Enclosure Hygrostats and Humidity Controllers
Product Specifications
Product Overview
A hygrostat is a humidity switch, not a humidity meter. It closes a contact when the relative humidity inside the enclosure passes the set point, and that contact switches a heater or a fan. The purpose is to hold the air inside the cabinet above the dew point, so moisture does not condense on cold terminals, boards and busbars when the cabinet cools down overnight or after a shutdown.
Two families cover the work. Mechanical hygrostats use a humidity sensitive element with a spring contact, a setting range of 40 to 90 percent RH or 50 to 100 percent RH, and a switching differential of about 4 to 5 percent RH. Electronic units add a sensor and a relay, can combine thermostat and hygrostat in one housing, and carry up to 8 A on the contact. DC versions switch 20 to 56 V loads directly through a MOSFET output, which is the part for a 24 V or 48 V cabinet with no AC rail.
The set point is not a comfort setting. It is the level at which the heater can still lift the air above the dew point for the coldest surface in the cabinet. A cabinet that is opened several times a day in a humid hall needs a lower set point than a sealed cabinet with a steady internal temperature, and a unit with a 50 to 100 percent RH range cannot be set to hold 45 percent at all. That is the first thing to check before the part number.
Key Specifications
| Device | Type | Setting range | Switching differential | Contact | Supply |
|---|---|---|---|---|---|
| Rittal SK 3118.000 | Mechanical hygrostat | 50 - 100% RH | approx. 4% RH | Single pole changeover, quick break, 5 (0.2) A AC inductive, 20 W DC | 24 - 250 V AC, 24 - 48 V DC |
| Pfannenberg FLZ 600 | Mechanical hygrostat | 40 - 90% RH | approx. 5% RH | Changeover spring contact, N.O. 5 (0.2) A, N.C. 2 (0.2) A at 24 - 250 V AC | 24 - 250 V AC |
| Pfannenberg FLZ 610 | Electronic hygrostat and thermostat | 40 - 90% RH, 0 - 60 C | approx. 2 K, approx. 4% RH | Relay changeover, 8 (3) A at 240 V AC, 4 A at 24 V DC | 230 V AC or 115 V AC |
| STEGO EFR 012 | Electronic hygrostat, relay | 40 - 90% RH | approx. 5% RH, tolerance 3% RH | 8 (1.6) A at 240 V AC, 100 W DC | 230 V AC |
| STEGO DCF 010 | Electronic hygrostat, DC, MOSFET | 40 - 90% RH | approx. 4% RH, tolerance 1% RH | 15 A DC, 13 A DC or 11 A DC by variant | 20 - 56 V DC |
Included Models and Order Codes
Part numbers below are the ones that ship from stock most often. The three DCF 010 codes are the same device with three DC ratings and three operating temperature ceilings, so the code follows the ambient at the mounting position, not the load alone.
| Part number | Device | Setting range | Switching capacity | W x H x D | Mounting |
|---|---|---|---|---|---|
| 3118.000 | Rittal SK hygrostat | 50 - 100% RH | 5 (0.2) A AC, 20 W DC | 71 x 71 x 33.5 mm | 35 mm rail, or screw adapter on plate |
| 17207000000 | Pfannenberg FLZ 600 | 40 - 90% RH | N.O. 5 (0.2) A, N.C. 2 (0.2) A | 37 x 47 x 60 mm | Clip for 35 mm rail |
| 17218101000 | Pfannenberg FLZ 610, 230 V | 40 - 90% RH and 0 - 60 C | 8 (3) A at 240 V AC | 59 x 38 x 80.5 mm | Clip for 35 mm rail |
| 17218150000 | Pfannenberg FLZ 610, 115 V | 40 - 90% RH and 0 - 60 C | 8 (3) A at 120 V AC | 59 x 38 x 80.5 mm | Clip for 35 mm rail |
| 01245.0-00 | STEGO EFR 012 | 40 - 90% RH | 8 (1.6) A at 240 V AC, 100 W DC | 64.5 x 42 x 38 mm | Clip for 35 mm rail |
| 01012.0-20 | STEGO DCF 010, 15 A | 40 - 90% RH | 15 A DC, ambient to +40 C | 93 x 53 x 44 mm | Clip for 35 mm rail, 2 m sensor |
| 01012.0-21 | STEGO DCF 010, 13 A | 40 - 90% RH | 13 A DC, ambient to +50 C | 93 x 53 x 44 mm | Clip for 35 mm rail, 2 m sensor |
| 01012.0-22 | STEGO DCF 010, 11 A | 40 - 90% RH | 11 A DC, ambient to +60 C | 93 x 53 x 44 mm | Clip for 35 mm rail, 2 m sensor |
Setting the Control Loop
The table is the short version of the commissioning step: which unit, which set point and why. The numbers assume the heater is sized to lift the cabinet a few kelvin above ambient, which is the normal case for a PTC heater of 10 to 150 W.
