row, which is what an electrician needs before the rail is drilled.
- Three forms on one page: radiant, convection and fan versions are listed with their airflow and surface temperature, so the form is chosen from the cabinet, not from stock.
- Continuous duty stated: the PTC bodies are rated for 100 percent duty, which removes the question of whether a timer or a thermostat is mandatory.
- Small and large parts side by side: a 10 W radiant part and an 800 W fan heater are on the same list, because a panel line usually needs both for different cabinets.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Enclosure Panel Heaters and Thermostats for Cold Cabinets, Enclosure Hygrostats and Humidity Controllers, Enclosure Heat Exchangers for Dusty and Sealed Sites, Enclosure Air Conditioners for Sealed Cabinet Cooling, Filter Fan Units and Exhaust Filters for Enclosure Cooling.