| Cabinet and climate | Unit | Set point | Reason |
|---|---|---|---|
| Sealed cabinet, heater only, humid hall | SK 3118.000 | 65 - 70% RH | Leaves headroom below saturation |
| Cabinet opened several times per shift | FLZ 610 | 60% RH, heater 15 C | Humidity and temperature in one unit |
| Outdoor cabinet with day and night swing | EFR 012 | 70% RH | 5% RH differential avoids chattering |
| 24 V DC cabinet, no AC rail | DCF 010 | 65% RH | Switches the 24 V heater directly |
| Cold store door frame, frequent defrost | FLZ 600 | 60% RH | Mechanical unit, no supply needed |
| Cabinet with filter fan and heater | FLZ 610 | 55% RH, fan 35 C | Fan runs only above the temperature set point |
Key Features
Two setting ranges – 50 to 100 percent RH for Rittal units and 40 to 90 percent RH for Pfannenberg and STEGO units, so the set point has to be inside the range the unit actually offers.
Contact rating for inductive loads – 5 (0.2) A and 8 (1.6) A are stated with the inductive figure in brackets, which is the number that matters for a heater with a fan motor on the same circuit.
Switching differential stated – about 4 to 5 percent RH on mechanical units and 2 K plus 4 percent RH on the combined unit, which sets how often the heater cycles.
Hygrostat and thermostat in one housing – the FLZ 610 measures humidity and temperature independently, so one rail position covers both the heater and the fan.
DC versions with MOSFET output – the DCF 010 takes 20 to 56 V DC and switches up to 15 A DC, with an external sensor on a 2 m cable so the electronics sit away from the heater.
One rail, one footprint – every unit clips to 35 mm DIN rail to EN 60715, and the Rittal unit also takes a screw adapter for a mounting plate.
Applications
Hygrostats follow the moisture source, not the cabinet size. Three patterns repeat.
Switchgear cabinets in unheated halls – a heater on a hygrostat, so the busbars stay above dew point during the night and the morning switch-on does not flash over a wet insulator.
Outdoor telecom and traffic cabinets – an electronic unit with a 5 percent RH differential, holding the internal air dry without cycling the heater on every cloud.
Food and pharma wash-down areas – a sealed cabinet with a heater and a hygrostat, where the daily wash raises the external humidity and the internal surfaces are the coldest parts.
Hygrostats are quoted together with the heater or the fan they switch, and the SUPERB PCBA and the SUPERB PCB are checked against the same panel wiring schedule so the contact rating and the load match before the cabinet is assembled.
Sourcing and Cross-Reference
Match the contact to the heater, not to the label on the heater box. A 150 W heater at 230 V draws 0.65 A, well inside a 5 A contact, but a 1000 W heater draws 4.3 A and a fan on the same contact adds inrush. The bracket figure, not the headline figure, is the one to compare.
Decide AC or DC before the part number. A 24 V cabinet with a DC heater needs the DCF 010 class, because an AC hygrostat contact will not switch a DC load of that size without arcing.
Allow for the differential. A 5 percent RH differential on a 65 percent set point means the heater runs until the air reaches 70 percent and then waits, so the effective band is 5 percent wide. On a cabinet with a small volume that is a short cycle, and a wider differential is the cheaper answer than a bigger heater.
Keep the sensor in moving air. A unit mounted flat against the door reads the door temperature, and a cold door holds the contact closed long after the air has dried. Mount it on the rail or the plate, clear of the heater outlet. See lead time and availability when a heater and a controller have to ship together.
The SUPERB Assembly team mounts the hygrostat where the air moves, not on the door skin, because a sensor sitting against cold sheet metal reads low and the heater never comes on.
Q: Can one unit control both the heater and the cabinet fan?
A: Yes. Send the cabinet volume, the heater wattage and the supply voltage; the SUPERB Tech team quotes the hygrostat with a contact rating that covers the load.
Why Builders Buy Hygrostats From SUPERB
- Set point checked against the range: the 40 to 90 percent RH and 50 to 100 percent RH families are kept apart, so the set point asked for is inside the range supplied.
- AC and DC versions: the DC units cover 24 V and 48 V cabinets where an AC contact is the wrong part.
- Contact rating quoted with the load: the inductive figure is checked against the heater and fan before the part number is confirmed.
- Rail mounting and sensor length stated: the footprint and the 2 m sensor cable are in the quote, so the panel is not re-drilled on site.